12
EDS 820 IO-Link
Edition: 2020-04-21
HYDAC ELECTRONIC GMBH
Part No.: 669916 E
ATTENTION
Exceeding or falling below the measuring range leads to a limitation to the
corresponding upper or lower limit of the measuring range.
11.1.1
Two-point mode - Switch point setting (SP)
One switch point and one switch-back point can be set for each switching output. The
particular output will switch when the pre-set switch point is reached and then switch back
when the level drops below the switch-back point.
Example for switch point 1 (N/C and N/O function):
Abbreviations: "SP1", "SP2" = switch point 1 / switch point 2
"RP1", "RP2" = switch-back point 1 / switch-back point 2
"HNO",
= N/O when hysteresis function is active
"HNC"
= N/C when hysteresis function is active
NOTICE
It is only possible to set the switch point (SP) if it is higher than the respective
switch-back point (RP).
11.1.2
Window mode - Window function setting (Fno / Fnc)
The window function enables monitoring of a particular range. An upper and a lower
switch point which defines the range can be assigned to each switching output.
On
Normally open function
Off
On
Normally closed function
Off