Variable "SP States" index=72 id=V_SpStates
data type: 8-bit Record (subindex access not supported)
access rights: ro
dynamic
subindex
bit
offset
data type
allowed
values
default value
mod.
other var.
name
description
1
0
Boolean
false
Primary Value SP1
2
1
Boolean
false
Primary Value SP2
3
2
Boolean
false
Secondary Value SP1
V 1.3 only
4
3
Boolean
false
Secondary Value SP2
V 1.3 only
Octet 0
bit offset
7
6
5
4
3
2
1
0
subindex
/ / / / / /
/ / / / / /
/ / / / / /
/ / / / / /
4
3
2
1
Variable "Q1 Mapping" index=73 id=V_Q1Mapping
Variable "Q2 Mapping" index=74 id=V_Q2Mapping
data type: 8-bit UInteger
allowed values: 0 = Primary Value SP1, (Version 1.3 only : 1 = Secondary Value SP1)
default value: 0
access rights: rw
octet
0
bit offset
7 - 0
element bit
7 - 0
Variable "Primary Value Range" index=80 id=V_PrimaryValueRange
data type: 72-bit Record (subindex access not supported)
access rights: ro
subindex
bit
offset
data type
allowed
values
default
value
mod.
other var.
name
description
1
56
16-bit Integer
0
Lower Value
2
40
16-bit Integer
2500
Upper Value
3
32
8-bit Integer
1
Decimals
4
0
4-octet String
UTF-8
"bar"
Unit
Variable "Secondary Value Range" index=81 id=V_SecondaryValueRange (V1.3 only)
data type: 72-bit Record (subindex access not supported)
access rights: ro
subindex
bit
offset
data type
allowed
values
default
value
mod.
other var.
name
description
1
56
16-bit Integer
-250
Lower Value
V1.3 only
2
40
16-bit Integer
1000
Upper Value
V1.3 only
3
32
8-bit Integer
1
Decimals
V1.3 only
4
0
4-octet String
UTF-8
"C"
Unit
V1.3 only