14 / 27
Name (number), function
Adjustable value range
Description
Default value
Distance unit (P00b),
Length unit
Selectable values
Metric (EU):
−
m
−
cm
−
mm
−
custom unit
Imperial (US):
−
inch
−
ft
The unit of measurement for the transmitter when the distance and level are set.
If “custom unit” is selected, the unit uses the unit of length as the distance unit based on the value
specified in “User Unit.”
HyView setting:
“
Device Settings
” > “Application” > “
Engin
eering units”
VGF-DISPLAY:
MAIN MENU / BASIC SETUP / UNITS / ENGINEERING UNITS /
DISTANCE UNITS
m
Output unit,
volume (P02b)
Volume unit
Selectable values
Metric (EU):
−
liter
−
hl
−
m
3
−
million liters
Imperial (US):
−
gallon
−
ft
3
−
barrel
−
million gallons
The unit of the transmitted number when set to volume measurement. The device converts the
measured level into volume by calculation.
It is done by using a level-dependent (non-linear) function.
It also gives the unit of measure for the “Output” co
lumn in the VM table (OC).
HyView setting:
“
Device Settings
” > “Measurement configuration” > “Volume units”
VGF-DISPLAY:
MAIN MENU / BASIC SETUP / UNITS / ENGINEERING UNITS /
VOLUME UNITS
IT IS ONLY DISPLAYED IF THE PV IS VOLUME!
liter
Output unit,
Weight (P02a)
Weight unit
Selectable values
Metric (EU):
−
kg
−
ton
−
US ton
Imperial (US):
−
lb
−
US ton
−
metric ton
The unit of the transmitter number if the device is set for weight measurement. The device converts the
measured level into weight.
It is done by using a level-dependent (non-linear) function.
It also gives the unit of measure for the “Output” column in the VM table (OC).
HyView setting:
“
Device Settings
” > “Measurement configuration” > “Mass units”
VGF-DISPLAY:
MAIN MENU / BASIC SETUP / UNITS / ENGINEERING UNITS /
MASS UNITS
IT IS ONLY DISPLAYED IF THE PV IS MASS!
kg
Operating mode (P00a),
Measured medium property
Selectable values:
−
Liquid
−
Granular solid
−
Two interfacing liquids
The basic characteristic of the measured medium is set here. The measuring capabilities of the device
vary significantly depending on this characteristic of the medium (see specification).
HyView setting:
“
Device Settings
” > “Application” > “Operating mode”
VGF-DISPLAY:
MAIN MENU / BASIC SETUP / APPLICATION
Liquid medium
Unit system (P00d),
Temperature unit
Selectable values:
−
°C
−
°F
The unit of temperature measurement is selected here.
HyView setting:
“
Device Settings
” > “Measurement configuration” > “Temperature”
VGF-DISPLAY:
MAIN MENU / BASIC SETUP / UNITS / ENGINEERING UNITS /
TEMPERATURE UNITS
°C
Output function (P01ab),
Application mode
Selectable values
Metric (EU):
−
Distance
−
Level
−
Volume
−
Mass
−
Ullage volume
Set the physical quantity for the transmitted meter. The device measures distance. The other
quantities are calculated based on the specified tank parameters and material characteristics.
HyView setting:
“
Device Settings
” > “Measurement configuration” > “
Measurement mode (PV
source)”
VGF-DISPLAY:
MAIN MENU / MEASUREMENT CONFIG / PV. MODE
LEVEL
Custom Unit multiplier (P07)
User defined unit
(Length unit)
0.
001…100
The distance in "custom unit" is the distance in meters multiplied by P07 to get. The corresponding
setting field only appears or is active if "custom unit" is selected in the unit system.
The reference of the multiplier is meter, the value of the conversion factor must always be given in
relation to it.
For example, if the conversion factor is 10, then the new unit is 10 m (33 ft) or if the conversion factor
is 0.1, the new unit is 0.1 m.
HyView setting:
“
Device Settings
” > “Application” > “
Conversion factor
”
VGF-DISPLAY:
no adjustment available
1.000
Select echo (P25)
Selectable values:
−
Highest amplitude
−
First
−
Second
−
Last
In problematic cases, it is possible to choose between the echoes created during the measurement in
order to ensure a stable measurement and transmission.
HyView setting:
“
Device Settings
” > “Measurement optimalization” > “Selection of Echo…”
VGF-DISPLAY:
no adjustment available
Highest amplitude
Filling speed (P26)
0.
1…900m/h
(0.33
…
2950 ft/h)
The maximum rate of rise in the tank during filling. Entering it correctly increases the reliability of the
measurement during charging.
HyView setting:
“
Device Settings
” > “Measurement optimalization” > “Level elevation rate …”
VGF-DISPLAY:
no adjustment available
900m/h (2950 ft/h)
Emptying speed (P27)
0.1…900m/h
(0.33
…
2950 ft/h)
The maximum rate of dropping in the tank during emptying. Entering it correctly makes the
measurement more reliable during emptying.
900m/h (2950 ft/h)