6.3.

Use the AutoSet function to scan and program the unit High- or Low-Level to the distance detected. After the scan you will be prompted to accept the distance 
measured. The High and Low level can also be manually adjusted in 'Setup'. 

 
 
 
 
 
 

 

A

DVANCED 

S

ETTINGS

 

6.4.

 

P

ARAMETER

 

D

ESCRIPTION

 

O

PTIONS

 

Comms 

Comms Adjust HART protocol settings 

Device ID 

Default 1 

BaudRate 

1200 

Blanking 

Blanking is a dead-band / non measured range. The unit cannot 

measure within this range 

Adjustable - recommended default 

250mm (10") 

Tracking 

Adjust tracking response time for application. The faster the tracking, the 

more responsive the measurement is, but the less smooth the output 

signal 

InstaTrack provides pulse by pulse live measurement

 

Slow 

Medium 

Fast 

InstaTrack 

Mapping 

Mapping creates a digital 'map' of false echoes caused by problem 

mounting and structures. Select 'ExecuteMap' to set a mapped distance, 

conduct or delete Mapping. Select 'MappedDist' to view a previously 

mapped distance 

MappedDist 

 

ExecuteMap 

Set Map Dist 

EchoSize 

The unit will target this echo size (measured in signal voltage) during 

operation. High values can increase stability but make the unit more 

susceptible to false echoes. Lower values can make the unit less 

sensitive and less likely to see false echoes 

0.4 - 2.49V 

Default 0.59V 

Analog 

Adjust Analog output. Switch from 4-20mA to 20-4mA and fine tune both 

4mA current and 20mA current 

4-20mA 
20-4mA 

Tune 4mA 

Tune 20mA 

Sensitivity 

Increase or decrease the unit Automatic Sensitivity Control range. 20 is 

maximum / highest sensitivity 

0: Lowest 

10: Default 

20: Highest 

WaveBoost 

WaveBoost adds additional echo amplification on top of the Automatic 

Sensitivity Control. WaveBoost should only be used if maximum 

Sensitivity is not sufficient 

0: Lowest (default) 

20: Maximum 

Factry Reset 

Reset Restore all parameters to factory default 

Yes / No 

Device Info 

Displays product type, serial number & software revision 

 

Lock Code 

Enable / Disable lock code 

If enabled, select lock code number 

Enable / Disable 
Default Disabled 

1-200 

 

7.

 

HART UNIVERSAL / COMMON PRACTICE COMMAND LIST 

The 

Microflex-D

 supports the following HART Universal and Common commands: 

C

OMMAND 

N

O

F

UNCTION

 

Read unique identifier 

Read Primary Variable 

Read current and percent of range 

Read current and four predefined dynamic variables 

Write polling address 

Read loop configuration 

Read Dynamic Variable Classifications 

11 

Read unique ident. associated with tag 

12 

Read message 

13 

Read Tag, Description, Date 

14 

Read PV sensor information 

15 

Read output information 

16 

Read final assembly number 

17 

Write message 

18 

Write Tag, Description, Date 

19 

Write final assembly number 

20 

Read Long Tag 

34 

Write damping value 

35 

Write range values 

44 

Write PV units 

57 

Read unit tag, descriptor, date 

58 

Write unit tag, descriptor, date 

59 

Write number of response preambles 

109 

Burst mode control 

         Autoset 
►  Set Lo Level

 

        

Set Hi Level 

 

Set Lo Level 
 

        

SCANNING 

 

Set Lo Level 
►  No

 

        

Yes 

2.597m 

Содержание MICROFLEX-D Series

Страница 1: ...C LEVEL TRANSMITTER USER MANUAL Hycontrol Ltd Larchwood House Orchard Street Redditch Worcestershire UK B98 7DP Tel 44 0 1527 406800 Fax 44 0 1527 406810 Email sales hycontrol com Web www hycontrol com Company registered in England No 1755684 ...

Страница 2: ... SOFTWARE 6 6 1 MAIN MENU 6 6 2 SETUP 6 5 3 AUTOSET 7 5 4 ADVANCED SETTINGS 7 7 HART UNIVERSAL COMMON PRACTICE COMMAND LIST 7 8 TROUBLESHOOTING 8 8 1 UNIT IS DISPLAYING INCORRECT DISTANCE 8 8 2 ANALOGUE TREND IS ERRATIC UNSTABLE 8 8 3 UNIT IS LOCKED UP OR FLAT LINE MEASUREMENT 8 8 4 PLC INDICATION DOES NOT MATCH MEASUREMENT 8 8 5 AUTOSET FAILS 8 9 ACCESSORIES 8 10 SPECIFICATIONS 9 ...

Страница 3: ...flected from the surface of the liquid being measured The reflected signal is processed using specially developed software to enhance the correct signal and reject false echoes The principle of operation is often referred to as time of flight The time it takes the ultrasonic pulse to travel from and back to the transducer is directly proportional to the distance travelled An automatic sensitivity ...

Страница 4: ...4 10 3 DIMENSIONS FLANGE 3 1 2 ANSI Polypropylene Flange for NPT threaded units or 2 ANSI Polypropylene Flange for BSPT threaded units 4 WIRING ...

Страница 5: ... with the unit measurement Do not mount in the centre of a curved roof to avoid the potential of parabolic echoes Avoid mounting in direct sunlight The following are examples of common INCORRECT mountings which can prevent the unit from operating correctly Do NOT mount near infeed Do NOT mount cone or transducer face above roofline Do NOT mount over or adjacent to any obstacles Do NOT mount at an ...

Страница 6: ...djust parameters 6 COMMISSIONING SOFTWARE Start up the unit The Microflex D uses automatic sensitivity control to detect and maintain the level After applying power to the unit allow 20 30 seconds for the unit to adjust to the application For best results ensure there is a liquid level present in the application or a flat surface below the transducer MAIN MENU 6 1 To access the Main menu press CAL...

Страница 7: ... 4mA current and 20mA current 4 20mA 20 4mA Tune 4mA Tune 20mA Sensitivity Increase or decrease the unit Automatic Sensitivity Control range 20 is maximum highest sensitivity 0 Lowest 10 Default 20 Highest WaveBoost WaveBoost adds additional echo amplification on top of the Automatic Sensitivity Control WaveBoost should only be used if maximum Sensitivity is not sufficient 0 Lowest default 20 Maxi...

Страница 8: ...st Re locate the installation to avoid the interfering object If the unit is locked lower than the real level confirm the application is not within Blanking distance Increase Sensitivity WaveBoost until the unit measures correct level Tracking speed may be too slow for the application Increase the Tracking speed PLC indication does not match measurement Connect a Multimeter in series with the powe...

Страница 9: ...Accuracy 0 25 of maximum range Operating Temperature 40 C to 60 C 40 F to 140 F Maximum Operating Pressure 0 5 to 3 bar 0 44 PSI Automatic Temperature Compensation Yes Beam Angle 7 Materials Transducer PVDF Housing Powder coated aluminium Display 4 line graphic display 128 x 64 Keypad 4 keys CAL RUN UP DOWN Memory 10 years data retention Enclosure Sealing IP67 Cable Entries M20 cable glands Mounti...

Страница 10: ...HYCONTROL reserves the right to change technical data without notice ...

Отзывы: