Hycontrol MICROFLEX-D Series Скачать руководство пользователя страница 3

3 / 10 

Thank you for choosing a HYCONTROL instrument. 

We are sure that you will be satisfied throughout its use!

 

 

1.

 

INTRODUCTION 

Application 

The 

Microflex-D

  from 

Hycontrol

  is  a  compact,  loop-powered  ultrasonic  level  transmitter  for  continuous  measurement  of  liquids.  Despite  the  unit  being 

positioned at a budget price-point it does not compromise on quality and provides effortless and intuitive operation. Easy and flexible mounting, combined 
with high chemical compatibility and a measuring range of 8 metres (or 12 metres in the case of the 

ER 

model), makes the 

Microflex-D

 suitable for multiple 

applications in a wide range of industries. 

 

Operation principle

 

The 

Microflex-D

 emits an ultrasonic pulse which is reflected from the surface of the liquid being measured. The reflected signal is processed using specially 

developed software to enhance the correct signal and reject false echoes. The principle of operation is often referred to as ‘time-of-flight’. The time it takes 
the ultrasonic pulse to travel from and back to the transducer is directly proportional to the distance travelled. 
An automatic sensitivity control allows the unit to dynamically adjust and improve the received echoes for the best possible measurement outcome. 
 
 

 

2.

 

MODEL TYPES 

MICROFLEX-DB

 – Microflex-D with 2” BSPT thread, 8m (26’) range 

MICROFLEX-DN 

– Microflex-D with 2” NPT thread, 8m (26’) range 

MICROFLEX-DBER

 – Microflex-D with 2” BSPT thread, extended 12m (40’) range 

MICROFLEX-DNER 

– Microflex-D with 2” NPT thread, extended 12m (40’) range 

 

 

                    

 

 

A - Removable lid with viewing window 
 
B - Electronics housing 
 
C - M20 cable gland 
 
D – 2” NPT or BSPT thread 
 
E - Transducer face 

Содержание MICROFLEX-D Series

Страница 1: ...C LEVEL TRANSMITTER USER MANUAL Hycontrol Ltd Larchwood House Orchard Street Redditch Worcestershire UK B98 7DP Tel 44 0 1527 406800 Fax 44 0 1527 406810 Email sales hycontrol com Web www hycontrol com Company registered in England No 1755684 ...

Страница 2: ... SOFTWARE 6 6 1 MAIN MENU 6 6 2 SETUP 6 5 3 AUTOSET 7 5 4 ADVANCED SETTINGS 7 7 HART UNIVERSAL COMMON PRACTICE COMMAND LIST 7 8 TROUBLESHOOTING 8 8 1 UNIT IS DISPLAYING INCORRECT DISTANCE 8 8 2 ANALOGUE TREND IS ERRATIC UNSTABLE 8 8 3 UNIT IS LOCKED UP OR FLAT LINE MEASUREMENT 8 8 4 PLC INDICATION DOES NOT MATCH MEASUREMENT 8 8 5 AUTOSET FAILS 8 9 ACCESSORIES 8 10 SPECIFICATIONS 9 ...

Страница 3: ...flected from the surface of the liquid being measured The reflected signal is processed using specially developed software to enhance the correct signal and reject false echoes The principle of operation is often referred to as time of flight The time it takes the ultrasonic pulse to travel from and back to the transducer is directly proportional to the distance travelled An automatic sensitivity ...

Страница 4: ...4 10 3 DIMENSIONS FLANGE 3 1 2 ANSI Polypropylene Flange for NPT threaded units or 2 ANSI Polypropylene Flange for BSPT threaded units 4 WIRING ...

Страница 5: ... with the unit measurement Do not mount in the centre of a curved roof to avoid the potential of parabolic echoes Avoid mounting in direct sunlight The following are examples of common INCORRECT mountings which can prevent the unit from operating correctly Do NOT mount near infeed Do NOT mount cone or transducer face above roofline Do NOT mount over or adjacent to any obstacles Do NOT mount at an ...

Страница 6: ...djust parameters 6 COMMISSIONING SOFTWARE Start up the unit The Microflex D uses automatic sensitivity control to detect and maintain the level After applying power to the unit allow 20 30 seconds for the unit to adjust to the application For best results ensure there is a liquid level present in the application or a flat surface below the transducer MAIN MENU 6 1 To access the Main menu press CAL...

Страница 7: ... 4mA current and 20mA current 4 20mA 20 4mA Tune 4mA Tune 20mA Sensitivity Increase or decrease the unit Automatic Sensitivity Control range 20 is maximum highest sensitivity 0 Lowest 10 Default 20 Highest WaveBoost WaveBoost adds additional echo amplification on top of the Automatic Sensitivity Control WaveBoost should only be used if maximum Sensitivity is not sufficient 0 Lowest default 20 Maxi...

Страница 8: ...st Re locate the installation to avoid the interfering object If the unit is locked lower than the real level confirm the application is not within Blanking distance Increase Sensitivity WaveBoost until the unit measures correct level Tracking speed may be too slow for the application Increase the Tracking speed PLC indication does not match measurement Connect a Multimeter in series with the powe...

Страница 9: ...Accuracy 0 25 of maximum range Operating Temperature 40 C to 60 C 40 F to 140 F Maximum Operating Pressure 0 5 to 3 bar 0 44 PSI Automatic Temperature Compensation Yes Beam Angle 7 Materials Transducer PVDF Housing Powder coated aluminium Display 4 line graphic display 128 x 64 Keypad 4 keys CAL RUN UP DOWN Memory 10 years data retention Enclosure Sealing IP67 Cable Entries M20 cable glands Mounti...

Страница 10: ...HYCONTROL reserves the right to change technical data without notice ...

Отзывы: