22
Problem: Down draft on chimney caused by one or more of the following.
Possible Causes:
Remedies:
• This problem may occur in factory built flues because the insulation
has settled or a seam has ruptured. In masonry flues, mortar loss
may be causing seepage of cooler outside air into the stack. Check
entire flue for structural integrity and leakage. Correct or repair as
needed, or replace or re-line the chimney.
• Remove obstruction.
• Increase chimney height.
• Flue has a cold spot which
inhibits exhaust discharge from
rising properly.
• There is an obstruction outside
chimney, such as a tree.
• Flue is located too close to the
peak of the roof or does not rise
above it to provide the proper
draft.
9.
Problem: Odor detected in home during initial firing.
• There is an oily film that remains
on
the steel after the manufacturing
process. Firing the
furance has
raised the temperature of the fire
box to a level that is
sufficient to
vaporize the residue.
• The odor should disappear after a few hours of usage.
Possible Causes:
Remedies:
10.
Problem: Excessive smoke discharge from fuel door during reloading.
Possible Causes:
Remedies:
11.
• See #6.
• See #6.
• See #6.
• See #9.
• Excessively long stove pipe run
from furnace flue.
• Too many elbows.
• Insufficient draft.
• Excessive smoke accumulation.