General Information 

The Fire Chief EPA-

Certifi

ed Furnace has been engineered to accommodate the heating requirements of the average sized home, even 

during winter’s coldest months.  It is constructed with high grade, heavy gauge steel and is continuously welded to assure the highest 

structural strength.  In addition, the firebox is lined with insulated stainless steel panels to ensure many years of energy efficient service. 

The design of the secondary combustion chamber increases fuel efficiency by creating a “secondary burn” of smoke and wood gases 

before they are vented up the chimney. The cast iron doors are custom fitted to provide an airtight seal, greatly extending the burn time 

and ensuring maximum efficiency in fuel consumption.  The heavy-gauge cast iron grate, designed for maximum heat transfer, allows for 

convenient ash removal and reduced maintenance.

For total comfort and convenience, a thermostatically controlled 

D

raft 

B

lower 

and fan limit controlled Circulation Blower

 

are

 included.  

These fully automatic components furnish rapid heat disbursement throughout your home, minimizing recovery time when the wall 

thermostat demands heat.

All of these features are standard, offering you the most efficient, durable and affordable indoor wood burning furnace.

Efficiency was determined using the higher heating value of the fuel per B415.1-10 testing requirements. Dry seasoned wood will develop 

greater BTU output. A well-insulated dwelling will always lead to better results and overall improved fuel usage efficiency.

Your Fire Chief Furnace is designed to be either a supplemental or central heating source for your home.  This wood burning furnace may 

be installed in parallel with a properly operating electric, gas or oil-fired central furnace, listed or certified in accordance with a nationally 

recognized safety standard, and within clearances specified on the nameplate.  When in a parallel installation the static pressure of the 

central furnace plenum may not exceed 0.15 water column inches and the maximum setting on central furnace limit switch is 182°F.  With 

the Fire Chief Furnace in an “Interconnection Arrangement”

your furnace should be upstream of the central furnace.  The Fire Chief 

Furnace warm air supply should never be connected to return air for the central furnace.  A qualified installer should perform the 

installation.

IMPORTANT:  FOR TECHNICAL SUPPORT OR CUSTOMER SERVICE 

ISSUES, DO NOT RETURN TO THE DEALER

THE DEALER DOES NOT HAVE 

REPLACEMENT PARTS

.

 CALL 1-800-875-4788.

Forced Hot Air Circulation:

The plenum size of your Fire Chief Furnace must not be reduced to less than 100 square inches, and must provide a minimum of 

18 inches between the top of your Fire Chief Furnace and the main trunk connection.  

Do not modify the outer shell of the furnace at any 

time.  

The plenum attached to the furnace must be constructed of metal.  The warm air supply duct system should be constructed of 

materials with a minimum temperature rating of 250° Fahrenheit.

Clearances:

Unit must be placed on a non-combustible floor.  This floor must extend at least 16 inches in front, 8 inches on either side of fuel loading 

and ash removal doors, underneath the chimney connector and must extend 2 inches on either side of the chimney connector.  The 

furnace must maintain the following clearances to combustibles:

• Heat plenum = 2 inches
• Chimney connector = 18 inches
• Front = 48 inches
• Rear = 12 inches
• Sides = 6 inches
• Main furnace = 12 inches

These are minimum clearances and should be strictly followed.  In the case of a power outage, a dangerous level of heat accumulation 

may develop.  Do not store fuel or other combustible materials within installation clearances.

Содержание Fire Chief FC1500

Страница 1: ...D BURNING INDOOR FURNACE MODELS FC1500 FC1700 Manufactured by Fire Chief Industries 10950 Linpage Place Saint Louis MO 63132 1 800 875 4788 MADE IN USA Certified to UL391 Sept 2010 CSA B366 1 2014 Rev...

Страница 2: ...This Page Intentionally Blank...

Страница 3: ...that is properly cut and stored to dry will produce more BTUs and higher heat output than wood that has a higher moisture content Wood with higher moisture content will create creosote in the chimney...

Страница 4: ...nsportation Damage Every effort has been made to ensure that your Fire Chief Furnace will arrive in perfect condition Any visible damage should be noted on the freight bill at the time of delivery If...

Страница 5: ...Chimney Fire Warning 13 Power Failure 14 Furnace Diagram with Parts List 15 Grate System Diagram FC1500 16 Grate System Diagram FC1700 16 Blower Motor Assembly Diagram 17 Wiring Diagram 18 Troublesho...

Страница 6: ...or oil fired central furnace listed or certified in accordance with a nationally recognized safety standard and within clearances specified on the nameplate When in a parallel installation the static...

Страница 7: ...t buildup in the furnace causing the blower to short cycle and damage the blower motor and will not be covered under warranty This is not a down draft furnance and not to be installed as one If you do...

Страница 8: ...ion blower using 4 20 bolts and nuts Line up the blower with the pre drilled holes on the backside of the furnace firmly attach with the screws provided 2 Attach blower to the left and right mounting...

Страница 9: ...6 8 sheet metal screws provided 6 Top Panel A 8 Sheet Metal Screw Bottom Panel C Side Panel B Side Panel B 4 Position the assembled filter box on rear of furnace supporting it firmly up to electrical...

Страница 10: ...s of your choice of chimney type for models FC1500 and FC1700 a minimum 6 inch diameter chimney is needed In order to create the most effective draft the chimney size should not exceed 12 inches with...

Страница 11: ...charge When using a brick chimney you must line the entire chimney with stainless steel liner The liner must be 6 for the FC1500 and FC1700 The diameter of the chimney stack should be consistent throu...

Страница 12: ...ESS THAN 6 inches 150mm ON OIL ELECTRIC OR GAS FURNACES DO NOT CONNECT TO A DOWNFLOW FURNACE DO NOT CONNECT DUCTWORK SO THAT A REVERSE FLOW IS POSSIBLE OPERATE THE GAS OIL ELECTRIC FURNACE PERIODICALL...

Страница 13: ...stacked to provide a free flow of air between the logs thus allowing more rapid seasoning of the wood If wood is stored outdoors it should be completely covered year round to protect it from moisture...

Страница 14: ...ated with chemical preservatives in your furnace The combustion of these substances may release harmful toxic gases Do Not Burn Garbage Lawn clippings or yard waste Materials containing rubber includi...

Страница 15: ...urs you are over firing your furnace This type of occurrence is usually symptomatic of heat demands in excess of furnace capacity Contact an authorized professional to determine if your Fire Chief Fur...

Страница 16: ...r desired setting If you are unable to detect or hear the speed change when you move the switch selector to a different setting it doesn t mean the blower motor didn t change speeds Most blower motors...

Страница 17: ...s damaged due to power failure NOTE OVER FIRING OR DELIBERATE ABUSE CAN EASILY BE DETERMINED UPON INSPECTION AND WILL VOID THE WARRANTY Always keep your wood covered year round Dry wood will produce a...

Страница 18: ...WAF 002 WAF 002 7 1 ELECTRICAL CONTROL ASSEMBLY INDOOR WAF IECA WAF IECA 8 1 BLOWER ASSEMBLY FC3SPMOTOR FC3SPMOTOR 8a 1 BLOWER MOTOR FCDD037P FCDD037P 8b 1 BLOWER HOUSING FCBH FCBH 9 1 FILTER BOX KIT...

Страница 19: ...RT 2b 1 ROLLER GRATE EXTENSION BASE SHORT 4 1 FC000 ROLLER GRATE EXTENSION SHORT 5 1 FC000 ROLLER GRATE 6 6 FIRE BRICK FC1700 PARTS LIST ITEM QTY PART DESCRIPTION 1 1 FC000 ROLLER GRATE HANDLE 2 1 ROL...

Страница 20: ...Blower Motor Assembly Diagram 2 1 2 3 17 PARTS LIST PART DESCRIPTION QTY ITEM BLOWER HOUSING ASSEMBLY 1 1 BLOWER MOTOR 1 2 MOTOR CAPACITOR 1 3 2 PART NUMBER FCBH FC3610J370 FC3SPMK...

Страница 21: ...C TRANSFORMER RELAY DRAFT MOTOR ON OFF SWITCH 3 SPEED SWITCH DRAFT BLOWER MOTOR FCDB 3 SPEED BLOWER MOTOR FC3SPMOTOR BLUE MED RED LOW BLACK HI 120V AC POWER SUPPLY WHITE BLACK GREEN BLACK WHITE FCDBSW...

Страница 22: ...ibrates during operation Screw on squirrel cage is not tight Check squirrel cage alignment and position so that it does not drag on the housing during rotation then tighten the screw sufficiently to f...

Страница 23: ...n on page 3 Possible Causes Remedies Excessively long run of stove pipe from furnace to flue Relocate the furnace so the horizontal run does not exceed 5 feet and has a 2 inch rise per foot The run sh...

Страница 24: ...hermostat to call for more heat more often which will initiate the running of the draft blower Consequently the fires will be hotter thereby reducing the accumulation of creosote Install flue gas ther...

Страница 25: ...y There is an obstruction outside chimney such as a tree Flue is located too close to the peak of the roof or does not rise above it to provide the proper draft 9 Problem Odor detected in home during...

Страница 26: ...rmation in the manual relating to the proper installation procedures or contact your local heating and cooling contractor Refer to information in the manual relating to the proper ducting procedures o...

Страница 27: ...e appliance part to be defective He or she must submit a written statement to Fire Chief Industries detailing an assessment of the problem This assessment MUST be accompanied by substantiating proof o...

Страница 28: ...ssing Warranty Claims Please reference this page when requesting Customer Service Customer Information Purchased From Name Dealer Store Street Dealer Store Phone City Date Purchased State Zip Installe...

Отзывы: