Self-contained emergency lighting luminaire
9/16
IMM - UTILIGHT SGN LED - ST_AT_CT - PL_EN V01
UTILIGHT SGN LED
IP40 IP54
EN
INSTALLATION AND MAINTENANCE MANUAL
MOUNTING TYPE
W140
–
back to the wall
C142
–
directly to the ceiling
C142 + W141
–
semaphore
C142 + C143
–
suspended with cords and easy height adjustment
C142 + C144
–
suspended with cords or chains
C145
–
recessed
C146
–
directly to the ceiling or back to the wall with a pos
-
sibility to connecting surface wiring
SYSTEM VARIANT
ST
–
STANDARD – tests commissioned manually (see
menu and magnetic switch)
AT
–
AUTOTEST – internal components, battery and light
source tests being performed automatically
CT
–
CENTRALTEST – internal components, battery and
light source tests being performed on command
from the main unit of central management
system H-300
SIZE OF EXIT SIGN
20x10
–
ISO 7010 compliant exit sign with the dimensions of 20x10 cm and a viewing distance of 20 meters
30x15
–
ISO 7010 compliant exit sign with the dimensions of 30x15 cm and a viewing distance of 30 meters
40x20
–
ISO 7010 compliant exit sign with the dimensions of 40x20 cm and a viewing distance of 40 meters
TEST
The microcontroller-based control and test unit performs automatically (AT) or on order from the central management
system (CT) or by manual execution (ST) two types of tests:
TEST A
–
internal components and light source test lasting 60 seconds – performed every 30 days for the AT system variant
TEST B
–
internal components, light source and operation duration test (till the battery is fully discharged) – performed every 360 days for AT
system variant
TECHNICAL DATA
Supply voltage
230V AC 50/60Hz
Power consumption
M:
1)
charging – 4W, standby – 2W
NM:
2)
charging – 2.3W, standby – 0.2W
Power factor
0.4
Protection class
I
Ingress protection
IP40, IP54
3)
Light source type
LED strip
4)
Light source temperature
5000K
Colour rendering index
70
Light source supply power
1W
Light source lifespan
> 50 000h
Battery type
Li-Ion
Battery voltage
3,7V
Battery capacity
0.7Ah; 2.2Ah; 4.4Ah
Battery recharging time
12h
Emergency operation time
1h; 3h; 8h
Ambient temperature range
+5 – +40ºC
Supply cable cross-section area
0.5 – 2.5mm
2
Supply cable diameter
≤ 17mm
Communication cable diameter
<7mm
Suitable for through wiring
YES
Suitable for surface wiring
YES (C146 only)
1)
M
– maintained mode;
2)
NM
– non-maintained mode;
3)
Special construction, version 0054;
4)
Non-exchangeable but serviceable light source.
SAFETY
• During the installation and usage of emergency luminaires, follow the national safety rules as well as generally accepted technical rules.
• Supply voltage should never be removed from the permanent phase by any external switches, relays or contactors (BMS, wall switch, etc.).
• During usage of emergency luminaires keep a register of inspection reports.
• Luminaire installation or maintenance has to be preceded by turning off the power supply and battery.
• Ensure that all foreign bodies are removed before the luminaire power is switched on.
• The luminaire is to be used undamaged and in accordance with specifications.
• The luminaire designed for use inside the building.
The above-mentioned luminaire is a fire protection equipment and therefore falls within relevant standards and regulations.
NOT OBEYING THE SAFETY INSTRUCTIONS AND RECOMMENDATIONS CAN CAUSE LIFE THREAT OR EVEN DEATH
NOT OBEYING THIS INSTRUCTION MANUAL CAN RESULT IN LUMINAIRE DAMAGE AND LOSS OF WARRANTY