Operation of two Hy-Security gate operators as a master/slave pair is simply a matter of correctly
interconnecting the two control circuits. Join the following four wires from the master operator to the slave:
Terminal #1 master to terminal #1 slave,
Terminal #3 master to terminal #3 slave,
Terminal #4 master to terminal #4 slave,
*Terminal #10 master to terminal #10 slave
All stop control inputs must be connected to the master operator only. The slave operator must not have any
connection between terminal #2 and terminal #4, such as a stop button or jumper.
*On DC battery powered operators, interconnect the black wires (-) to the on/off switch instead of the #10
wires. This prevents one operator from powering the other when the disconnect switch is off.