16
adjusted among 0.5,1.0,1.5,2.0,2.5……9.5
~
10KV, pressing "ESC",
the cursor would go to the first line, and then pressing “
”, it
would be moved down to the " □ Start to measure" which is shown
in Figure 7.
⑤
Turning on the "high voltage allowable" switch, pressing
"ENT", the instrument would
begin to produce high voltage output accompanied by the hint
sound of "beep", at this time, the screen would show " It is being
measured, please wait…" which is shown in Figure 8.
⑥
After about 40 seconds, the measurement would be
completed. The high voltage would be cut off automatically and the
screen would display the measurement results, which is shown in
Figure 9.
It is being measured,
please wait…
Dielectric loss:
tg
δ
=0.42%
Capacitance
: 1000P
Measuring method
D
Connection mode
N
Measuring voltage
10KV
□
Start to measure
Frequency:
W
Connection mode: N
Voltage
:
10KV
Dielectric loss
:
tg
δ
=0.42%
C
apacitance
:
1000P
Figure 7 Start to measure
Figure 8 Measuring
Figure 9 Measurement Result Figure
Figure 10 Printing Results