Protocol™ Installation and
Service Manual
will re-energize the solenoid when the condensing temperature reaches 65
°
F. Consult
Engineering representative if adjustment of the T-STAT control is required.
FIELD PIPING & TXV SIZING
Besides standard discharge lines, the liquid return line from the condenser
must
also be
piped back to the unit when remote air-cooled units are used with low temp cases.
If the unit has low and medium temp suction groups, the protocol unit will have TWO
liquid lines leaving the unit- one for medium temp cases and one for low temp cases.
Only the liquid to the low temp cases will be subcooled to 50
°
F. The liquid to the
medium temp cases will be at the condensing temperature.
Units with low temp ZFKV compressors
must insulate
the liquid line to the low temp
cases/walk-ins coolers since the refrigerant is at a subcooled temperature. Also, suction
line sizing should take into account the lower liquid temperature.
When expansion valves are selected for the cases, they should be sized for a liquid
temperature of 50
°
F due to subcooling.
SERVICE
There is a shut off valve before the TXV for service of solenoids, the TXV, or the EPR in
the Low Temp economizer loop. Shut off valves are also present at each compressor
injection port.
87
Содержание Proto-Aire
Страница 1: ...9 20 2005 Installation Manual Hussmann Part 0385841 ...
Страница 11: ...Protocol Installation and Service Manual TYPICAL PIPING ELECTRICAL HOOKUP Vertical Units 7 ...
Страница 12: ...Protocol Installation and Service Manual 8 ...
Страница 13: ...Protocol Installation and Service Manual 9 ...
Страница 14: ...Protocol Installation and Service Manual 10 ...
Страница 15: ...Protocol Installation and Service Manual 11 ...
Страница 16: ...Protocol Installation and Service Manual 12 ...
Страница 17: ...Protocol Installation and Service Manual 13 ...
Страница 18: ...Protocol Installation and Service Manual 14 ...
Страница 19: ...Protocol Installation and Service Manual 15 ...
Страница 20: ...Protocol Installation and Service Manual 16 ...
Страница 21: ...Protocol Installation and Service Manual 17 ...
Страница 22: ...Protocol Installation and Service Manual 18 ...
Страница 23: ...Protocol Installation and Service Manual 19 ...
Страница 24: ...Protocol Installation and Service Manual Horizontal Units 20 ...
Страница 25: ...Protocol Installation and Service Manual 21 ...
Страница 26: ...Protocol Installation and Service Manual 22 ...
Страница 27: ...Protocol Installation and Service Manual 23 ...
Страница 28: ...Protocol Installation and Service Manual 24 ...
Страница 29: ...Protocol Installation and Service Manual 25 ...
Страница 30: ...Protocol Installation and Service Manual 26 ...
Страница 31: ...Protocol Installation and Service Manual 27 ...
Страница 32: ...Protocol Installation and Service Manual 28 ...
Страница 33: ...Protocol Installation and Service Manual 29 ...
Страница 34: ...Protocol Installation and Service Manual 30 ...
Страница 35: ...Protocol Installation and Service Manual 31 ...
Страница 36: ...Protocol Installation and Service Manual 32 ...
Страница 37: ...Protocol Installation and Service Manual Proto_Aire Units 33 ...
Страница 38: ...Protocol Installation and Service Manual 34 ...
Страница 39: ...Protocol Installation and Service Manual 35 ...
Страница 40: ...Protocol Installation and Service Manual 36 ...
Страница 41: ...Protocol Installation and Service Manual 37 ...
Страница 42: ...Protocol Installation and Service Manual 38 ...
Страница 43: ...Protocol Installation and Service Manual 39 ...
Страница 58: ...Protocol Installation and Service Manual Very Large Box Very Large Box Pump Station Water Cooled Condenser 54 ...
Страница 62: ...Protocol Installation and Service Manual 58 ...
Страница 68: ...Protocol Installation and Service Manual Electrical Legend 64 ...
Страница 69: ...Protocol Installation and Service Manual Main Power Wiring 208V Two Wide Protocol 65 ...
Страница 70: ...Protocol Installation and Service Manual 208V 5 or 6 Compressor Protocol 66 ...
Страница 71: ...Protocol Installation and Service Manual 460V Two Wide Protocol 67 ...
Страница 72: ...Protocol Installation and Service Manual 460V 5 or 6 Compressor Protocol 68 ...
Страница 73: ...Protocol Installation and Service Manual 460V Two Wide Protocol with Factory installed transformer 69 ...
Страница 74: ...Protocol Installation and Service Manual 460V Two Wide Protocol with Field supplied transformer 70 ...
Страница 75: ...Protocol Installation and Service Manual 460V 5 or 6 Compressor Protocol with Field supplied transformer 71 ...
Страница 76: ...Protocol Installation and Service Manual 600V Two Wide Protocol 72 ...
Страница 77: ...Protocol Installation and Service Manual 600V 5 or 6 Compressor Protocol 73 ...
Страница 78: ...Protocol Installation and Service Manual 600V Two Wide Protocol with Field supplied transformer 74 ...
Страница 81: ...Protocol Installation and Service Manual Control and Compressor Wiring PCS without Vapor Wiring 77 ...
Страница 82: ...Protocol Installation and Service Manual PCS with Vapor Wiring 78 ...
Страница 83: ...Protocol Installation and Service Manual CPC Danfoss Comtrol without Vapor Wiring 79 ...
Страница 84: ...Protocol Installation and Service Manual CPC Danfoss Comtrol with Vapor Wiring 80 ...
Страница 85: ...Protocol Installation and Service Manual Controller Wiring PCS 81 ...
Страница 86: ...Protocol Installation and Service Manual CPC 82 ...
Страница 87: ...Protocol Installation and Service Manual CPC Einstein 83 ...
Страница 88: ...Protocol Installation and Service Manual Danfoss 84 ...
Страница 89: ...Protocol Installation and Service Manual Comtrol 85 ...
Страница 99: ...Protocol Installation and Service Manual 95 ...
Страница 100: ...Protocol Installation and Service Manual 96 ...
Страница 101: ...Protocol Installation and Service Manual POWERLINK Operation 97 ...