3086855_C
3-3
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
MPCETNM6S
Product will be degraded and may spoil if
allowed to sit in a non-refrigerated area.
DO3: For either fans or refrigeration 2
Fans: The relay will cut in when the fans
have to operate Refrigeration 2: The relay will
cut in
when refrigeration step 2 has to
be cut in
DO4: For either alarm, rail heat, light or hotgas
defrost
Alarm: Cf. diagram. The relay is cut in
during normal operation and cuts out in
alarm situations and when the controller is
dead (de-energised)
Rail heat: The relay cuts in when rail heat
is to operate
Light: The relay cuts in when the light has
to be switched on Hotgas defrost: See dia
gram. The relay will cut out when defrost
has to be done
Data communication
The controller is available in several versions
where data communication can be carried out
with one of the following systems: MOD-bus or
LON-RS485.
If data communication is used, it is important
that the installation of the data communication
cable is performed correctly.
See separate literature No. RC8AC…
Electric noise
Cables for sensors, DI inputs and data com-
munication
must
be kept separate from other
electric cables:
- Use separate cable trays
- Keep a distance between cables of at least
10 cm
- Long cables at the DI input should be avoided
Содержание MPCETNM6S
Страница 2: ......
Страница 12: ...1 6 Installation P N 3086855_C U S Canada 1 800 922 1919 Mexico 1 800 890 2900 www hussmann com NOTES...
Страница 18: ...3 4 Start up Operation P N 3086855_C U S Canada 1 800 922 1919 Mexico 1 800 890 2900 www hussmann com...
Страница 28: ...4 6 Maintenance P N 3086855_C U S Canada 1 800 922 1919 Mexico 1 800 890 2900 www hussmann com NOTES...
Страница 40: ...Hussmann Corporation 12999 St Charles Rock Road Bridgeton MO 63044 2483 www hussmann com...