REPLACING DAMAGED DRAIN FITTING
The following procedure is for the field repair of a
broken drain fitting.
1. Use a drill with a 1
7
/
8
-in. (48 mm) hole saw to
drill out the bottom of the drain fitting. Be sure to
drill completely through fitting and bottom liner.
2. Apply teflon tape to threaded end of adapter and
screw into threaded end of tee.
3. Apply an ABS and PVC compatible primer and
sealer to adapter and inside of drain. Insert adapter
into drain fitting.
Low Temperature
Multi-deck Frozen Food
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Drain Fitting
Viewed from Inside Merchandiser
Foam Bottom
Assembly
Modified
Drain Fitting
PVC Adapter
1
1
/
2
x 1
1
/
4 inch
(38 x 32 mm)
(obtained at local
building supply store)
Tee 1
1
/
4 in.
(32 mm)
TxSxS
End Section View
Rear of Case