7
Parameter Programmed Report
Parameter Description
Value
Min
Max
1
Freezer Cut-in warm
32°F
-40ºC (-40ºF)
40ºC (104ºF)
2
Freezer Cut-out warm
28°F
-40ºC (-40ºF)
40ºC (104ºF)
3
Freezer Cut-in cold
22°F
-40ºC (-40ºF)
40ºC (104ºF)
4
Freezer Cut-out cold
18°F
-40ºC (-40ºF)
40ºC (104ºF)
5
Compressor ON time delay at Controller Power Up
0 min 0 sec
0 sec
59 min 59 sec
6
Compressor Minimum (ON) time
4 min 0 sec
0 sec
30 min 59 sec
7
Compressor Minimum (OFF) time
0 min 30 sec
0 sec
59 min 59 sec
8
Potentiometer off position
10º
5º
57º
9
Potentiometer on position
15º
9º
61º
10
On-Off logical function
1
11
Controller Operation Temperature Units
1
12
Sensor failure mode
(compressor and fan relay
failure mode)
3
13
Compressor On Time if Sensor failed
0 hour 6 min
1 min
59 hour 59 min
14
Compressor Off Time if Sensor failed
0 hour 2 min
1 min
59 hour 59 min
15
Defrost Function
1
16
Defrost Method
2
17
Time to first defrost(Initial frost build time)
2 hour 0 min
10 min
71 hour 59 min
18
Time to subsequent defrost
4 hour 0 min
10 min
71 hour 59 min
19
Defrost duration Time (failsafe)
0 hour 30 min
1 min
4 hour 59 min
20
Defrost Termination temperature
50°F
-40ºC (-40ºF)
40ºC (104ºF)
21
Drip time
0 min 0 sec
0 sec
59 min 59 sec
22
Defrost Cycle at power on
0
23
Evaporator Temp. Sensor
1
24
Defrost Termination Method
2
25
Temperature Initiated Defrost Function
1
26
Temperature Initiated Defrost (T = Tspace-Tevap.)
4°F
0ºC (0ºF)
40ºC (72ºF)
27
Temperature Initiated Defrost Time Delay
3 min 0 sec
0 sec
59 min 59 sec
28
Temperature Initiated Defrost Time Delay
After Defrost
30 min 0 sec
0 sec
59 min 59 sec
29
Temperature Alarm Enable
1
30
High Temperature Alarm - Warm
42°F
-40ºC (-40ºF)
40ºC (104ºF)
31
Low Temperature Alarm - Warm
24°F
-40ºC (-40ºF)
40ºC (104ºF)
32
High Temperature Alarm - Cold
34°F
-40ºC (-40ºF)
40ºC (104ºF)
33
Low Temperature Alarm - Cold
16°F
-40ºC (-40ºF)
40ºC (104ºF)
34
Temperature Alarm Differential
4°F
1ºC (2ºF)
10ºC (18ºF)
35
Temperature Alarm Time delay
0 hour 30 min
0 min
4 hour 59 min
36
Temperature Alarm Disable Time after Start Up
2 hour 0 min
0 min
17 hour 59 min
37
Temperature Alarm Delay after Defrost
1 hour 0 min
0 min
17 hour 59 min
38
Buzzer Function
1
39
Buzzer Period
24.9 sec
0.2 sec
24.9 sec
40
Led Alarm Function
1
41
Led Alarm Period
2.0 sec
0.4 sec
24.8 sec
42
Defrost Display Lock
(display indication during defrost)
1
43
Sensor Fault Monitoring Time
1 min 0 sec
5 sec
59 min 59 sec
44
Display Temperature Offset
0°F
-40ºC (-72ºF)
40ºC (72ºF)
45
Display Unlock Time
0 hour 10 min
0 min
1 hour 59 min
46
Show Parameter Code Number
1
47
Parameter Code Number
6
0
99
48
Maximum Compressor Run Function
0
49
Maximum Compressor Run Time
2 hour 0 min
0 min
17 hour 59 min
50
Defrost Heater Duty Cycle Function
0
51
Heater On Time
1 min 0 sec
5 sec
59 min 59 sec
52
Heater Off Time
0 min 30 sec
0 sec
59 min 59 sec
0=display temperature read
1=lock the display on temp.
2=display DF
0=disable or 1=enable
0=disable or 1=enable
0=disable or 1=enable
0=disable or 1=enable
0=disable
1=Evap. Sensor
2=Control Sensor
3=Digital Switch (close)
0=disable or 1=enable
0=disable or 1=enable
0=disable or 1=enable
0=disable or 1=enable
0=disable or 1=enable
0=Celsius or 1=Fahrenheit
0=Relays fail OPEN
2=Relays fail CLOSE
3=Duty cycle
0=disable
1=System run time
2=Compressor run time
1=Electric
2=Off-cycle
3=reverse cycle
0=disable or 1=enable
8/20/2015
MPC-ET-8S_Report.xls
Safenet III Programmed Parameters
Содержание Chino MPC-ET Series
Страница 16: ...16 Safenet III Operation ...