2
Important Safety Instructions & Guidelines
Risk to Breathing
Avoid using the air compressor in con
fi
ned areas. Always have adequate
space (12 inches) on all sides of the air compressor. Also keep children,
pets, and others out of the area of operation. This air compressor does
not provide breathable air for anyone or any auxiliary breathing device.
Spraying material will always need to be in another area away from the air
compressor to not allow intake air to damage the air compressor
fi
lter.
Risk of Electrical Shock
Never utilize the air compressor in the rain or wet conditions. Any electrical
issues or repairs should be performed by authorized personnel such as an
electrician and should comply with all national and local electrical codes.
The air compressor should also have the proper three prong grounding
plug, correct voltage, and adequate fuse protection.
Risk of
Explosion or Fire
Never operate the compressor near combustible materials, gasoline or
solvent vapors. If spraying
fl
ammable materials, locate the air compressor
at least 20 feet away from the spray area. Never operate the air compres-
sor indoors or in a con
fi
ned area.
Risk of Bursting
Always drain the air compressor tank daily or after each use. If the tank
develops a leak, then replace the air compressor. Never use the air com-
pressor after a leak has been found or try to make any modi
fi
cations to the
tank. Never modify the air compressor
ʼ
s factory settings which control the
tank pressure or any other function.
Specifications
Pump . . . . . . . . . . . . . . . . . .Oil-lube, direct drive
Motor Induction. . . . . . . . . . . . . . . . . . . . . . .1 HP
Bore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.65”
Stroke . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.26”
Voltage Single Phase . . . . . . . . . . . . . . .120 VAC
Minimum Circuit Requirement . . . . . . . .15 Amps
Air Tank Capacity . . . . . . . . . . . . . . . . . 3 Gallons
Cut-in Pressure . . . . . . . . . . . . . . . . . . . . 95 PSI
Cut-out Pressure . . . . . . . . . . . . . . . . . . 125 PSI
SCFM @ 90 PSI. . . . . . . . . . . . . . . . . . . . . . . 2.4
Glossary
CFM
: Cubic feet per minute.
SCFM
: Standard cubic feet per minute; a unit of
measure for air delivery.
PSIG
: Pounds per square inch gauge; a unit of
measure for pressure.
ASME
: American Society of Mechanical Engineers.
California Code
: Unit may comply with California
Code 462 (l) (2)/ (M) (2).
Cut-In Pressure
: The air compressor will
automatically start to refill the tank when
the pressure drops below the prescribed
minimum.
Cut-Out Pressure
: The point at which the motor
stops when the tank has reached maximum
air
pressure.
Code Certification
: Products that bear one or more
of the following marks: UL, CUL, ETL, CSA,
have been evaluated by OSHA-certified
independent safety laboratories and meet
the applicable Underwriters Laboratories
Standards for Safety.
Duty Cycle
This is a 50% duty cycle air compressor. Do not run the air compressor more than 30 minutes of
one hour. Doing so could damage the air compressor.