17
B.ZERO
Set Bar Zero
B . F U L L
Set Bar Full Scale
This function will not be enabled or displayed unless barform has been set to Deviation
or Variable barform (see Barform function).
The BarGraph™ zero display point may be set
to a certain display value. This is not a calibration function. It only affects the range of values
that the bar display will show. This function can be used to limit the lowest value that the
BarGraph™ will display. See Example at bottom of page.
Press
ENTER/SAVE
Press
INCREASE
DECREASE
Press
ENTER/SAVE
The display will show the current BarGraph™ zero display point.
Pressing the INCREASE or DECREASE pushbutton will increase or decrease
the zero display point.
Press ENTER/SAVE to store the new setting.
This function will not be enabled or displayed unless barform has been set to Deviation
or Variable barform (see Barform function).
The BarGraph™ Full Scale display point may
be set to a display value. This is not a calibration command. It only affects the bar display. This
command and the Set Bar Zero function may be used to limit the values shown on the bar
display to a specific region of interest. See Example at bottom of page.
Press
ENTER/SAVE
Press
INCREASE
DECREASE
Press
ENTER/SAVE
The display will show the current BarGraph™ Full Scale display value.
Pressing the INCREASE or DECREASE pushbutton will increase or decrease
the Full Scale display value.
Press ENTER/SAVE to store the new setting.
Example: If the BarGraph is monitoring a process that runs from 0 to 120, but the process
never falls below 110 or rises above 115, displaying from 0 to 120 on the bar
display will force the operating region to the last 1/12 of the bar display. Set-
ting
B.ZERO
to 110 and
B.FULL
to 115 will force the entire bar to display only
the region of interest.