Configuring USC 42
You must first calibrate the position system before configuring USC 42
(chapter 5.3). Device calibration and device configuration operations are only possible
on the password level “Admin”.
CAUTION!
It is only possible to assign parameters and calibrate the device when the
device is at a standstill!
The USC 42 enters a safe state if rotary motion is detected when parameters are
being assigned
5.1 Launching the software US42Pro
When the software is launched, the start
screen is displayed.
Click 'Connect' to establish communica-
tions with the USC 42 . The connection
status is indicated on the right of the but-
ton.
Display
Status
grey
not con-
nected
change
light green / dark
green
connected
After the connection setup, the device data are
read out. To calibrate and configure the
USC 42 the user must first log in using the
Admin password.
ATTENTION!
Change the Admin password 'huebner2' to protect the configuration from unauthor-
ized access (chapter 4.1.6).
5.2 Operating mode
5.2.1 Speed mode
Select the operating mode “Speed mode” if no position dependent switching points or
position dependent current values 4 mA…20 mA are used.
It is not necessary to calibrate the USC 42 in this operating mode.
5.2.2 Position and speed mode
Select the operating mode “Position and speed mode” if position dependent switching
points or position dependent current values 4 mA…20 mA are used.
In this operating mode it is necessary to calibrate the USC 42 (see Chap.5.3).