U-ONE
®
-SAFETY Compact
Configuration manual SCU C / SRC C / SGS C
USC42_SCU-KonfigManual-en_R5
13
4.1.10 Pulldown menu: Options
Reset to factory settings
All parameters and the USC 42 will be deleted and reset to factory settings.
Factory settings:
Password level1
Password level2
huebner1
huebner2
Operating mode
Position and
speed mode
Reset and preset
inputs
Deactivated
Speed and position
switching points
Deleted
Error reset with
software only
Active
Test pulse duration
1 ms
T/ti
1000
Current output
Deactivated
Current output
source
Position
dependent
Error reset with
software only
Active
Incremental output
(optional)
4096
pulses per
revolution
4.1.11 Pulldown menu: Options
Recover password
If a user forgets his/her password, it is possible to
assign a new password using the “Recover Pass-
word” function and following the steps below:
•
Select “Recover Password”.
•
To generate a recovery key click the
button, then click the
button to send the request to the manufac-
turer immediately or later if there is no In-
ternet connection.
•
A recovery password will be generated
and sent back to the designated recipient.
•
It is possible to assign a new password
once the recovery password has been entered in the appropriate field.
Fig. 4-7: recover password