Inputs Tab
Figure 61. External Modbus Device Properties/Inputs Tab
Coil Address
—Modbus coil address assigned to the discrete input on the field device (Modus Server).
Refer to the manufacturer user manual to obtain this information.
Description
—unique name for this device in the E3 system.
Mode
:
•
Disabled
—output is not used.
•
Maintained
—The event is active while the input (coil) is on and immediately cancels when turned
off by a Modbus client.
•
Momentary
—The event is active when the discrete input (coil) is ON and remains active until an
event CANCEL command is issued to the E3 controller.
Trigger
—event to trigger when the input (coil) is ON.
Auto Inhibit
—the auto-inhibit key switch ignores triggered events when the input (coil) is ON.
1.
Configure the
A
DDRESS
,
D
ESCRIPTION
,
M
ODE
,
T
RIGGER
, and
A
UTO
-I
NHIBIT
properties for each
input in the list.
2.
Use the
A
DD
I
NPUT
button to add and configure additional inputs.
3.
Click
R
EMOVE
on any input to remove that input definition from the system.
4.
Click
C
LOSE
to return to the
MODBUS
S
UMMARY
screen.