![Hubbell GAI-TRONICS E3 Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/hubbell/gai-tronics-e3/gai-tronics-e3_console-manual_2180116021.webp)
Pub. 42004-550A
Elemec3
Console Manual
—Version 3.0
Page 14 of 114
P:\Standard IOMs - Current Release\42004 Instr. Manuals\42004-550A.docx
09/20
N
OTE
:
Redundant
Elemec3
systems require access to SNTP (Simple Network Time Protocol)
network service
•
N+1 System—
a system consisting of two E3 controllers sharing a single set of amplifiers with
duplicated access panels and I/O controllers
The first controller operates as the
primary
controller and the second controller operates as the
back-
up
. The primary controller manages system operation under normal conditions. The back-up
controller becomes active to maintain system operation upon failure of the primary controller.
N
OTE
:
Redundant
Elemec3
systems require access to SNTP (Simple Network Time Protocol)
network service
Volume Level
—sets the system-wide volume for all stored audio playback.
Attenuation
—sets the system-wide attenuation level. Audio attenuates to this level, either through
mixing (live speech and playback audio) or through an access panel’s
A
TTENUATE
button.
Network Settings
—Refer to the Network Settings section on page 15.
Event Recorder Enabled
—Specific events and live audio broadcasts are recorded using one or two
external recording device(s) connected to the
A
UXILIARY
A
UDIO
O
UTPUT
O
NE
terminals on the E3
controller. See Pub. 42004-497,
Elemec3
System Controllers, for event recorder connection information
(see the Reference Documentation section).
Enable audio event recording if using an event recorder connected to the E3 controller.
Max Mute Duration
—the maximum duration of audio muting.
Select a
M
UTE
push button on an access panel or the
M
UTE
O
N
A
CK
property of an event to mute the
event. After the specified mute duration, the audio resumes broadcasting if it can access the resources
to do so.
Max Attenuation Duration
—the maximum duration of audio attenuation.
Select the
A
TTENUATE
A
LARM
push button on an access panel at normal volume level to attenuate an
audio event. A setting of 00:00:00 sets the maximum attenuation duration to forever.
Max Fault Acknowledge Duration
—the maximum duration that active faults remain acknowledged
before the system requires reacknowledgement. Acknowledge faults using the E3 Portal application.
Disable Mix 2?
—disables the second audio mix, limiting the system to a single audio pathway. A
mix
is
an audio pathway to the system amplifiers. The system has two audio pathways or
mixes
to the
amplifiers.
N
OTE
:
This feature supports legacy
Elemec
systems and is not recommended for use in current systems.
The
Elemec3
system will be incapable of multiple simultaneous broadcasts when enabled.
Allow Mix Substitution?
—allows for mixed audio (Live Playback) routing to the Aux,
Page/Party, or Monitor outputs.
When selected, mixed events targeting the same audio output are mixed before sending to that audio
output. Bridge outputs to the remote system always allow mix substitution, regardless of this setting.