09/20
Figure 51. Monitored Relay Module Controller Properties
The E3
Console sequentially assigns I/O card addresses when defining the I/O cards in the console. Valid
addressed are 0–F (hexadecimal). Configure the hardware address on each I/O card to match address
assigned in E3 Console. On I/O cards with CAN bus interface, the address is set using a hexadecimal
switch located on the card. On I/O cards with IP interface, the address is set using a serial port connection
and command line interface (CLI). Refer to individual I/O card manuals to set the address (see the
Reference Documentation section).
Inputs Tab
The inputs tab lists the inputs for the currently displayed I/O controller. The E3 Console sequentially
assigns each input address based on the card address and input number. The first input on I/O card zero is
0.1
, the second input on card zero is
0.2
, and so on. The properties for each input appear in the columns
from left to right across the inputs tab and define the address, description, input type, trigger, fault
category, and inhibit state.
Select the input switch type from the drop-down list in column three to enable the remaining fields to
define each input.
N
OTE
:
Select the input type first to activate the remaining fields.
Description
—a unique description for the input.
Input Switch Type
—the switch type for the input contacts. Input types include maintained, momentary,
NO, NC, supervision, etc. The available input types are dependent on the I/O controller type.
Trigger (Event) Selection
—event to trigger when the input activates.
Fault Reporting Category
—
I
GNORE
,
N
ORMAL
, or
*U
RGENT
*
(only selectable for monitored inputs.)
Auto Inhibit
—the auto-inhibit key switch controls the suppression of the input.