Fig. 3
INSTALLATION INSTRUCTIONS
IMPORTANT:
This exit sign may be equipped with one or more options.
Check model number suffix for option designation. Option connection
wires must be run before exit sign face, white trim plate and clear cover
are installed.
FIRE ALARM PANEL (-FAP) OPTION
FAP option connects to 24 volt AC or DC (purple wires).
Flash Rate: .5 seconds on, .5 seconds off. Duty Cycle: 50%.
DC REMOTE (-DC) OPTION
DC Remote option connects to 6-24 volt DC [yellow (–), blue(+)].
FLASHER MODULE (-FM) OPTION
Flash Rate: .5 seconds on, .5 seconds off. Duty Cycle: 50%
Connect option wires (-FAP
or -DC) to grey connector on
option board.
Route wires through
transformer compartment and
out backplate.
93029029
2. The white trim plate surrounding the
exit sign face is held in place by “hook
and loop” velcro, located on the
underside of the trim plate. Remove
the trim plate by carefully lifting
straight up to disengage the velcro.
4. Drill the appropriate size
hole in the enclosure for
conduit entrance.
Fig. 2
shows the recommended
locations.
1300681
3. Remove the exit sign and
mounting bracket from
the enclosure before
proceeding to Step 4.
5. Connect appropriate UL Listed hub(s) to the
conduit, and connect to the enclosure. Route
building utility conductors through conduit and
into enclosure.
1300681
6. Reinstall exit sign mounting bracket and exit
sign. Remove exit sign front face from housing
before proceeding to Step 7.
WIRING DIAGRAM
120/277VAC
AC ONLY, EMERGENCY MODELS
1. Loosen the four slotted
cover screws and remove
the clear cover.
(Typical, four locations)
Fig.1
Fig.2
7. Make all connections to building utility AC
conductors using color coded leads provided.
See Fig. 3 and Fig 4. for appropriate wiring
diagrams.
Fig. 4
WIRING DIAGRAM
120/277VAC
DUAL CIRCUIT (-2C Option) MODELS
8. For emergency models, connect
the battery as shown in Fig. 5.
93029025
Dual-circuit transformer
secondary wires connect
to input connector
on option board.
Connect dual-circuit primary transformer
wires to utility source.
120VAC - connect black and white leads.
277VAC - connect red and white leads.
Fig. 5
EMERGENCY MODEL
BATTERY CONNECTION
Charger board and battery
pack. (Emergency models only).
For emergency models, plug 2-pin
battery connector into PC board.
9. Snap-in appropriate chevron arrow blank-outs in exit sign front face,
if required. Reassemble exit sign face to housing. Rinstall the white
trim plate (press down to engage the fastening strips). Secure the
clear cover to the enclosure.
10. Energize the AC power to the exit sign.
NOTE: For emergency models, allow the battery to fully charge
before testing.
93029235