INSTALLATION INSTRUCTIONS

IMPORTANT:

 This exit sign may be equipped with one or more options.  

Check model number suffix for option designation.  Option connection 
wires must be run before exit sign face, white trim plate and clear cover 
are installed.

FIRE ALARM PANEL (-FAP) OPTION

FAP option connects to 24 volt AC or DC (purple wires). 

Flash Rate: .5 seconds on, .5 seconds off.  Duty Cycle:  50%.

DC REMOTE (-DC) OPTION 

DC Remote option connects to 6-24 volt DC  [yellow (–),  blue(+)].

FLASHER MODULE (-FM) OPTION

 

Flash Rate: .5 seconds on, .5 seconds off.  Duty Cycle:  50%

Connect option wires (-FAP 
or -DC) to grey connector on 
option board.

Route wires through 
transformer compartment and 
out backplate.

93029029

2.    The white trim plate surrounding the 

exit sign face is held in place by “hook 

and loop” velcro, located on the 

underside of the trim plate.  Remove 

the trim plate by carefully lifting 

straight up to disengage the velcro.  

4.   Drill the appropriate size 

hole in the enclosure for 

conduit entrance.  

Fig. 2 

shows the recommended 

locations.

1300681

3.    Remove the exit sign and 

mounting bracket from 

the enclosure before 

proceeding to Step 4.

5.    Connect appropriate UL Listed hub(s) to the 

conduit, and connect to the enclosure.  Route 

building utility conductors through conduit and 

into enclosure.

1300681

6.    Reinstall exit sign mounting bracket and exit 

sign.  Remove exit sign front face from housing 

before proceeding to Step 7.

WIRING DIAGRAM

120/277VAC

AC ONLY, EMERGENCY MODELS

1.    Loosen the four slotted 

cover screws and remove 

the clear cover.

 

(Typical, four locations)

Fig.1

Fig.2

7.    Make all connections to building utility AC 

conductors using color coded leads provided.

 

See Fig. 3 and Fig 4. for appropriate wiring 

diagrams.

Fig. 4

WIRING DIAGRAM

120/277VAC

DUAL CIRCUIT (-2C Option) MODELS

8.    For emergency models, connect 

the battery  as shown in Fig. 5.

93029025

Dual-circuit transformer
secondary wires connect
to input connector 
on option board.

Connect dual-circuit primary transformer 
wires to utility source. 
120VAC - connect black and white leads.
277VAC - connect red and white leads.

Fig. 5

EMERGENCY MODEL

BATTERY CONNECTION

Charger board and battery 

pack. (Emergency models only).

For emergency models, plug 2-pin 

battery connector into PC board.

9.    Snap-in appropriate chevron arrow blank-outs in exit sign front face, 

 

if required.  Reassemble exit sign face to housing.  Rinstall the white 

trim plate (press down to engage the fastening strips).  Secure the 

clear cover to the enclosure.

10.  Energize the AC power to the exit sign.  

 

NOTE:  For emergency models, allow the battery to fully charge 

 

before testing.

93029235

1300685

1300685