background image

TROUBLE SHOOTING

“EXIT” legend does not illuminate

 

•  Check wiring connections.

Emergency circuit does not work

 

•  Batteries are shipped uncharged and disconnected.  Connect power pack leads and charge before testing.

  •  Make sure charger board is properly seated.
  •  Check wiring connections.

TESTING

Signs should be tested and maintained in accordance with National Electrical Code and NFPA 101 Life Safety Code requirements. It is recommended that 
emergency exit signs be tested for 30 seconds once a month and for 90 minutes once a year.

REPLACING A BATTERY PACK

De-energize the AC power supply to the exit sign; remove the clear cover.  Remove the white trim plate and the exit sign face.  Disconnect the 2-pin battery 
pack connector from the charger board.  Remove the battery pack from the compartment.  Install a new battery pack with the correct part number into the 
compartment, and plug in the 2-pin connector to the charger board.  Reinstall the exit sign face, white trim plate and secure the clear cover.  Energize AC power 
to the exit sign.  Allow the new battery pack to fully charge, and press the “TEST” button to verify operation.

RECYCLING INFORMATION       

All thermoplastic parts are recyclable.  All cartons contain recycled materials.  Please recycle responsibly.

NOTICE:

Emergency model exit signs contain rechargeable nickel-cadmium batteries which must be recycled or disposed of properly.

LN4X Series

LED Exit Sign Listed For Damp And Wet Locations
AC Non-Emergency Models  Are UL Type 4X Rated

Installation, Operation and Maintainance Instructions

Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com

Copyright

©

 Hubbell Lighting, Inc., All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A.

 

 

93029236A  

6/10

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed including the following.

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

  1.  Do not let power supply cords touch hot surfaces. 
  2.  Do not mount near gas or electric heaters.
  3.  Equipment should be mounted in locations and at heights where it will not readily be subject to tampering  
     by unauthorized personnel.
  4.  The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition.
  5.  Do not use this equipment for other than its intended purpose.
  6.  Servicing of this equipment should be performed by qualified service personnel.
  7.  Test cycling:  the Life Safety Code (NFPA 101) requires testing of emergency exit signs once a month for a  
     minimum of 30 seconds and once a year for a minimum of 90 minutes.

INSTALLER: 

•SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS

•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT

WARNING

 – 

This product contains chemicals known to the State of California to cause cancer, birth defects and/or other 

reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this product.

93033371

OPERATION

“AC ON” LED is iluminated when AC power is present.  
NOTE: All models are supplied with an AC Lockout circuit, which prevents the “EXIT” legend from illuminating when the battery is connected and no AC power 

is present.
NOTE:  All models are supplied with a Low Voltage Disconnect circuit, which prevents damage to the battery from deep discharge during prolonged 

emergency operation.
NOTE: Batteries are often shipped in a discharged state – this is normal.  The battery will require charging. Allow several hours of charge before testing the unit.

Models With SPECTRON® Self-Testing/Self-Diagnostic Circuitry

Models equipped with the Spectron self-testing/self-diagnostic electronics system provide:

 

 

Visual indication of AC power status 

 

Visual indication of self-diagnostic test cycle

 

—Visual indication of any unit malfunctions including—

 

 

Battery fault 

 

Transfer fault 

 

Charger fault 

 

Emergency

 

Lamp fault

Spectron equipped units also include:

Brownout protection: unit will automatically transfer to emergency operation upon detection of low AC power (approximately 80% of nominal line).

Time Delay Retransfer: upon return of normal AC power, unit will remain in the emergency mode for an additional 15 minutes to allow AC power to stabilize.

LED Status Indicator
A bicolor LED (green/red) is provided on the control panel of all models 
equipped with the Spectron option.

Red Status Indicator Code

Description

One blink ON/pause

Battery not connected

Two blinks ON/pause

Battery fault

Three blinks ON/pause

Charger fault

Four blinks ON/pause

Transfer circuit fault

Five blinks ON/pause

Emergency Lamp fault

Automatic Tests
The unit will automatically initiate a self-test/self-diag-
nostic cycle based on the following table:

Testing Period

Duration of Test

Once a month

1 minute

Once every 6 months

Alternating:
30 minutes or 60 minutes

Manual Tests
Using the unit test switch, users can initiate different 
duration test cycles based on the following table:

Initiating Action

Test Cycle

Press test switch once

1 minute

Press test switch twice

90 minutes

Pressing the test switch at any time after a test cycle has 
begun cancels the remainder of the test and returns the 
unit to normal operation. 

Red Service Alert Indicator
Under normal operating conditions, the red Service Alert Indicator will remain “off”. 
In the event the Spectron controller detects a malfunction, the red Service Alert 
Indicator will blink at a 1 Hz. rate, based on the following table:

Green Operating Status Indicator
The green Operating Status Indicator serves as both an AC power and a self-test 
indicator. During normal operation, the green Operating Status Indicator will be 
illuminated, indicating the presence of AC power.  During all automatic or manual 
self-test cycles, the green Operating Status Indicator will blink at a 1 Hz. rate.

MAINTENANCE

1300681
1300682
1300684
1300685
93029025
93029029
93029235
93029327