110. System Self-Tests
Once the system is properly installed in accordance with the installation instructions, and AC
power is
supplied to the LG inverter system, the dual color (SDT STATUS) LED indicator will
illuminate, followed by
the amber (INV ON) LED indicator. The dual color LED indicates the unit’s status. A steady GREEN LED
indicates normal service; A blinking GREEN/RED LED
indicates the battery is charging; A blinking RED LED
(in different combinations) indicates a service alert. Refer to the INDICATION chart in sections 110.2 for
details. During loss of normal
utility
power the dual color LED will not be illuminated. The AMBER (INV ON)
LED indicator will be illuminated only during inverter operation initiated by the loss of utility power or during
any manual or automatic self-test.
Do not touch components inside the unit. DC voltage is always present at the batteries and battery
cables.
110.1 Self-Test/Diagnostic Functions
The self-diagnostic function is factory preset and performs the following:
A) Continuous monitoring of battery, battery charger and connected loads.
B) Self-testing and a (30) second discharge with a randomized start (per UL 924, Sec. 30.2), once
every (30) days, after normal utility power has been supplied for a minimum of (48) hours.
C) Self-testing and a (30) minute discharge with a randomized start (per UL 924, Sec. 30.2), once
every (180) days, after normal utility power has been supplied for a minimum of (48) hours.
D) Self-testing and a (90) minute discharge with a randomized start (per UL 924, Sec. 30.2), once
every (365) days, after normal utility power has been supplied for a minimum of (48) hours.
110.2 Self-Test/Diagnostic Indication
14.
109.2 For LG375SI and LG600SI
This model also provides for manual testing by pushing the TEST button in a specific pattern:
A)
B)
C)
Action
Reaction and LED Indication
Push test switch Once (within (2) seconds)
Push test switch Twice (within (2) seconds)
Push test swithc Three times (within (2) seconds)
Push test switch and hold for (3) seconds
Push test switch and hold for (6) seconds
(30) second test: one blink GREEN/pause
(30) minute test: two blinks GREEN/pause
(90) minute test: three blinks GREEN/pause
Cancels Test
System reset
INV ON status indicator (yellow) illuminates (indicates inverter is operational).
Normally-On, Normally-Off and Switched fixtures are illuminated (where applicable)