4
Test product information Press the
button to input the information and then press
the input to complete.
1. Current level Press the two buttons
and
to select the current between
current <15mA, 1A, 2.5A, 5A, 10A, 20A, 15mA+1A, 15mA+2.5A, 15mA+5A, 15mA+10A.
Among them, 15mA+1A, 15mA+2.5A, 15mA+5A, 15mA+10A are used on the high voltage
side of the transformer. When the low voltage side is measured at the same time, the high
voltage side uses 15mA and the low voltage side uses the high current gear.
Channel selection Press the two buttons
and
B to select between channel 1,
channel 2, dual channel,
Press the two buttons
and
to select the high voltage phase.
Press the two buttons
and
to select the low voltage phase.
The temperature rise time can be selected between 15s, 30s, 45s, 60s by pressing the
two buttons
and
B.
The converted temperature is 20.0 (Cu), 75.0 (Cu), 90.0 (Cu), 115.0 (Cu), 120.0 (Cu),
145.0 (Cu), 20.0 (Al), 75.0 (Al) by pressing the two buttons
and
, 90.0 (Al),
115.0 (Al), 120.0 (Al), 145.0 (Al) to choose between,
Winding temperature press
to enter the temperature and press
confirm,