background image

Battery Leakage

NO TICE

Battery overheating causes deformation, damage, and electrolyte overflow.

WARNING

When the electrolyte overflows, absorb and neutralize the electrolyte immediately.

When moving or handling a battery whose electrolyte leaks, note that the leaking

electrolyte may cause damage.

When the battery temperature exceeds 60°C, check whether the electrolyte

overflows. If the electrolyte overflows, handle the leakage immediately.

Electrolyte overflow may damage the equipment. It will corrode metal parts

and boards, and ultimately damage the boards.

If the electrolyte overflows, follow the instructions of the battery

manufacturer or use sodium bicarbonate (NaHCO

3

) or sodium carbonate

(Na

2

CO

3

) to neutralize the electrolyte.

Lithium Battery

The safety precautions for lithium batteries are similar to those for lead-acid

batteries except that you also need to observe the following precautions.

WARNING

There is a risk of explosion if the model of the replaced battery is incorrect.

A battery can be replaced only with a battery of the same or similar model

recommended by the manufacturer.

When handling a lithium battery, do not place it upside down, tilt it, or bump

it with other objects.

Keep the lithium battery loop disconnected during installation and

maintenance.

Do not charge a battery when the ambient temperature is below the lower

limit of the operating temperature (charging is forbidden at 0°C). Low-

temperature charging may cause crystallization, which will result in a short

circuit inside the battery.

Use batteries within the allowed temperature range. Otherwise, the battery

performance and safety will be compromised.

Do not throw a lithium battery in fire.

When maintenance is complete, return the waste lithium battery to the

maintenance office.

UPS5000-A-30 kVA, 40 kVA and 80 kVA

User Manual

1 Safety Information

Issue 13 (2022-01-19)

Copyright © Huawei Technologies Co., Ltd.

14

Содержание UPS5000-A-30 kVA

Страница 1: ...UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual Issue 13 Date 2022 01 19 HUAWEI TECHNOLOGIES CO LTD ...

Страница 2: ...s document may not be within the purchase scope or the usage scope Unless otherwise specified in the contract all statements information and recommendations in this document are provided AS IS without warranties guarantees or representations of any kind either express or implied The information in this document is subject to change without notice Every effort has been made in the preparation of th...

Страница 3: ...r Sales engineers Technical support engineers System engineers Hardware installation engineers Commissioning engineers Data configuration engineers Maintenance engineers Symbol Conventions The symbols that may be found in this document are defined as follows Symbol Description Indicates a hazard with a high level of risk which if not avoided will result in death or serious injury Indicates a hazar...

Страница 4: ...st document issue contains all the changes made in earlier issues Issue 13 2022 01 19 Updated the reference document name for the dry contact card Issue 12 2020 01 10 Added SNMP descriptions to the sections about site configuration Added the SNMP V1 and V2 protocol description Updated the safety information Issue 11 2018 12 10 Update some MDU screenshots Issue 10 2018 04 18 This issue is the tenth...

Страница 5: ... Technical Specifications Issue 06 2015 06 26 This issue is the sixth official release which incorporates the following changes Updated the Monitoring screen image Issue 05 2014 09 26 This issue is the fifth official release which incorporates the following changes Added the features of four parallel systems and the battery monitoring unit BMU Issue 04 2014 07 16 This issue is the fourth official ...

Страница 6: ...hanges Added figures of OT and DT terminals for the UPS5000 A and tables that list their specifications in section 3 1 3 Issue 01 2013 11 05 This is the first release UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual About This Document Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd v ...

Страница 7: ... 2 2 2 Working Modes 17 2 2 2 1 Normal Mode 17 2 2 2 2 Bypass Mode 18 2 2 2 3 Battery Mode 18 2 2 2 4 Maintenance Bypass Mode 19 2 2 2 5 ECO Mode 19 2 3 Product Description 20 2 3 1 Appearance 20 2 3 2 Product Structure 21 2 3 2 1 30 kVA 40 kVA UPS 21 2 3 2 2 80kVA UPS 24 2 3 3 Control Port 26 2 4 Typical configurations 31 2 4 1 Single UPS 32 2 4 2 Parallel System 32 2 4 3 Dual Bus System 32 2 5 O...

Страница 8: ... Connecting AC Input Power Cables 80 3 2 7 4 Connecting AC Output Power Cables 84 3 2 7 5 Connecting Battery Cables 85 3 2 8 Remote EPO 87 3 2 9 Connecting Communications Cables 88 3 3 Installing a Parallel System 88 3 3 1 Connecting Power Cables 88 3 3 2 Connecting Signal Cables 92 3 4 Installation Verification 94 4 LCD and WebUI 99 4 1 MDU 99 4 2 LCD 101 4 2 1 Overview 102 4 2 2 Status Screen 10...

Страница 9: ...d Equalized Charging Test 158 5 6 2 Shallow Discharge Test 159 5 6 3 Capacity Test 161 5 6 4 Test Data Download 162 5 7 Transferring to Maintenance Bypass Mode 162 5 8 Transferring from Maintenance Bypass Mode to Normal Mode 164 5 9 Performing EPO 166 5 10 Clearing the EPO State 167 6 Routine Maintenance 169 6 1 UPS Maintenance 169 6 1 1 Monthly Maintenance 170 6 1 2 Quarterly Maintenance 170 6 1 ...

Страница 10: ...tery Specifications 181 8 8 Output Electrical Specifications 182 8 9 System Electrical Specifications 183 A Menu Hierarchy 184 A 1 LCD Menus 184 A 2 Menus on the WebUI 185 B Alarm List 188 C Acronyms and Abbreviations 200 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual Contents Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd ix ...

Страница 11: ...ponent damage personal injuries or property damage will not be covered under the warranty Follow local laws and regulations when installing operating or maintaining the equipment The safety instructions in this document are only supplements to local laws and regulations The Company will not be liable for any consequences of the following circumstances Operation beyond the conditions specified in t...

Страница 12: ... figure Follow the specified procedures for installation operation and maintenance Before handling a conductor surface or terminal measure the contact point voltage and ensure that there is no risk of electric shock After installing the equipment remove idle packing materials such as cartons foam plastics and cable ties from the equipment area In the case of a fire immediately leave the building o...

Страница 13: ...tallation Repaint any paint scratches caused during equipment transportation or installation in a timely manner Equipment with scratches cannot be exposed to an outdoor environment for an extended period of time Before operations ensure that the equipment is firmly secured to the floor or other solid objects such as a wall or an installation rack Do not use water to clean electrical components ins...

Страница 14: ...nals personnel who are trained or experienced in equipment operations and are clear of the sources and degree of various potential hazards in equipment installation operation maintenance Trained personnel personnel who are technically trained have required experience are aware of possible hazards on themselves in certain operations and are able to take protective measures to minimize the hazards o...

Страница 15: ...AC powered facilities must be performed by qualified personnel Cabling When routing cables ensure that a distance of at least 30 mm exists between the cables and heat generating components or areas This prevents damage to the insulation layer of the cables Do not route cables behind the air intake and exhaust vents of the equipment Ensure that cables meet the VW 1 or ZB flame spread rating require...

Страница 16: ...s with ESD packaging materials before storing or transporting them Figure 1 1 Wearing an ESD wrist strap Neutral Ground Voltage It is recommended that the three phase loads be equalized and the neutral ground voltage be kept at less than 2 V to meet power distribution requirements 1 4 Installation Environment Requirements To prevent fire due to high temperature ensure that the ventilation vents or...

Страница 17: ...king at heights Wear personal protective equipment such as the safety helmet and safety belt or waist rope and fasten it to a solid structure Do not mount it on an insecure moveable object or metal object with sharp edges Make sure that the hooks will not slide off Set a restricted area and eye catching signs for working at heights to warn away irrelevant personnel Carry the operation machinery an...

Страница 18: ...wooden or fiberglass ladders when you need to perform live working at heights When a step ladder is used ensure that the pull ropes are secured and the ladder is held firm Before using a ladder check that it is intact and confirm its load bearing capacity Do not overload it Ensure that the ladder is securely positioned The recommended angle for a ladder against the floor is 75 degrees as shown in ...

Страница 19: ...nents or cables inside Metal shavings from drilling may short circuit boards inside the equipment Obtain consent from the customer and contractor before drilling holes Wear goggles and protective gloves when drilling holes When drilling holes protect the equipment from shavings After drilling clean up any shavings that have accumulated inside or outside the equipment Moving Heavy Objects DANGER Wh...

Страница 20: ...al and industrial purposes only It cannot be used as a power supply for life support devices For power supply systems that are critical to significant economic interests or public order such as the national computing center military command system emergency command center railway signal system and control center civil aviation and air traffic control center airport command center financial clearin...

Страница 21: ...t the administrator DANGER Do not expose the equipment to flammable or explosive gas or smoke Do not perform any operation on the equipment in such environments During installation and maintenance ensure that sundries do not enter the UPS Otherwise equipment damage load power derating power failure and personal injury may occur If the mains voltage Vrms exceeds 320 V AC the UPS may be damaged A UP...

Страница 22: ...erating sources such as sunlight fire sources transformers and heaters Overheating may cause battery explosion Do not burn batteries Otherwise the batteries may explode To avoid leakage overheating fire or explosions do not disassemble alter or damage batteries for example insert foreign objects into batteries or immerse batteries in water or other liquids Wear goggles rubber gloves and protective...

Страница 23: ...negative poles of the same battery or battery string Otherwise the battery may be short circuited Check battery connections periodically ensuring that all screws are securely tightened When installing batteries do not place installation tools on the batteries Battery Short Circuit DANGER Battery short circuits can generate high instantaneous current and release a great amount of energy which may c...

Страница 24: ...hat you also need to observe the following precautions WARNING There is a risk of explosion if the model of the replaced battery is incorrect A battery can be replaced only with a battery of the same or similar model recommended by the manufacturer When handling a lithium battery do not place it upside down tilt it or bump it with other objects Keep the lithium battery loop disconnected during ins...

Страница 25: ...S output voltage level or frequency Doing so may affect the power supply to equipment Exercise caution when setting battery parameters Incorrect settings will affect the power supply and battery lifespan UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 1 Safety Information Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 15 ...

Страница 26: ... an input mode indicates the energy flow direction 2 2 1 Conceptual Diagram The UPS5000 A is an online double conversion UPS that uses digital signal processing DSP technology and features high efficiency and high power density Figure 2 2 shows a conceptual diagram for the UPS UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 2 Overview Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 16 ...

Страница 27: ...ircuit to charge the battery string and the other part is converted by the inverter into AC voltage outputs The two conversions ensure high precision and high quality output voltages protecting loads from interferences such as input harmonics burrs and voltage transients Figure 2 3 shows the conceptual diagram of the UPS working in normal mode Figure 2 3 UPS conceptual diagram in normal mode UPS50...

Страница 28: ... by mains outage and incorrect AC voltage or frequency Figure 2 4 shows a conceptual diagram of the UPS working in bypass mode Figure 2 4 UPS conceptual diagram in bypass mode 2 2 2 3 Battery Mode If the AC input voltage is not normal the UPS transfers to battery mode to obtain power from batteries The inverter then converts the power into AC outputs Figure 2 5 shows a conceptual diagram of the UP...

Страница 29: ...when the bypass input voltage is within the ECO voltage range the bypass combined switch turns on and the bypass supplies power When the bypass input voltage is beyond the ECO voltage range the UPS transfers from bypass mode to normal mode In bypass mode or normal mode the rectifier keeps working and charges batteries using a charger The ECO mode delivers a higher efficiency Figure 2 7 shows a con...

Страница 30: ... Appearance Figure 2 8 UPS5000 A 30 kVA 40 kVA 1 Monitor display unit MDU 2 Front panel 3 Support base 4 Chassis UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 2 Overview Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 20 ...

Страница 31: ...Product Structure 2 3 2 1 30 kVA 40 kVA UPS Figure 2 10 and Figure 2 11 show the architecture of the UPS5000 A 30 kVA 40 kVA Figure 2 10 shows the UPS with the front panel and the MDU removed UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 2 Overview Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 21 ...

Страница 32: ...0 A 30 kVA 40 kVA product structure rear view and enlarged view of certain parts 1 Ventilation panel on the rear panel 2 Dry contacts 3 Battery temperature sensor port 4 Ambient temperature and humidity sensor port or battery monitoring unit BMU port 5 FE port upper and RS485 port lower 6 BSC port 7 Parallel ports 8 Slot for dry contact card optional UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual ...

Страница 33: ...rom top down MDU Reset Button If the MDU does not work properly use this button to reset the MDU without affecting power supply DIP Switch Typically three toggle switches are reserved for function settings Table 2 1 describes the DIP switch status Table 2 1 DIP switch status DIP Switch DIP1 DIP2 DIP3 LCD Operation Function Remarks Status 1 OFF OFF OFF N A Not defined N A Status 2 ON ON OFF Setting...

Страница 34: ...ring historical alarm records the MDU restarts automatically Status 5 OFF ON ON Control Clear operation logs Clears operation logs After clearing operation logs the MDU restarts automatically Status 6 OFF ON OFF Settings Advanced Param Work mode Self load mode Sets self load mode After entering self load mode subsequent to inverter startup the MDU does not restart automatically Status 7 OFF OFF ON...

Страница 35: ...2 MDU port 3 Bypass unit ready switch 4 MDU reset button 5 DIP switch 6 Power unit indicators 7 Power unit ready switch 8 Maintenance bypass switch 9 Cold start button UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 2 Overview Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 25 ...

Страница 36: ...umidity sensor is installed connect the BMU to the COM1 port on the UPS When an ambient temperature and humidity sensor is installed connect the BMU to the RS485_OUT port on the sensor 2 3 3 Control Port The UPS5000 A provides a communications slot a fast Ethernet FE port an RS485 port parallel ports a BSC port basic dry contacts and other control signal ports Parallel Port and BSC Port To connect...

Страница 37: ... switch and battery monitoring unit BMU They also allow the UPS to provide alarm signals for external devices and implement remote emergency power off EPO Table 2 3 describes the dry contacts Table 2 3 Dry contacts Silk Screen Description Status BFP_NO Triggers bypass backfeed protection Normally the COM and NC dry contacts are closed If bypass backfeed occurs the COM and NO dry contacts are close...

Страница 38: ...ry switch not tripped 12 V battery switch tripped The initial port voltage is 0 V SWITCH STATUS_OUT Monitors the UPS output circuit breaker on the output power distribution cabinet PDC Status Open circuit breaker OFF Closed circuit breaker ON The initial status is Closed SWITCH STATUS_0V Port for signal ground N A SWITCH STATUS_MT Monitors the maintenance circuit breaker on the output PDC Status O...

Страница 39: ...ts ensure that the silk screen names of the dry contacts at both ends of the cable match with each other Others Table 2 4 describes other control signal ports Table 2 4 Signal ports Port Silk Screen Description Battery temperature sensor port B_TEMP Connects to the indoor battery temperature sensor Southbound communication port 1 COM1 Connects to an ambient temperature and humidity sensor or BMU o...

Страница 40: ...cription 1 GND 2 N A 3 RS485 4 RS485 5 N A 6 12V_PORT Figure 2 15 RS485 pins Table 2 6 RS485 pin definition Pin Description 1 RS485_T 2 RS485_T UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 2 Overview Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 30 ...

Страница 41: ...ower to important loads in small and medium sized data centers It features high availability and strong transient overload capability Dual bus system The dual bus system is suitable for scenarios where high availability requirements are posed for power supply The dual bus system supplies power to important loads in large and medium sized equipment rooms and data centers In addition to common paral...

Страница 42: ...to loads If one UPS fails the other UPSs continue supplying power to loads Figure 2 16 Conceptual diagram of an N X parallel system 2 4 3 Dual Bus System A dual bus system consists of two independent UPS systems Each of these UPS systems in turn consists of one or more UPSs connected in parallel Of the two UPS systems one is a master system and the other is a slave system This design makes the dua...

Страница 43: ... 0400DC0 384BXA PDC 0630DC0 384BXA PDU8000 012 5DCV8 BXA001 PDU8000 025 0DCV8 BXA001 PDU8000 040 0DCV8 BXA001 PDU8000 063 0DCV8 BXA001 PDU8000 080 0DCV8 BXA001 Controls the connection between battery strings and the UPS Provides overload protection short circuit protection and remote trip control PDU8000 0125 0250 0400 0630 0800 DCV8 BXA001 BCB Box User Manual UPS5000 A 30 kVA 40 kVA and 80 kVA Us...

Страница 44: ...vides output dry contacts RMS RELAY01A Dry Contact Extended Card User Manual Ambient temperatur e and humidity sensor N A Monitors the ambient temperature and humidity UPS Ambient Temperature and Humidity Sensor User Manual Battery monitor unit BMU N A Monitors battery voltages and temperature s as well as battery string charge and discharge currents Communica tes with the UPS over Modbus UPS Batt...

Страница 45: ...e BMU by using a 04080298 transfer cable which is delivered with the BMU When no ambient temperature and humidity sensor is installed connect the BMU to the COM1 port on the UPS When an ambient temperature and humidity sensor is installed connect the BMU to the RS485_OUT port on the sensor UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 2 Overview Issue 13 2022 01 19 Copyright Huawei Technologies C...

Страница 46: ...3Installation 3 1 Installation Preparations 3 1 1 Site UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 36 ...

Страница 47: ...Dimensions Figure 3 1 UPS5000 A 30 kVA 40 kVA installation dimensions unit mm UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 37 ...

Страница 48: ...sive materials and salty air Do not install the UPS in environments with conductive metal scraps in the air The optimal operating temperatures for valve regulated lead acid VRLA batteries are 20 30 C Operating temperatures higher than 30 C shorten the battery lifespan and operating temperatures lower than 20 C reduce the battery backup time Installation Clearances Reserve sufficient clearances aro...

Страница 49: ... UPS5000 A 30 kVA 40 kVA as an example to show the installation clearance Figure 3 3 Installation clearances unit mm 3 1 2 Tools and Instruments CAUTION Insulate installation tools to prevent electric shocks Prepare the following tools and meters indicated in Table 3 1 for installation Table 3 1 Tools and meters Tools and Meters Electric pallet truck Manual pallet truck Ladder Rubber mallet UPS500...

Страница 50: ... Cable tie Level instrument Polyvinyl chloride PVC insulation tape Cotton cloth Label Electrician s knife Electrostatic discharge ESD gloves Protective gloves Insulated gloves Insulation protective shoes Torque screwdriver Cable cutter Brush Flat head screwdriver 2 5 mm UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 40 ...

Страница 51: ...ion is not recommended If UPSs are connected in parallel input and output power cables for each UPS should have the same length and specifications Table 3 2 lists the recommended cross sectional areas for power cables Table 3 3 lists the requirements for power cable connectors Table 3 7 lists the recommended UPS input switch configurations Table 3 2 Recommended cross sectional areas for power cabl...

Страница 52: ... Battery input Nominal discharge current 384 V voltage thirty two 12 V batteries A 82 110 219 Maximum discharge current end of discharge current of thirty two 12 V batteries namely 1 67 V cell discharge current of 192 2 V cells A 98 131 262 Recommended cross sectional area mm2 3 x 16 3 x 35 3 x 95 N Ground cable Recommended cross sectional area mm2 PE 1 x 10 1 x 16 1 x 25 UPS5000 A 30 kVA 40 kVA a...

Страница 53: ...d in Table 3 2 are measured at a rated voltage of 380 V if the rated voltage is 400 V multiply the currents by 0 95 if the rated voltage is 415 V multiply the currents by 0 92 If primary loads are non linear loads increase the cross sectional areas of neutral wires 1 5 1 7 times CAUTION Use OT or DT terminals of the specifications listed in Table 3 3 Table 3 4 and Table 3 5 to prevent short circui...

Страница 54: ...7 N m Figure 3 4 OT terminal for the UPS5000 A Table 3 4 OT terminal specifications for the UPS5000 A Nominal conductor cross sectional area mm2 OT terminal hole diamete r d2 mm Dimensions mm W F L E D T 10 6 4 0 2 12 0 0 2 9 3 0 2 23 8 0 3 8 5 0 2 7 0 1 25 0 1 16 6 4 0 2 12 0 0 2 13 3 0 2 29 8 0 3 10 5 0 2 9 0 1 5 0 1 35 9 0 2 22 0 0 2 16 0 0 2 41 0 0 3 14 0 0 2 13 3 1 8 0 1 UPS5000 A 30 kVA 40 k...

Страница 55: ...14 60 1 50 35 8 8 4 8 5 12 0 0 16 16 66 50 8 8 4 10 0 40 14 19 72 70 10 10 5 12 16 22 80 95 10 10 5 13 18 25 87 120 12 13 15 0 50 20 0 0 24 28 96 150 12 13 16 22 32 103 Table 3 6 Input front end circuit breaker configurations Circuit Breaker 30 kVA 40 kVA 80 kVA Mains input front end circuit breaker 80A 3P 100A 3P 160A 3P Bypass input front end circuit breaker 80A 3P 100A 3P 160A 3P UPS5000 A 30 k...

Страница 56: ...FFC Bypass input circuit breaker T1N160 TMD R160 3P FFC 30 kVA Output branch circuit breaker S203 C50 ABB recommended when the short circuit current of the circuit breaker is located is less than 6 kA 40 kVA S203 C63 80 kVA T1N160 TMD R125 3P FFC ABB recommended when the short circuit current of the circuit breaker is located is less than 36 kA NOTE The input front end and output back end circuit ...

Страница 57: ...oor condition and the UPS will be stored for a long time after it is unpacked wrap the UPS with the original plastic coat to prevent dust 3 1 4 1 30 kVA 40 kVA UPS Procedure Step 1 Visually inspect the UPS appearance for shipping damage If any shipping damage is founded report it to the carrier immediately Step 2 Use a pallet truck to transport the UPS to the installation position Step 3 Cut and r...

Страница 58: ...and contact your local Huawei office immediately Step 7 Place the UPS in the installation position End 3 1 4 2 80 kVA UPS Procedure Step 1 Visually inspect the UPS appearance for shipping damage If any shipping damage is founded report it to the carrier immediately Step 2 Use a pallet truck to transport the UPS to the installation position Step 3 Hold the sliding plate steadily cut and remove the ...

Страница 59: ...he packing materials and foam as shown in Figure 3 9 Figure 3 9 Removing packing materials Step 5 Remove the moisture proof bag UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 49 ...

Страница 60: ...TICE Remove both the upper and lower front panels from the UPS Removing the upper one facilitates removal of L shaped brackets Removing the lower one prevents itself from falling off during transportation Figure 3 10 Removing UPS front panels 1 Press the button on both sides of UPS front panel 1 2 Remove UPS front panel 1 3 Remove the screws of UPS front panel 2 4 Remove UPS front panel 2 NOTE Bef...

Страница 61: ... Push the cabinet along the sliding plate to the installation position End 3 2 Installing a Single UPS 3 2 1 Installing the UPS5000 A 30 kVA 40 kVA Tower mounting the UPS Step 1 Assemble support bases When you assemble two modules snap the fasteners into the holes to secure them as shown in Figure 3 12 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huaw...

Страница 62: ...ise 2 Pull the handle out of the groove Step 3 Hold the front end handle and back end handle to place the UPS on support bases Each UPS requires two pairs of support bases and the distance between the two pairs of support bases must be 480 mm or more as shown in Figure 3 14 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 52 ...

Страница 63: ...he chassis Figure 3 15 Pushing the back end handle into the groove 1 Press the back end handle switch 2 Push the handle into the groove 3 Tighten the screws clockwise to secure the handle Step 5 Install the front panel as shown in Figure 3 16 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 53 ...

Страница 64: ...Step 6 Recommended Install a lock for the maintenance bypass switch to prevent misoperations as shown in Figure 3 17 The required lock core diameter is 5 mm to 6 3 mm Figure 3 17 Installing a lock for the maintenance bypass switch unit mm End UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 54 ...

Страница 65: ...and right side panels 3 Remove the handle 4 Remove the MDU NOTE Before you remove the side panels unscrew the mounting ear of the power unit Step 2 Place the ready switches on the power unit and bypass unit into the unlocked state and remove the power unit and bypass unit as shown in Figure 3 19 NOTICE Two persons are required to move a power unit During movement keep the power unit and bypass uni...

Страница 66: ...gn the lower edge of a guide rail with the lower edge of a U scale and then engage the mounting brackets on both ends of the guide rail into the mounting holes as shown in Figure 3 20 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 56 ...

Страница 67: ...guide rail is aligned with the lower edge of a U scale 2 Install floating nuts on the front of the guide rail as shown in Figure 3 21 Figure 3 22 shows the installation method Figure 3 21 Installation positions of floating nuts UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 57 ...

Страница 68: ...de rail Use the same method to install the other guide rail Figure 3 23 Securing the back end of the guide rail rear view NOTICE In this step secure only the back end of the guide rail Step 4 Insert the subrack into the cabinet as shown in Figure 3 24 Then secure the front end of the guide rail with panel screws UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copy...

Страница 69: ...ing a mounting bracket Step 6 Insert the power unit and bypass unit into the subrack and secure them with screws as shown in Figure 3 26 NOTICE After you insert the power unit and bypass unit rotate the ready switches to locked state UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 59 ...

Страница 70: ...ong with the support and connect cables as shown in Figure 3 27 Figure 3 27 Installing the MDU Step 8 Install the front panel and rotate the Huawei logo on it clockwise 90 degrees as shown in Figure 3 28 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 60 ...

Страница 71: ... Using Leveling Feet Step 1 Lower the four leveling feet at the bottom of the cabinet using a wrench until all the four castors at the bottom hang in the air and the leveling feet bear the whole cabinet weight as shown in Figure 3 29 Figure 3 29 Lowering the leveling feet UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 61 ...

Страница 72: ...core diameter is 5 10 mm Figure 3 30 Lock for the maintenance bypass switch End Installing a UPS by Using L shape Brackets Step 1 Determine the position for installing the UPS and mark mounting holes as shown in Figure 3 31 Figure 3 31 Marking off template Unit mm 1 Edge of the cabinet rear 2 Mounting holes for antiseismic kits 3 Mounting holes for L shaped brackets UPS5000 A 30 kVA 40 kVA and 80 ...

Страница 73: ...nsion bolt 1 M12 bolt 2 Spring washer 3 Flat washer 4 Expansion sleeve NOTICE Knock the expansion bolts into the holes until the expansion sleeve completely fits into the hole The expansion sleeve must be completely buried under the ground to facilitate subsequent installation Figure 3 33 Installing an expansion bolt unit mm 1 Drill holes in the ground by using a hammer drill The hole depth is 52 ...

Страница 74: ...e L shaped brackets Step 6 Adjust the cabinet position so that the expansion bolt holes are aligned with the four holes at the bottom of the cabinet Step 7 Check the cabinet levelness using a level If the cabinet is not leveled adjust the leveling feet Step 8 Secure the two L shaped brackets to the ground using four M12x60 expansion bolts as shown in Figure 3 34 Step 9 Install a lock for the maint...

Страница 75: ...ale 01 and engage the mounting brackets on both ends of the guide rail into the mounting holes of the mounting bar as shown in Figure 3 35 Figure 3 35 Engaging mounting brackets front view 1 Scale 2 Mounting bracket 3 Lower edge of a U scale 2 Use panel screws to secure the front and back ends of the guide rail as shown in Figure 3 36 NOTICE Do not fully tighten panel screws which facilitates subs...

Страница 76: ... the front of each guide rail 1 Use a scale plate to determine the installation positions of floating nuts Figure 3 38 shows a scale plate NOTICE Level the Bottom line on the scale plate with the bottom line of the U sale 01 on the rack Install floating nuts onto the mounting holes for the mounting bar that corresponds to Hole location lines UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Install...

Страница 77: ...nstall floating nuts as shown in Figure 3 22 Figure 3 39 shows the installation positions of floating nuts UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 67 ...

Страница 78: ...ower unit and bypass unit rotate the ready switches to unlocked state NOTICE Two persons are required to move a power unit Keep the power units and bypass unit horizontal during movement Figure 3 40 Removing the UPS front panels MDU power units and bypass unit UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 68 ...

Страница 79: ...tall mounting brackets on the chassis two on the left and two on the right as shown in Figure 3 41 Figure 3 41 Installing mounting brackets Step 6 Place the chassis into the rack as shown in Figure 3 42 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 69 ...

Страница 80: ...eling feet using an adjustable wrench until the bottom of the chassis is level with the Edge of cabinet line on the scale plate as shown in Figure 3 43 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 70 ...

Страница 81: ...ale plate Step 8 Check the cabinet levelness using a level If the cabinet is not leveled adjust the leveling feet Step 9 Secure the chassis to the rack as shown in Figure 3 44 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 71 ...

Страница 82: ...Antiseismic Kits Step 1 Determine the positions for installing antiseismic kits based on the marking off template Step 2 Drill holes for installing expansion bolts and install expansion bolts Step 3 Move the UPS to the installation position over its castors Step 4 Remove the lower front panel of the UPS and PDU cover Step 5 Secure two antiseismic kits to the front and rear of the chassis using eig...

Страница 83: ...ower front panel of the UPS and PDU cover End 3 2 4 Optional Installing a Battery Monitoring Unit Connect the BMU by using a 04080298 transfer cable which is delivered with the BMU When no ambient temperature and humidity sensor is installed connect the BMU to the COM1 port on the UPS Figure 3 46 shows the position of the BMU on the UPS When an ambient temperature and humidity sensor is installed ...

Страница 84: ...ure 3 46 Connecting the UPS and BMU without ambient temperature and humidity sensor UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 74 ...

Страница 85: ...as instructed Place the batteries in a correct way to prevent vibrations and shocks Install the batteries from the lower layer to the upper layer to prevent falling over due to imbalance Procedure Step 1 Install the battery rack and batteries For details see the battery installation guide delivered with batteries Step 2 Optional Install a BCB box UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 In...

Страница 86: ...g cables clean the cabinet top bottom copper bar wiring positions and other positions Ensure that there is no dust or scraps inside and around cabinets Prepare terminals onsite The length of the copper wire should be the same as that of the part of the terminal that covers the conductor Procedure Step 1 Route a cable into the cabinet and bind it to a nearby beam Step 2 Pull the cable to the copper...

Страница 87: ... Context NOTICE Cable routings for only the UPS5000 A 80 kVA are elaborated in this section Procedure Step 1 Remove the power distribution unit PDU cover as shown in Figure 3 49 Figure 3 49 Removing the PDU cover Step 2 Route power cables 1 Remove 1 3 covers from the bottom of the cabinet based on the number and positions of cables as shown in Figure 3 50 UPS5000 A 30 kVA 40 kVA and 80 kVA User Ma...

Страница 88: ... cabinet Figure 3 51 Routing power cables from the bottom of the cabinet 1 Bypass input power cable 2 Mains input power cable 3 Output power cable 4 Battery input power cable End 3 2 7 2 Connecting Ground Cables UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 78 ...

Страница 89: ... are OFF Paste warning labels to prevent operation on the switches The basic rule for routing cables is from inside out and from bottom up Figure 3 52 Grounding the UPS5000 A 30 kVA 40 kVA NOTE The three ground cables shown in Figure 3 52 are all connected by default UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 79 ...

Страница 90: ...re a power source connect AC input power cables to mains input terminals N and 1L1 1L2 1L3 on the UPS Figure 3 54 Connecting AC input power cables to the UPS5000 A 30 kVA 40 kVA 1 Input N 2 Input 1L1 3 Input 1L2 4 Input 1L3 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 80 ...

Страница 91: ...ected internally No copper bars are required The neutral terminals of the UPS5000 A 80 kVA are near the interior of the cabinet It is recommended to connect the neutral cable before other power cables End Dual Mains Step 1 Remove the copper bars between mains input terminals and bypass input terminals as shown in Figure 3 56 and Figure 3 57 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installa...

Страница 92: ...opper bars from the UPS5000 A 80 kVA Step 2 Connect mains input cables to mains input terminals N and 1L1 1L2 1L3 on the UPS cabinet Connect bypass input cables to bypass input terminals N and 2L1 2L2 2L3 on the UPS cabinet as shown in Figure 3 58 and Figure 3 59 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 82 ...

Страница 93: ...ables to the UPS5000 A 80 kVA 1 Mains input N 2 Mains input 1L1 3 Mains input 1L2 4 Mains input 1L3 5 Bypass input N 6 Bypass input 2L1 7 Bypass input 2L2 8 Bypass input 2L3 NOTE The neutral terminals of the UPS5000 A 80 kVA are near the interior of the cabinet It is recommended to connect the neutral cable before other power cables End UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation...

Страница 94: ...cable Connect AC output power cables to output terminals N U V and W on the UPS cabinet as shown in Figure 3 60 and Figure 3 61 Figure 3 60 Connecting AC output power cables to the UPS5000 A 30 kVA 40 kVA 1 Output N 2 Output U 3 Output V 4 Output W UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 84 ...

Страница 95: ...utions when connecting cables NOTICE Ensure that cables are correctly connected between battery strings and the battery switch and between the battery switch and the UPS Avoid inverse connections Connect battery cables to battery terminals N and on the UPS cabinet as shown in Figure 3 62 and Figure 3 63 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Hua...

Страница 96: ...y input 2 Battery input N 3 Battery input A neutral wire is routed from the middle of the positive and negative battery strings Figure 3 64 shows a neutral wire routed from the middle of the two battery strings consisting of 40 batteries half positive and half negative UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 86 ...

Страница 97: ...er charger and static bypass but does not disconnect the UPS mains input To power off the UPS completely turn off the front end input switch when you trigger EPO Connect the EPO switch to specified dry contacts on the UPS Figure 3 65 uses the UPS5000 A 30 kVA 40 kVA UPS as an example NOTE By default the EPO switch is NO When you turn on the EPO switch EPO is triggered Figure 3 65 EPO NO status UPS...

Страница 98: ...p 2 Connect input power cables to each UPS Step 3 Connect output power cables to each UPS Step 4 Connect battery cables to each UPS Step 5 Select a parallel connection method to connect cables to the parallel system based on site configurations Figure 3 66 Figure 3 67 and Figure 3 68 show the typical conceptual diagram and cable connections for a 1 1 parallel system Figure 3 66 Conceptual diagram ...

Страница 99: ...ass input power cable 3 Battery cable 4 Output power cable NOTE To clearly and simply show cable connections this document uses the number of oblique lines to indicate the number of power cables of the same type Do not configure circuit breakers for the mains and bypass input N wires and output N wire Connect power cables according to port silk screen UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual...

Страница 100: ...wer cables and UPS output power cables Figure 3 69 Figure 3 70 and Figure 3 71 show the conceptual diagram and cable connections for a bus system consisting of two UPS systems respectively Figure 3 69 Conceptual diagram of a dual bus system UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 90 ...

Страница 101: ... A 30 kVA 40 kVA dual bus system 1 Mains input power cable 2 Bypass input power cable 3 Battery cable 4 Output power cable UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 91 ...

Страница 102: ...nal Cables Connecting Signal Cables in a Parallel System To connect signal cables in a parallel system perform the following steps Connect the parallel ports on the UPSs over parallel cables to create a loop N X parallel system Figure 3 72 shows cable connections UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 92 ...

Страница 103: ...ignal cables in a UPS5000 A 30 kVA 40 kVA N X parallel system Dual bus system Connect cables to BSC ports on the master and slave UPS systems Figure 3 74 shows cable connections in the scenario where the master system consists of two UPSs UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 93 ...

Страница 104: ...tency between system configurations and delivery configurations The system configurations including models and the number of units comply with the contract 02 Cable layout Cables are routed properly and meet engineering requirements 03 Secure cable connections Input and output power cables and battery cables are securely connected and spring washers have been flattened to prevent them from falling...

Страница 105: ...ccording to wiring diagrams 10 Connections of live wires and neutral wires Connections for mains input terminals 1L1 1L2 1L3 and N bypass input terminals 2L1 2L2 2L3 and output terminals U V W and N are correct 11 Live wire sequence In single UPS mode live wires are connected in a correct sequence in a parallel system mains and bypass live wires are connected in the same sequence on the input and ...

Страница 106: ...ped according to standards and that there is no bare copper wire Ensure that there is no foreign matter at the bottom of the UPS NOTE Figure 3 75 and Figure 3 76 show the positions to be checked 14 Check that DIP switch settings are correct Set toggle switch 4 to ON 15 Copper busbar short circuit Copper busbars are confirmed as being open circuited using a multimeter or an insulation resistance te...

Страница 107: ...VA UPS 1 Wiring terminals 2 Wiring terminal box Figure 3 76 80 kVA UPS 1 Wiring terminals 2 UPS bottom UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 97 ...

Страница 108: ...ure 3 77 Fill the holes with sealing putty 1 Paper protective film 2 Sealing putty UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 3 Installation Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 98 ...

Страница 109: ...unning status and alarms Exterior Figure 4 1 MDU panel 1 LCD 2 Back Shutdown button 3 Up button 4 Down button 5 Startup Enter Mute button 6 Fault indicator INFO button 7 Bypass indicator 8 Battery indicator 9 Mains indicator UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 99 ...

Страница 110: ...or are both on The UPS is in battery ECO mode when the battery indicator and bypass indicator are both on Functions The LCD displays the UPS running data and alarm information and allows you to set parameters and control UPS running The backlight turns off if you do not press any button within 30s Table 4 2 Button description Button Meaning Description ESC Back Shutdown On any screen other than th...

Страница 111: ... buzzes hold down for more than 2s to mute it The mute function cannot mute the sound generated due to low battery capacity Fault indicator INFO button When an alarm is generated press to view the active alarm information When no alarm is generated press to return to the default screen When the buzzer buzzes hold down to mute it The mute function cannot mute the sound generated due to low battery ...

Страница 112: ... in this document correspond to the MDU version V100R003C01SPC410 and are for reference only Main Menu Screen Figure 4 2 Main Menu screen 4 2 2 Status Screen On the Main Menu screen select Status and press The Status screen is displayed as shown in Figure 4 3 Figure 4 3 Status UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 10...

Страница 113: ...ring currents is displayed during battery charge and is displayed during battery discharge The positive voltage and current and negative voltage and current are displayed for the battery version with neutral wire Only the voltage and current are displayed for the battery version without neutral wire Status The value can be Not connected Not chg or dis Hibernating Flt charging Eql Charging or disch...

Страница 114: ...put apparent power of each phase on the UPS Pout_A Pout_B and Pout_C Output active power of each phase on the UPS Load ratio_A Load ratio_B and Load ratio_C Load ratio of each phase on the UPS Table 4 9 Parallel System Load Item Description Sys Sout_A Sys Sout_B and Sys Sout_C Output apparent power of each phase in the parallel system Sys Pout_A Sys Pout_B and Sys Pout_C Output active power of eac...

Страница 115: ...played Table 4 11 Runtime Item Description Inv runtime Time for which the UPS runs in normal mode BPM runtime Time for which the UPS runs in bypass mode NOTE The value takes an integer For example If the value is less than 1 the value takes 0 If the value is greater than or equal to 1 and less than 2 the value takes 1 4 2 3 Alarms On the Main Menu screen select Alarms and press The Alarms screen i...

Страница 116: ...es your account will be locked out for 5 minutes After you log in to the WebUI you will be logged out if another user logs in with the same user name Change the password after your first login to prevent unauthorized access Control Buzzer The Control Buzzer screen provides the Buzzer On and Buzzer Off menus If the buzzer is muted the Buzzer On screen is displayed after you press If the buzzer is e...

Страница 117: ...re 4 6 Settings screen User Screen Figure 4 7 User screen Item Description Default Value Value Range Language Supports 12 display languages English English Chinese Spanish Dutch French German Italian Polish Portuguese Russian Swedish and Turkish Password N A 000001 N A UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 107 ...

Страница 118: ...atically changes to Manual The IP address is bound as the IP address set last time allowing you to log in for the second time Item Description Default Value Value Range IP address Specifies the IP address for the Ethernet NOTICE Ensure that the UPS IP address is unique on the network segment Otherwise the WebUI display function may not function properly 192 168 0 10 1 0 0 0 223 255 255 2 55 Subn m...

Страница 119: ...85 communication ensure that the parity modes for the device nodes are set to the same mode None None Odd Even Stop bit Stop bit in the Modbus communication frame format When the UPS is connected over the serial port Modbus set this parameter based on the frame format that the upstream device Modbus supports 1 1 2 Figure 4 11 Ambient temperature and humidity sensor Item Description Default Value V...

Страница 120: ...ption Default Value Value Range Start address N A 16 16 28 Quantity Number of cascaded battery temperature sensors 0 0 4 Figure 4 13 BMU Item Description Default Value Value Range Start address N A 112 N A Quantity Number of cascaded BMUs 0 0 12 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 110 ...

Страница 121: ... Description Default Value Value Range Single Parallel Specifies whether the UPS works in single mode or parallel mode Single Single Parallel Working mode UPS working mode Normal Normal ECO Self load Converter ECO volt range In ECO mode when the difference between the bypass voltage and the rated voltage is greater than this value the system determines that the ECO voltage is abnormal and transfer...

Страница 122: ...the settings in the future perform operations under the guidance of maintenance engineers Non BSC Non BSC Standard BSC Filt maint intvl Specifies the rack air filter maintenance interval If it is set to 0 there is no reminder 0 0 365 NTC The short distance battery temperature sensor monitors the ambient temperature near batteries and ensures that batteries work reliably and securely Disabled Disab...

Страница 123: ...ut Settings Figure 4 16 Output Settings Screen Item Description Default Value Value Range Outp volt lev Specifies the system output voltage level This parameter is configurable only after the inverter shuts down After you change the voltage level the upper limit of the bypass voltage restores to the default value If the voltage level is 380 V or 400 V the default upper limit is 15 If the voltage l...

Страница 124: ...ass frequency when the bypass frequency changes If output is overloaded or the inverter is faulty an interruption less than 20 ms occurs when the UPS transfers from normal mode to bypass mode If Output freq track rate Hz s is fast the inverter frequency is unstable 0 6 Hz s 0 1 Hz s to 2 0 Hz s NOTE Output voltage and Freq track rateare displayed in the scroll manner The full display is as follows...

Страница 125: ... range When the difference between the bypass input frequency and the rated frequency is greater than the specified value the system determines that the bypass frequency is abnormal so the bypass is unavailable 2 Hz 0 5 Hz to 6 Hz Battery Settings NOTICE Battery parameter settings greatly affect battery maintenance battery lifespan and UPS discharge time When you set battery parameters note the fo...

Страница 126: ... the capacity of each battery that is connected in the battery string in series Depends on the actual model 5 9999 Batteries in string Specifies the number of batteries in a battery string The default value depends on the model The value range depends on the model Num of batt strings Specifies the number of battery strings connected in parallel 1 1 4 UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual ...

Страница 127: ...t Value Value Range Cell eql volt Indicates the battery equalized charging voltage The parameter is configurable in any mode 2 35 V cell 2 30 V cell 2 40 V cell Auto eql chg When the value is Enabled the UPS automatically changes the battery management status to equalized charge based on the charge current and floating charge time Enabled N A Float Charge Figure 4 21 Float Charge screen UPS5000 A ...

Страница 128: ...oefficient for correcting the float voltage based on the battery temperature when a battery temperature sensor is connected 3 3 mV C cell 0 0 mV C cell 6 0 mV C cell Temp comp center Basic point of temperature compensation 25 C 20 30 Discharge Figure 4 22 Discharge screen Item Description Default Value Value Range Max dis time Indicates the maximum battery discharge time When the discharge time re...

Страница 129: ...me The shallow discharge test starts in the specified time 00 00 06 00 00 00 06 00 06 00 12 00 12 00 18 00 or 18 00 24 00 Time interval Indicates the time interval for shallow discharge tests The parameter is configurable in any mode 60d 30d 90d Discharge ratio Indicates the proportion of the discharge capacity to the total discharge capacity The parameter is configurable in any mode 20 10 50 Back...

Страница 130: ...therwise the UPS may not run properly If some dry contacts are not used set them to Disabled to prevent false alarms Figure 4 26 Dry Contact Settings screen Item Description BTG Enable or disable battery grounding fault detection GEN Enable or disable D G connection detection OL Enable or disable BCB connection detection STA Enable or disable battery circuit breaker status detection OUT Enable or ...

Страница 131: ...ically starts After first startup set basic parameters including the language date and time network parameters and common parameters Restore Default Settings Screen Restore default settings after the inverter shuts down NOTE Default settings can be successfully restored only after you set DIP1 DIP2 and DIP3 on the DIP switch to ON ON and OFF respectively 4 2 5 Control On the Main Menu screen selec...

Страница 132: ...hallow discharge test can be conducted to test the battery loop reliability and short time discharge capacity when the batteries have not discharged for a long time Capacity Test Fully discharge batteries A deep discharge test is conducted to obtain the battery discharge performance data Stop Test Stop a shallow discharge test capacity test or forced equalized charging Clearing Historical Alarms N...

Страница 133: ...rowser and choose Tools Internet Options Step 2 On the Advanced tab page ensure that Use TLS 1 0 and Use TLS 1 1 are selected and click OK Step 3 Enter https UPS IP address in the address box of the browser select a language set User name and Password and click Login NOTE The preset UPS IP address is 192 168 0 10 You can set the UPS Ethernet IP address on the LCD or WebUI The value range is 1 0 0 ...

Страница 134: ... and controls the buzzer Other control and maintenance functions that may affect system operation are invisible and parameters cannot be set browser browsing user Only browses the system running information NOTE If an incorrect password is entered five consecutive times the account will be logged out for 5 minutes After a user logs in to the WebUI if another user logs in with the same user name th...

Страница 135: ...ow and UPS running information 2 Menu bar Displays alarms and real time data sets parameters and provides control commands The Active Alarms page is displayed by default 3 Information area Displays system monitoring information 4 3 2 1 Parameter Settings Figure 4 31 Parameter Settings UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 01 19 Copyright Huawei Technologies C...

Страница 136: ...orrectly Enable Disable Enable D G ECO bypass supply Indicates whether ECO bypass is allowed to supply power in D G mode When the D G is connected to the dry contact signal GEN If this parameter is set to Enable the system can enter ECO bypass mode when the D G supplies power to the bypass and the ECO function is enabled If this parameter is set to Disable the system is not allowed to enter ECO mo...

Страница 137: ... load impact and facilitates better cooperation between the UPS and the D G Depends on the actual model 0 kVA to 5000 kVA D G charger power ratio 0 0 100 Input cur limiting Specifies whether to enable or disable input current limiting to protect generators Disable Disable Enable Input cur limiting ratio Limits the input current to protect the D G 200 50 200 Output Setting Item Description Default ...

Страница 138: ...ween bypass mode and normal mode which impacts the system This parameter specifies the number of transfers between bypass mode and normal mode within 1 hour which ensures system security 5 1 10 Inverter async alarm Specifies whether an Inverter asynchronous alarm can be displayed on the LCD when the inverter cannot track the bypass frequency change Normal power supply is not affected no matter whe...

Страница 139: ...isable Enable Bus overvolt recovery time If Bus overvoltage recovery is set to Enable the bus overvoltage alarm is automatically cleared and the rectifier and inverter automatically start when the bus voltage recovers less than 420 V within Bus overvolt recovery time 5s 5s 1 min 5 min 10 min Capacitor failure detection If Capacitor failure detection is set to Enable the power unit performs inverte...

Страница 140: ...scharge time When you set battery parameters note the following Retain default settings for Chg cur limiting coef and Cell float voltage Only professional maintenance personnel are allowed to change the settings When you set parameters ensure the following Chg cur limiting coef Transfer to equalized charging cur coef Single batt float chg voltage deviation alarm thres and Single batt dis voltage d...

Страница 141: ...d float charge time Enable Disable Enable Transfer to equalized charging cur coef C10 The battery enters equalized charge state when the battery current exceeds this parameter value 0 05 0 02 0 08 SOC to start equalized charging If the SOC is lower than the specified value batteries start equalized charging 70 0 100 Scheduled equalized charging interval d After batteries transfer from equalized ch...

Страница 142: ...rm manually or enable the restart function for the UPS Enable Disable Enable EOD restart delay min If EOD restart is set to Enable the UPS starts working after the time set for EOD restart delay when the input recovers from the power failure upon EOD 10 1 1440 Undertemp alarm thresh C Battery temperatures can be monitored in a timely manner If a battery overtemperature alarm is detected the chargi...

Страница 143: ... delay time If the parameter is disabled this function is not available Disable Disable Enable Backup time warning An alarm is generated if this parameter is set to Enable and the backup time is less than the warning threshold Disable Disable Enable Remain cap warning An alarm is generated if this parameter is set to Enable and the remaining capacity is less than the warning threshold Disable Disa...

Страница 144: ... generation time and clear time Figure 4 34 Historical Alarms page 4 3 3 2 Logs Page On the Logs page you can set Log to Historical logs Cap test logs or Common test logs and query or export logs NOTE Historical logs can be exported but not queried Figure 4 35 Logs Page UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 134 ...

Страница 145: ... to 20 characters and at least two types of uppercase letters lowercase letters digits and underscores If the LUI password complexity check is disabled the user password is required to be a string of six to eight digits If the password complexity check is enabled the user password is required to be a string of 6 20 characters and contain at least two types of characters 4 3 4 2 Site Config On the ...

Страница 146: ...ess of a server on which the NMS software is installed The trap port needs to be the same as that on the NMS If SNMP Trap is incorrectly set or not set system information will be lost or not reported in time The certificate is used for Secure Sockets Layer SSL encryption protection for WebUI login You need to apply to a third party institution for the certificate Configuration Management is used t...

Страница 147: ...gement Import a CA certificate to verify the validity of the ModbusTCP access certificate ModbusTCP Authentication Verify the identity legitimacy of both parties to ensure data security for both parties in ModbusTCP communication After eUPS certificate management is configured a certificate can be imported on the WebUI to replace the preset eUPS certificate 4 3 4 3 RCCMD RCCMD RCCMD function is se...

Страница 148: ... Encrypted Transmission is set to Enable by default as shown in Figure 4 40 If it is set to Disable the RCCMD certificate controls will not be displayed on the page as shown in Figure 4 41 If SSL Encrypted Transmission is set to Disable a message indicating there is a risk will be displayed UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 01 19 Copyright Huawei Technolo...

Страница 149: ...arm events and a maximum of 50 jobs can be added for each event as shown in Figure 4 42 Figure 4 42 shows the buttons on the Event Configuration page and Table 4 14 describes these buttons Figure 4 42 Event configuration page UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 139 ...

Страница 150: ...on for adding one job You can add one job for the event by clicking this button 4 Button for adding one job for events Select multiple events and you can add one job for the selected events at the same time by clicking this button 5 Button for deleting all jobs You can delete all jobs of the event by clicking this button Figure 4 43 shows the buttons after one event is expanded and Table 4 15 desc...

Страница 151: ... the page for adding a job for the event is displayed When adding a job the job types to be selected are RCCMD Shutdown RCCMD Message RCCMD Execute and RCCMD TRAP RCCMD Shutdown is selected by default For different job types you need to enter different contents RCCMD Shutdown You need to specify the RCCMD client IP address and port When the RCCMD client receives the job it will shut down the compu...

Страница 152: ...to all connected RCCMD clients based on the sending mechanism If you want to define the TRAP message by yourself you can use the TRAP signal to display the UPS information For example if you enter INVOLT V the RCCMD client will receive the UPS input voltage value for example single phase 220 V three phase A 220 V B 220 V C 220 V Table 4 16 lists the signal names that can be entered UPS5000 A 30 kV...

Страница 153: ...ity INVOLT Input voltage V BYPASSINVOLT Bypass input voltage V TEMPDEG Temperature inside the UPS Celsius AUTONOMTIME Battery backup time minutes STATUS UPS status N A RUNTIME UPS operating time minutes BATTVOLT Battery voltage V INFREQ Input frequency Hz BYPASSINFREQ Bypass input frequency Hz OUTFREQ Output frequency Hz UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 ...

Страница 154: ...ds remaining time When the battery backup time has only X seconds left the job will be sent to the RCCMD client once NOTE X and Y are variables and stand for time RCCMD Certificate Management NOTICE After replacing the certificate on the MDU WebUI replace the certificate on the RCCMD client too Otherwise communication will fail For details about the replacing method see the RCCMD user manual The d...

Страница 155: ... MIB The MIB is in the MDU Click Download UPS RFC1628 MIB on the page of the web browser to download the MIB file which allows the third party NMS to manage the UPS remotely Figure 4 49 Download the MIB NOTE The UPS RFC1628 MIB has more alarms than RFC1628 Download the UPS RFC1628 MIB before using UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 01 19 Copyright Huawei T...

Страница 156: ...g the UNMS II For details see the UNMS II user manual 4 3 5 Protecting the Server by Using the RCCMD Software 4 3 5 1 Introduction to the Software The RCCMD shutdown software is part of the centralized monitoring system of the Generex network The UPS5000 MDU integrates the functions of the Generex RCCMD server Sends the shutdown command notification message and Trap message to the RCCMD client if ...

Страница 157: ...set If the RCCMD client is set to the unencrypted mode you need to set the SSL encryption to Disable on the server WebUI Step 4 Configure events If you set the job type to RCCMD Message under Inverter on specify the IP address and port of the RCCMD client The port is 6003 by default If you need to modify the port modify the port on the RCCMD client at the same time to keep them the same Enter the ...

Страница 158: ... the RCCMD can check whether the UPS and RCCMD communicate properly the RCCMD can receive messages sent by the MDU Procedure Step 1 On the RCCMD client add the IP address of the MDU that detects heartbeat as shown in Figure 4 52 Step 2 The UPS5000 MDU supports both ways of heartbeat detection If the job configured for the MDU event is set to RCCMD TRAP the RCCMD client needs to be set to by the us...

Страница 159: ...CCMD client You can also manually detect heartbeat by clicking Run alive check now Figure 4 53 Detecting heartbeat manually UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 149 ...

Страница 160: ...Figure 4 54 Detecting heartbeat manually and successfully End UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 4 LCD and WebUI Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 150 ...

Страница 161: ...er the UPS is powered on initialization begins The MDU displays the Huawei logo and an initialization progress bar Step 2 After the LCD starts properly perform the following operations If this is the first startup set the language date time network parameters system parameters and battery parameters by using the setting wizard If this is not the first startup retain the previous settings NOTE Afte...

Страница 162: ...g is shared High or low charging power shortens the battery lifespan or even promptly damages batteries To determine the battery capacity contact Huawei technical support Figure 5 1 Settings wizard Step 3 After the quick settings if no alarm is displayed on the LCD go to the next step If any abnormal alarm is displayed clear the abnormal alarm Because batteries have not been connected the No batte...

Страница 163: ... a browser Internet Explorer 11 for example and choose Tools Internet Options b Click the Advanced tab check that Use TLS 1 0 Use TLS 1 1 and Use TLS 1 2 are selected and click OK Figure 5 2 Setting the Internet options c In the address box of the browser enter https UPS IP address d Select a language Enter a user name and password and click Login The system supports Internet Explorer 11 and Firef...

Страница 164: ...it responds to the startup command Step 6 Check that the UPS has transferred to normal mode by viewing the system running diagram Check on the LCD Check the UPS three phase output voltage and frequency by choosing Status UPS Output to view real time data on the LCD Use a multimeter to measure the valid three phase output voltage and frequency Check on the WebUI On the home page choose Monitoring R...

Страница 165: ...ansfer the UPS to bypass mode perform only Step 1 after confirming that the UPS generates no alarm If you need to power off the UPS perform all the preceding steps NOTICE After you shut down the inverter if the bypass is normal the UPS transfers to bypass mode if the bypass is abnormal the UPS supplies no power Before you shut down the UPS ensure that all loads have shut down Procedure Step 1 Shut...

Страница 166: ... switches End 5 3 Starting the UPS in Battery Mode Procedure Step 1 Ensure that batteries have been connected properly Use a multimeter to check that the absolute voltages of positive and negative battery strings are greater than a certain value single battery voltage x number of batteries in the battery string Step 2 Open the upstream mains input and bypass input switches and close the battery ci...

Страница 167: ...O mode by default Set the UPS to ECO mode when energy saving is required In ECO mode the bypass takes priority over the inverter in supplying power If the bypass is disconnected the UPS switches to normal mode The switchover time is less than 4 ms for typical working conditions and is less than 20 ms under harsh working conditions Both a single UPS and the parallel system support the ECO mode for ...

Страница 168: ...power immediately when the bypass becomes abnormal and the UPS may power off End 5 6 Testing Batteries 5 6 1 Forced Equalized Charging Test Context NOTICE Before conducting a forced equalized charging test check whether the requirements of a forced equalized charging test are met If the requirements are met the button for starting a forced equalized charging test is available Otherwise the button ...

Страница 169: ...w Discharge Test NOTICE Before conducting a shallow discharge test check whether the requirements of a shallow discharge test are met If the requirements are met the button for starting a shallow discharge test is available Otherwise the button is unavailable Before a shallow discharge test ensure that The UPS works in normal mode with a load ratio fluctuation less than 10 The UPS has generated no...

Страница 170: ...ick Start next to Shallow discharge test to start a shallow discharge test Figure 5 10 Starting a shallow discharge test NOTE When the battery test is complete the test data is used as common test data Record the data obtained from the latest five tests Click Stop next to Shallow discharge test in any of the following cases The battery discharge capacity reaches the specified value 10 50 20 by def...

Страница 171: ...arge SOC reaches 100 and the load ratio fluctuation is less than 10 The UPS has generated no battery overtemperature overvoltage or overcurrent alarm No generator is connected to the UPS The mains batteries charger and discharger are normal No overload alarm is generated Procedure Step 1 Log in to the WebUI Step 2 On the Monitoring Control System Commands and Tests page click Start next to Capacit...

Страница 172: ...t discharge capacity in a month as the capacity test data for the month A maximum of recent 36 capacity test records can be saved End 5 6 4 Test Data Download Procedure Step 1 Log in to the WebUI Step 2 Choose Query Logs select Cap test logs or Common test logs from the Log drop down list box click Export and select a path as shown in Figure 5 12 and Figure 5 13 Figure 5 12 Capacity test logs Figu...

Страница 173: ... the UPS to bypass mode Step 2 Turn on the maintenance bypass switch Turn on the maintenance bypass switch If the maintenance bypass switch is locked unlock it first Rotate the maintenance bypass switch to ON The system hence transfers to maintenance bypass mode as shown in Figure 5 14 and Figure 5 15 Figure 5 14 Turning on the maintenance bypass switch on the UPS5000 A 30 kVA 40 kVA UPS5000 A 30 ...

Страница 174: ... WebUI as shown in Figure 5 16 and Figure 5 17 By default the maintenance bypass switch is OFF Figure 5 16 Maint Breaker closed alarm on the LCD Figure 5 17 Maint Breaker closed alarm on the WebUI End 5 8 Transferring from Maintenance Bypass Mode to Normal Mode UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 5 Operations Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 164 ...

Страница 175: ...bypass switch as shown in Figure 5 18 and Figure 5 19 The Maint breaker closed alarm disappears on the LCD and WebUI View the system running diagram on the LCD or WebUI to check that the UPS has transferred to bypass mode Figure 5 18 Turning off the maintenance bypass switch on the UPS5000 A 30 kVA 40 kVA UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 5 Operations Issue 13 2022 01 19 Copyright Hua...

Страница 176: ...default If the UPS is in normal mode the UPS provides no output after you press the EPO switch The loads power off If the UPS is in maintenance bypass mode the UPS still supplies power after you press the EPO switch Procedure Step 1 Turn on the external EPO switch that connects to the dry contact The UPS enters the EPO state EPO alarms are displayed on the LCD and WebUI as shown in Figure 5 20 and...

Страница 177: ...ch is not in the EPO state Step 2 Clear the EPO alarms in the system LCD On the main screen choose Alarms Clear Faults After the dialog box is displayed press and the EPO alarm can be cleared as shown in Figure 5 22 and Figure 5 23 Figure 5 22 Alarms screen Figure 5 23 Clearing the alarm UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 5 Operations Issue 13 2022 01 19 Copyright Huawei Technologies C...

Страница 178: ...igure 5 24 Clearing the alarm on the WebUI Step 3 Check that the EPO alarm has disappeared from the alarm list If the bypass is normal the UPS transfers to bypass mode Step 4 Start the inverter End UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 5 Operations Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 168 ...

Страница 179: ...ly trained personnel are allowed to perform maintenance Customers are not allowed to maintain components behind protective covers that can be removed only using tools If the components are to be maintained contact Huawei technical support Only maintenance engineers can maintain power units and bypass units Maintain UPSs regularly based on the following requirements Otherwise the UPSs may fail to o...

Страница 180: ...ut voltage is abnormal check the power grid status and input cable connection If the output voltage is abnormal check the UPS running status and check whether an alarm is generated Information on the LCD The status icons on the LCD indicate that all units are operating properly all operating parameters are within their normal ranges and no fault or alarm information is displayed If an alarm is gen...

Страница 181: ...s Power cables and terminals between the UPS and the power distribution cabinet The insulation layer of cables is intact and terminals are free from black marks and noticeable sparks Replace the cables Secure the output terminals Cables and circuit breaker through current capacity The circuit breakers and cables meet load requirements The actual cable through current capacity is greater than the c...

Страница 182: ...es Wear insulated gloves and a protective coat in case of electrolyte overflow When moving batteries avoid handling the battery upside down handle batteries gently and pay attention to personal safety Keep the battery switch off when installing or maintaining the batteries 6 2 1 Precautions for Battery Maintenance Before battery maintenance get the tools such as handles insulated Do not place othe...

Страница 183: ...fications 1 Identify the cause of an abnormal battery operating temperature 2 If the fault persists contact Huawei technical support Charge voltage of battery string Equalized charging voltage 2 35 V cell 1 x Single battery voltage 2 x Number of batteries in a battery string Float charging voltage 2 25 V cell 1 x Single battery voltage 2 x Number of batteries in a battery string 1 If the voltage d...

Страница 184: ...dicating tight connections does not change Take photos from multiple angles and contact Huawei technical support Cables between batteries No cable deteriorates and the insulation layer does not crack Replace the faulty cable Battery voltage Equalized charging voltage 2 35 V cell 0 02 V cell Float charging voltage 2 25 V cell 0 02 V cell 1 Check whether the equalized charging voltage and float char...

Страница 185: ...ate the cause when an exception is identified 2 If the fault persists contact Huawei technical support Battery connection reliability 1 Each battery terminal is connected reliably When battery strings are powered off check the reliability of each terminal in the order from positive terminals to negative terminals 2 The tightening torque of each battery screw meets the requirements of the battery m...

Страница 186: ...reach EOD the battery switch in the BCB box trips if the BCB box is configured To restore battery discharge close the battery switch in the BCB box if any first To restore battery discharge after batteries reach EOD use one of the following methods 1 Switch to another battery string Ensure that each battery has a voltage greater than the EOD voltage and 11 3 V cell 2 Restore the mains power supply...

Страница 187: ...unit The charger generate an alarm The buzzer is activated the Fault indicator is on and the charging function fails The charger fails Replace the power unit The charger experiences overcurrent The charger experiences undervoltage Check whether the configured number of batteries is correct If the value is correct but the alarm persists replace the power unit The UPS works in bypass mode and does n...

Страница 188: ... replacement and maintenance involved in Troubleshooting and Alarm List consult Huawei maintenance engineers UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 7 Troubleshooting Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 178 ...

Страница 189: ... W x D 500 mm x 264 mm x 800 mm 1020 mm x 440 mm x 850 mm Weight 70 kg 180 kg 8 2 Internal Switch Parameters Switch 30 kVA 40 kVA 80 kVA Maintenance bypass switch 750 V AC 80 A 3P 750 V AC 80 A 3P 750 V AC 160 A 3P 8 3 Environmental Specifications Item 30 kVA 40 kVA 80 kVA Operating temperature 0 40 C UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 8 Technical Specifications Issue 13 2022 01 19 Cop...

Страница 190: ...EMC Item 30 kVA 40 kVA 80 kVA Safety regulations EN62040 1 2013 IEC62040 1 2013 YD T1095 2010 EMC EN62040 2 IEC62040 2 IEC61000 3 11 IEC61000 3 12 IEC61000 2 2 IEC61000 4 2 EN61000 4 3 EN61000 4 6 IEC61000 4 8 8 5 Mains Input Electrical Specifications Item 30 kVA 40 kVA 80 kVA Input system Three phase four wire PE wire Rated input voltage 380 V AC 400 V AC or 415 V AC line voltage UPS5000 A 30 kVA...

Страница 191: ...voltage 380 V AC 400 V AC or 415 V AC line voltage Rated frequency 50 Hz 60 Hz Frequency range 6 Hz adjustable 0 5 6 Hz 2 Hz by default Input mode The mains input and bypass input use different power sources or share a power source 8 7 Battery Specifications Item 30 kVA 40 kVA 80 kVA Battery voltage 360 528 V DC 12 V batteries 30 44 batteries 32 by default If there are 36 44 batteries output power...

Страница 192: ...ire Voltage 380 V AC 400 V AC or 415 V AC tolerance 1 line voltage Frequency In normal mode the mains frequency is synchronized with the bypass input frequency In battery mode the frequency is 50 Hz or 60 Hz tolerance 0 05 Total harmonic distortion of output voltage THDv 1 full linear load 4 full non linear load Output PF 1 Transfer time 0 ms uninterruptible transfer 20 ms interruptible transfer O...

Страница 193: ...VA 40 kVA 80 kVA Parallel system reliability Parallel signals use redundancy design Parallel system ECO Supported UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual 8 Technical Specifications Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 183 ...

Страница 194: ... UPS Load Parallel System Load Environment Monitoring Runtime Alarms Active Alarms Hist Alarms Sort Alarms Clear Faults Control Buzzer Settings User Settings Comm Settings System Settings Input Settings Output Settings UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual A Menu Hierarchy Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 184 ...

Страница 195: ...in Batteries Sync Par Param available in parallel UPS mode Clear Historical alarms Clear Operation logs About Model ESN MDU ver PWR ver A 2 Menus on the WebUI Level 1 Menu Level 2 Menu Level 3 Menu Monitoring Active Alarms N A Real time Data UPS Module Param Settings System Settings Input Settings Output Settings Bypass Settings UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual A Menu Hierarchy Issue...

Страница 196: ... N A Config User Mgmt User Mgmt Idle Timeout Logout Site Config Time zone System Date and Time DST System Information SNMP SNMP Trap Certificate Management Configuration Management Multi brand Management Configure Alarm Notification Server Configure Alarm Notification Email Address ModbusTCP Certificate Management UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual A Menu Hierarchy Issue 13 2022 01 19 ...

Страница 197: ...agement RCCMD RCCMD SSL Encrypted Transmission Event Configuration RCCMD Certificate Management Maint Calib Module ECM Commissioning Var Module ECM Upgrade Software N A BSP Upgrade N A Download N A UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual A Menu Hierarchy Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 187 ...

Страница 198: ...it 0001 2 Cable connections are incorrect The mains is not normal The mains input fuse for the power unit is blown 1 Check whether cables to mains are disconnected loose or incorrectly connected 2 If cable connections are correct measure the mains voltage with a multimeter If the mains voltage is less than 80 V the mains voltage is not normal if the mains voltage exceeds 88 V the power unit sampli...

Страница 199: ...k the voltage system and bypass voltage thresholds configured on the LCD 0010 2 The bypass frequency range is not correctly set The bypass input frequency is not normal 1 Check the bypass input voltage or cable connections with a multimeter 2 Check the bypass input frequency Check the rated frequency and frequency range configured on the LCD 0011 1 Bypass ph reversed Minor The phase sequence of th...

Страница 200: ...f it trips close the BCB box switch 0022 1 No battery Minor There is no battery string The battery string is not properly installed The power unit battery fuse is blown 1 Check that battery cables are correctly connected 2 Check that the battery terminal voltage is normal 3 Check that the battery fuse in the power unit is intact 0025 1 Battery overvoltage Minor The configured number of batteries i...

Страница 201: ...Battery ground fault Critical The battery string is not properly grounded The battery ground monitoring cable is faulty The dry contact board is faulty 1 Check whether the positive and negative terminals of the battery string are grounded or have sufficient resistance to the ground 2 Check whether the battery grounding failure detector is faulty by replacing it with a new one 3 If no battery groun...

Страница 202: ...y undervoltage Critical The UPS has worked in battery mode for an extended amount of time The charger is faulty 1 Check whether the battery voltage is normal 2 Check whether the output is overloaded 3 Check whether any battery is damaged If yes replace the battery 4 Check whether any battery charger generates an alarm If yes replace the faulty unit 0040 7 Rectifier abnormal Critical The fan for th...

Страница 203: ...ibutions are normal replace the power unit 0061 2 Inverter alarm Minor The I2C bus is not normal The E2PROM is faulty 1 Rectify the fault and check whether the alarm is cleared 2 If the alarm is generated again replace the power unit 0061 7 Inverter alarm Minor The bypass waveform is not normal If not all units generate the alarm start the UPS transfer it to normal mode and replace the faulty unit...

Страница 204: ...Minor A large power RCD load is instantly connected or the output load short circuits The inverter bridge short circuits 1 Check the load 2 If the load is normal replace the power unit 0566 1 Output overload Minor The load is excessive Derating reduces the rated system power The unit is damaged 1 Check that there is no overload 2 Check that the unit power is not derated due to a fan fault 3 If the...

Страница 205: ...verload 0583 1 Inter rack par cable abnormal Critical The inter rack parallel system CAN bus is disconnecte d or short circuited Only one rack works in a parallel system An ECM is faulty 1 Check the inter rack parallel system CAN bus 2 Rectify the disconnection or short circuit fault 3 Replace the ECM 0583 4 The inter rack industrial frequency synchronizatio n cable is broken Replace the inter rac...

Страница 206: ...or The system frequently transfers to bypass mode due to overload timeout or load impact Check the load 0087 1 System transfer to bypass Warning The neighboring UPS is not normal and transfers to bypass mode Check the reason why the neighboring UPS transfers to bypass mode 0089 1 Rack output overload Minor The load is excessive Check the load Remove some loads or expand the UPS power capacity if t...

Страница 207: ... The running status is displayed No further measures are required 0342 Mains input breaker open Critical The mains input circuit breaker is OFF The running status is displayed No further measures are required 0343 BPM input breaker open Critical The bypass input circuit breaker is OFF The running status is displayed No further measures are required 0340 The maintenance circuit breaker is ON Minor ...

Страница 208: ... frequency range are correctly set 3 Check that the bypass cables and circuit breakers are correctly connected 0098 1 Bypass current not shared Minor The output and input circuit breakers are OFF The length of the bypass input or output cables is incorrect The bypass SCR open circuits 1 Check that the output and bypass input circuit breakers on each rack are ON 2 Check that bypass input and output...

Страница 209: ...is loose Parameters are set incorrectly 1 Check the dual bus connector 2 Check the parameter settings 0102 1 Maint breaker misoperation Critical The user operation is incorrect 1 Shut down the inverter and then close the maintenance circuit breaker 2 After maintenance open the maintenance circuit breaker and then start the inverter 0380 In self check Warning The inverter is in self check Wait unti...

Страница 210: ...Direct Current D G Diesel Generator DIP Dual In Line Package DSP Digital Signal Processing E ECM Energy Control Module ECO Economy Control Operation EMC Electromagnetic Compatibility EOD End Of Discharge EPO Emergency Power Off ESN Equipment Serial Number UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual C Acronyms and Abbreviations Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 200 ...

Страница 211: ...rthing R RS485 Recommend Standard 485 S SNMP Simple Network Management Protocol SOC State Of Charge SSL Secure Sockets Layer STS Static Transfer Switch T THDi Total Distortion Of The Input Current Waveform THDv Total Harmonic Distortion Of Output Voltage U UI User Interface UPS Uninterruptible Power System UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual C Acronyms and Abbreviations Issue 13 2022 01...

Страница 212: ...V VRLA Valve Regulated Lead Acid W WebUI Web User Interface UPS5000 A 30 kVA 40 kVA and 80 kVA User Manual C Acronyms and Abbreviations Issue 13 2022 01 19 Copyright Huawei Technologies Co Ltd 202 ...

Отзывы: