background image

KE 4256-3230 Keatec T Series UPS 10-40K 380Vac Users Guide English 20170126                                  This manual is for qualified personnel only 

 

 

T SERIES UPS 

10-40kVA 380Vac 3PH 

   

 

User Guide 

 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER 

(A)  MAKES  NO  WARRANTY  AS  TO  THE  ACCURACY,  SUFFICIENCY  OR  SUITABILITY  OF  ANY  TECHNICAL  OR  OTHER 

INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION; 

(B)  ASSUMES  NO  RESPONSIBILITY  OR  LIABILITY  FOR  LOSSES,  DAMAGES,  COSTS  OR  EXPENSES,  WHETHER  SPECIAL, 

DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE 

USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK; AND 

(C)  REMINDS  YOU  THAT  IF  THIS  MANUAL  IS  IN  ANY  LANGUAGE  OTHER  THAN  ENGLISH,  ALTHOUGH  STEPS  HAVE  BEEN 

TAKEN  TO  MAINTAIN  THE  ACCURACY  OF  THE  TRANSLATION,  THE  ACCURACY  CANNOT  BE  GUARANTEED.  APPROVED 

CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE.   

(D) INFORMS YOU THE INFORMATION IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. 

(E) RESERVES ALL RIGHTS. 

   

 

Summary of Contents for T 3310E

Page 1: ...BILITY OR LIABILITY FOR LOSSES DAMAGES COSTS OR EXPENSES WHETHER SPECIAL DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATIO...

Page 2: ...ion notes 7 3 5 External Protective Devices 7 3 6 Power Cables 8 3 7 Power cable connections 8 3 8 Battery connection 11 3 9 UPS Parallel Installation 12 3 10 Computer access 13 4 Operation 15 4 1 Ope...

Page 3: ...he risk of electric shock securely ground the UPS 4 Batteries can present a risk of electrical shock or burn from high short circuit current Observe proper precautions 5 Only qualified service personn...

Page 4: ...e battery for this series UPS can be configured using 16 18 or 20 12V batteries 40kVA the battery for this series UPS can be configured using 32 34 36 38 or 40 12V batteries Charging Current is config...

Page 5: ...the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage To file a...

Page 6: ...nal block without cover 1 LCD LED panel 2 RS485 port 3 Dry contact port 4 Parallel port 1 5 USB port 6 Parallel port 2 7 RS232 8 Power Switch 9 REPO port 10 I P Switch 11 Terminal block for AC IN OUT...

Page 7: ...ck without cover 1 LCD LED panel 2 Intelligent Slot 1 SNMP card Relay card 3 Intelligent Slot 2 SNMP card Relay card 4 Battery Power Switch 5 Dry contact port 6 USB port 7 RS485 port 8 REPO port 9 RS2...

Page 8: ...life and capacity In a normal installation the battery temperature is maintained between 15 C and 25 C Keep batteries away from heat sources or main air ventilation area etc WARNING Typical battery pe...

Page 9: ...and physical WARNING Upon starting ensure that you are aware of the location and operation of the external isolators which are connected to the UPS input bypass supply of the mains distribution panel...

Page 10: ...Users Guide English 20170126 This manual is for qualified personnel only Page 9 UPS are open Check to see if they are electrically isolated and post any necessary warning signs to prevent their inadv...

Page 11: ...negative There are 3 connectors for GROUND under the terminal block 30 40kVA Terminal sequence from left to right Input phase A L1 input phase B L2 input phase C L3 input Neutral line output phase A L...

Page 12: ...and the battery negative are connected to the UPS respectively The battery sets between the Battery anode and the neutral are called positive batteries and those between neutral and cathode are called...

Page 13: ...nd for battery capacity 65AH charger current 9 75A When connecting 32 34 36 38 40 batteries set the battery quantity and its capacity after the UPS starts in AC mode Charger current will be adjusted a...

Page 14: ...allel system For a group of paralleled modules behave as one large UPS system and in order to assure that all modules are equally utilized and comply with relevant wiring rules follow the requirements...

Page 15: ...s Guide English 20170126 This manual is for qualified personnel only Page 14 The Software Parameter Setting window will open as below Select the COM port related to the UPS set the baud rate as 9600 a...

Page 16: ...tion between UPS and computer CAUTION Do not use the PC Software to set output voltage and frequency while the inverter is running Shut down the inverter before using the PC Software to set the output...

Page 17: ...not critical the UPS can be set at ECO mode in order to increase the efficiency of the power supplied In ECO mode the UPS works in Line interactive mode so the UPS will transfer to bypass supply When...

Page 18: ...UPS is operating normally it may take 60 seconds to boost up the system and perform self test completely Switch off the MAINS to simulate utility failure The rectifier will turn off and the battery s...

Page 19: ...al operation until it has been verified that there are no internal UPS faults Switch ON the output breaker Switch ON the input breaker The UPS powers from the static bypass instead of the maintenance...

Page 20: ...shut down the UPS and the LOAD After all power switches isolators and circuit breakers are opened there should be no output On line mode Press OFF to shut down the UPS wait about 30s Open the BATTERY...

Page 21: ...tery power switch for standard UPS Open the OUTPUT breaker The UPS shuts down WARNING Wait for about 5 minutes for the internal DC bus and capacitors to completely discharged 4 2 6 Parallel UPS Settin...

Page 22: ...KE 4256 3230 Keatec T Series UPS 10 40K 380Vac Users Guide English 20170126 This manual is for qualified personnel only Page 21...

Page 23: ...ork Mode value then click Set to save the values as shown below The UPS will sound a beep to indicate that the setting has been correctly saved From the Data Set window select Ups ID and put the ID va...

Page 24: ...e cannot be connected when setting the parallel parameters If after setting the UPS paralleling of UPS is required Power off all the UPS Connect all the UPS according to parallel cable installation Th...

Page 25: ...Data Press key for short time to select Data page the Data page displays input data and output data INPUT Press Off key for short time to enter Data the first page is mains input and bypass input data...

Page 26: ...glish 20170126 This manual is for qualified personnel only Page 25 OUTPUT press key for short time to move to the second page the second page of Data is Output data OUTPUT press key for short time to...

Page 27: ...English 20170126 This manual is for qualified personnel only Page 26 LOAD press key for short time to move to the fourth page the fourth page of data is Load data INSIDE press key for short time to mo...

Page 28: ...the LCD LED DSP and the UPS type SETTING User press key for short time to move to the setting page then press OFF key to enter setting user page Press key to change item press OFF key to enter item a...

Page 29: ...Grade 220 230 240 F_Output Grade 50 and 60 F_mode CVCF and Non CVCF Test type 10s 10min and EOD Test Cycle 1 30 days Equipment ID Device address is 1 15 it is the MODBUS device address used for RS232...

Page 30: ...every second Maintenance Bypass press OFF key to enter item and confirm value press change value Upper Limit 5 10 15 20 25 Lower Limit 10 20 30 45 F_Range 1 2 4 5 10 Maintenance Battery press OFF key...

Page 31: ...only Page 30 I Maxcharge 1 10A Maintenance Parallel This item can be selected after the work mode is set to parallel Press OFF key to enter item and confirm value press change value ID 1 4 UPS ID Num...

Page 32: ...380Vac Users Guide English 20170126 This manual is for qualified personnel only Page 31 Record Event Press to select Up or Down or Delete Press OFF key to confirm Record Fault Press to select Up or D...

Page 33: ...T EXTINGUISH LIGHT CAUTION X means it is determined by other conditions UPS Alarm Information Faults No UPS Alarm Warning Buzzer LED 1 Rectifier Fault Beep continuously Fault LED lit 2 Inverter fault...

Page 34: ...w pre warning Once per second Battery LED blinking 36 Internal Communication Error Once per 2 seconds Fault LED blinking 37 DC component over limit Once per 2 seconds INV LED blinking 38 Parallel Over...

Page 35: ...ripheral monitoring devices via DB9 female The Relay card facilitates the effective monitoring of the real time status of UPS and timely feedback when an abnormal situation occurs such as UPS failure...

Page 36: ...e 4 Wires and Ground Rated Voltage 380 400 415Vac Power Factor 0 9 Voltage Regulation 1 Frequency Utility Mode 1 2 4 5 10 of the rated frequency optional Battery Mode 50 60 0 2 Hz Crest Factor 3 1 THD...

Page 37: ...ommunication Interface USB RS485 Parallel optional Coupler dry contact Intelligent slot SNMP card optional Relay card optional Environment Operating Temperature 0 40 Storage Temperature 25 55 Humidity...

Page 38: ...min 125 last 10min 150 last 1min 150 shut down UPS immediately Bypass Mode Breaker 63A Breaker 80A Short Circuit 164A Peak Overheat Line Mode Switch to Bypass Backup Mode Shut down UPS immediately Bat...

Page 39: ...is well connected Switch ON output breaker 4 Utility LED is flashing Utility voltage exceeds UPS input range If the UPS operates in battery mode pay attention to the remaining backup time needed 5 Ba...

Page 40: ...t UPS USB port Description Pin 1 Pin 1 PC 5V Pin 2 Pin 2 PC DPLUS signal Pin 3 Pin 3 PC DMINUS signal Pin 4 Pin 4 Signal ground Available function of USB Monitor UPS power status Monitor UPS alarm inf...

Page 41: ...ort PC RS232 port UPS RS232 port Pin 2 Pin 2 UPS send PC receive Pin 3 Pin 3 PC send UPS receive Pin 5 Pin 5 ground Available function of RS232 Monitor UPS power status Monitor UPS alarm info Monitor...

Page 42: ...2 4 Pin 2 4 485 B Pin7 Pin7 12Vdc Pin8 Pin8 GND Available function of RS485 Monitor UPS power status Monitor UPS alarm info Monitor UPS running parameters Timing off on setting Battery environment tem...

Page 43: ...alified personnel only Page 42 Appendix 6 Dry contact port communication port definition Definition of Male port Instruction UPS Instruction Pin1 UPS Battery Low Pin2 AC Power Failure Pin3 Turn off UP...

Page 44: ...tion between the button and UPS REPO port Button UPS REPO Description Pin 1 Pin 1 EPO Pin 2 Pin 2 GND A remote emergency stop switch Dry contact signal and normally open not provided can be installed...

Reviews: