UPS2000-G-(6 kVA-20 kVA)
User Manual
9 Technical Specifications
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
91
Item
6 kVA
10 kVA
15 kVA
20 kVA
Rated capacity
6 kVA
10 kVA
15 kVA
20 kVA
Output power factor
(PF)
0.9
Rated output voltage 220 V AC, 230 V AC, or 240 V
AC (single-phase output; select a
voltage system by setting a
voltage level on the LCD.)
220 V AC, 230 V AC, or 240 V
AC (single-phase output; select
a voltage system by setting a
voltage level on the LCD.)
380 V AC, 400 V AC, or 415 V
AC (three-phase output; select
a voltage system by setting a
voltage level on the LCD.)
Output voltage
tolerance
±1%
Total harmonic
distortion of output
voltage (THDv)
< 4% (non-linear load)
< 2% (resistive load)
Crest factor
A maximum of 3:1
Inverter overload
capability
105% ≤ load < 125%: transfer to bypass mode after 5 minutes
125% ≤ load < 150%: transfer to bypass mode after 1 minute
Load ≥ 150%: transfer to bypass mode after 100 milliseconds
The UPS stops supplying power if the bypass is abnormal.
Dynamic voltage
tolerance
±5%
Output voltage
unbalance
N/A
±1% (balanced load)
±3% (unbalanced load)
Average frequency
tracking rate
0.5–2 Hz/s (single UPS) or 0.5–1 Hz/s (parallel system)
Power segment
(only in single UPS
mode)
If overloaded, the UPS disconnects from secondary loads and
checks whether it is still overloaded.
In battery mode, the UPS disconnects from secondary loads if
the battery voltage is less than the specified value.
In battery mode, the UPS disconnects from secondary loads if
the discharge time is more than the specified value.
9.6 Battery Specifications
Table 9-6
Battery specifications
Item
6 kVA
10 kVA
15 kVA
20 kVA