UPS2000-G-(6 kVA-20 kVA)
User Manual
4 Control Panel
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
52
−
Subn. mask
parameter
Set a subnet mask for the SNMP card. The value ranges from
0.0.0.0
to
255.255.255.255
. The default value is
255.255.255.0
.
−
Gateway
parameter
Set a gateway address for the SNMP card. The value ranges from
1.0.0.0
to
223.255.255.255
. The default value is
192.168.0.1
.
2.
If a Modbus card is connected, the following parameters are displayed:
Figure 4-28
Modbus card settings
−
Comm. address
parameter
Set a communications address for the Modbus card over the dual in-line package
(DIP) switch on the Modbus card. The value cannot be changed on the LCD.
−
Baud rate
parameter
Set a baud rate for the Modbus card over the DIP switch on the Modbus card. The
value cannot be changed on the LCD.
3.
If a dry contact card is connected, set the following parameters:
Figure 4-29
Dry contact card settings
Multiple statuses can be associated with one dry contact, but one status cannot be associated with
multiple dry contacts.
−
Normal mode
parameter
Set the output dry contact associated with normal mode. When the UPS is in normal
or ECO mode, this dry contact is enabled. The value ranges from
Dry contact1
to
Dry contact6
. The default value is
Dry contact1
.
−
Battery mode
parameter
Set the output dry contact associated with battery mode. When the UPS is in battery
or ECO mode, this dry contact is enabled. The value ranges from
Dry contact1
to
Dry contact6
. The default value is
Dry contact2
.
−
Bypass mode
parameter
Set the output dry contact associated with bypass mode. When the UPS is in bypass
or ECO mode, this dry contact is enabled. The value ranges from
Dry contact1
to
Dry contact6
. The default value is
Dry contact3
.
−
Batt. undervolt
parameter