4 Control Panel
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
51
Basic Settings Screen
Figure 4-26
Basic Settings screen
Language
parameter
You can select
Chinese
,
English
(preset),
Turkish
,
French
, and
Russian
.
Change Password
parameter
You can change the password by choosing
Settings
>
Basic Settings
>
Change
Password
. The preset password is
000001
. The password allows you to enter the
Settings
screen.
Change Feature Code
parameter
You can change the feature code by choosing
Settings
>
Basic Settings
>
Change
Feature Code
. The preset feature code is
999999
. The feature code is used to restore the
preset password.
Communication Card Screen
1.
If an SNMP card is connected, set the following parameters:
Figure 4-27
SNMP card settings
−
IP alloc.
parameter
Specifies the DHCP address allocating mode. The options include
Manual
and
Automatic
. The default value is
Manual
. After the allocating mode is set to
Automatic
, an
Allocating
dialog box is displayed on the screen. If allocation
succeeds, the new IP address is displayed. If allocation fails, the IP address restores
to the default one: 192.168.0.10. If the allocating mode is set to
Automati
c, you can
only query the IP address but cannot set the IP address manually.
If the UPS monitor does not support the DHCP function, after the DHCP is selected for the SNMP card,
you cannot set the IP address of the SNMP card on the UPS monitor. You are advised to update the
version of the UPS monitor.
−
IP address
parameter
Set an IP address for the SNMP card. The value ranges from
1.0.0.0
to
223.255.255.255
. The default value is
192.168.0.10
.