UPS2000-G-(6 kVA-20 kVA)
User Manual
B LCD Menus and Parameters
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
106
Main
Menu
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range
Preset Value
after the
inverter shuts
down)
Self-Load
(configurable
after the
inverter shuts
down)
Output power
ratio
20%–100%
80%
Self-load mode
Enabled and Disabled
Disabled
Others
(configurable
after the
inverter shuts
down)
Recovery delay
time
0–900 seconds
5S
Max. BPS
transfers
1–3
3
Output
transformer
Enabled and Disabled
Disabled
Generator
mode
Weak adaptability mode,
Balanced mode, and
Strong adaptability mode
Balanced mode
Auto check
capa.
Enabled and Disabled
Enabled
Auto start
Enabled and Disabled
Disabled
No battery
alarm
(configurable
only when
batteries are not
connected)
Enabled and Disabled
Enabled
Battery
Paramete
rs
Basic
Batteries
/Positive
batteries/Negati
ve batteries
(configurable
in non-battery
mode)
16–20 monoblocs
20 Monobloc
Battery
capacity
(configurable
in non-battery
mode)
7–1000 Ah
For the UPS2000-G-6
kVA, the default
value is
7 Ah
on a
standard model and
40
Ah
on a long backup
time model.
For the
UPS2000-G-10 kVA,
the default value is
9
Ah
on a standard
model and
65 Ah
on a