8 Emergency Handling
Issue 07 (2020-04-10)
Copyright © Huawei Technologies Co., Ltd.
80
8
Emergency Handling
8.1 Background
To ensure the DC supply remains uninterruptible, take emergency measures to rectify any DC
output faults.
DC output faults include:
AC power distribution circuits are irrecoverably damaged.
DC loads or DC power distribution components are short-circuited.
Rectifiers shut down because the SMU is out of control.
Rectifiers lock out due to DC output overvoltage.
Disasters occur.
8.2 AC Power Distribution Faults
If the AC input to rectifiers is interrupted due to AC PDU faults, connect AC input power
cables to rectifier circuit breakers.
8.3 AC Power Failure
If an AC power failure will be rectified soon, use batteries to power DC loads. If an AC power
failure will last a long time or is caused by unknown reasons, start a diesel generator (D.G.).
You are advised to keep the D.G. running for at least 5 minutes before switching the power
system to the D.G. mode to minimize the impact of D.G. startup on power equipment. You
also need to switch on rectifier input circuit breakers one by one to minimize the impact of
rectifier startup on the D.G.
8.4 DC Power Distribution Faults
If a DC power distribution unit (PDU) is faulty, take emergency measures as follows:
1.
Load short-circuit: Remove the corresponding load fuse. If you need to replace the fuse
immediately, check that the fuse can be replaced with the power off.