Default Value Setting Value
Rated
Capacity
150 Ah
Rated capacity
of the batteries
in a battery
string.
NOTE
The batteries
controlled by
one circuit
breaker or fuse
are called a
battery string.
Other
Parameters
Installation
Time
-
Set to the
current date
If battery routes 1 and 2 are respectively connected to a battery string (each battery string consists of
four 12 V, 150 Ah batteries in series), set
Battery1 Connected
and
Battery2 Connected
to
Yes
and
others to
No
, and set
Rated Capacity
to
150 Ah
.
If battery route 1 is connected to two battery strings in parallel (each battery string consists of four
12 V, 150 Ah batteries in series), set
Battery1 Connected
to
Yes
and others to
No
, and set
Rated
Capacity
to
300 Ah
.
10.6 Setting Sensor Parameters
Set the sensor parameter to
Yes
or
None
based on actual sensor configurations.
shows the LCD menus and parameter settings.
Table 10-4
Sensor parameter settings
Main
Menu
Second-
Level
Menu
Third-
Level
Menu
Fourth-
Level
Menu
Default
Value
Setting
Parameters
Settings
Power
System
Sensor
Config.
Para.
Water
Sensor
None
Set this
parameter to
Yes
or
None
based on actual
sensor
configurations.
Smoke
Sensor
None
Ambient
Temp.
Sensor
None
Ambient
Humi.
Sensor
None