SUN2000-(55KTL, 60KTL) Series
User Manual
7 Man-Machine Interactions
Issue 06 (2020-01-03)
Copyright © Huawei Technologies Co., Ltd.
77
No. Parameter Description
Unit Default
Value
Value Range
Remarks
5
Power
quality
optimizatio
n mode
If
Power quality
optimization mode
is
set to
Enable
, the
inverter output current
harmonics will be
optimized.
N/A
Disable
Disable
Enable
N/A
6
PV module
type
This parameter is used
to set different types of
PV modules and the
shutdown time of the
concentration PV
modules. If the
concentration PV
modules are shaded,
the power drops
drastically to 0 and the
SUN2000 shuts down.
The energy yield
would be affected
since it takes too long
for the power to
resume and SUN2000
to restart. The
parameter does not
need to be set for
crystalline silicon and
filmy PV modules.
N/A
Crystalline
silicon
Crystalline
silicon
Film
CPV 1
CPV 2
If
PV module
type
is set to
Crystalline
silicon
or
Film
,
the SUN2000
automatically
detects the power
of PV modules
when they are
shaded and shuts
down if the
power is too low.
When the
concentration PV
modules are
used:
−
If
PV module
type
is set to
CPV 1
, the
inverter can
quickly
restart in 60
minutes when
the input
power of PV
modules
drops
drastically
due to
shading.
−
If
PV module
type
is set to
CPV 2
, the
inverter can
quickly
restart in 10
minutes when
the input
power of PV
modules
drops
drastically
due to
shading.