SUN2000-(55KTL, 60KTL) Series
User Manual
5 Electrical Connections
Issue 06 (2020-01-03)
Copyright © Huawei Technologies Co., Ltd.
41
Figure 5-11
Connecting an AC output power cable (four-core cable)
The cable colors shown in figures are for reference only. Select an appropriate cable according to the
local standards.
Step 5
Tighten the sealing nut and seal the cable gland.
----End
5.6 Connecting DC input power cables
Prerequisites
Before connecting DC input power cables, ensure that the DC voltage is within the safe
range (lower than 60 V DC) and that the two DC switches on the SUN2000 are OFF.
Failing to do so may result in electric shocks.
When the SUN2000 is grid-tied, it is not allowed to work on DC circuit, such as
connecting or disconnecting a PV string or a PV module in a PV string. Failing to do so
may cause electric shocks or arcing (which may further cause fire).