3
1. Do not use solid conductor hard cables.
2. 3-core outdoor cables (L1, L2, L3) are configured for the SUN2000-24.5KTL/28KTL.
The table lists only the recommended cable specifications. For more information about cable
specifications, see the User Manual.
2
Electrical Connection
OT-5.5 mm
2
-M6
PE terminal
1. It is recommended that the ground cable be connected to a nearby ground position.
2. To enhance the corrosion resistance performance of the PE terminals, apply silica gel on them
after connecting the ground cable.
Install a Ground Cable
2.1
Install AC Output Power Cables
2.2
Inverter Model
Cross-sectional Area of the Cable
(Recommended)
SUN2000-24.5KTL/28KTL
8.0 mm
2
(8 AWG)
NOTE
NOTE
M6
5 N·m