DEFAULT CONFIGURATION IN TRACKSO IOT GATEWAY 
 

Inverter ID: 

1, 2, 3, 4 …. 

Continuous numbering starting with 1, 

 (Range: 

1 to 247)  

Baud Rate: 

9600 (Default) (Values: 

9600, 19200, 38400)

 

Data Bits: 8 ,Stop Bit: 1 ,Parity: None 

CONFIGURATION AT THE INVERTER END 

Connect the SUN2000 to the mobile phone that runs SUN2000 app through a Bluetooth module or USB data cable (same as used for 
commissioning of the inverter) 

 

 

 

 

 

 

 

 

 

 
After the successful login, the Quick Settings screen or Function Menu screen is displayed 

Huawei APP Screenshot 

Settings 

 

Set Data & Time  

For a precise calculation of the statistics in the inverter itself and in a monitoring 

system, date and time have to be correct.

 

Set Baud Rate 

Default Value for configuration TrackSo – 9600 

If you connect multiple inverters via RS485, set the same baud rate on each 

inverter.

 

Set Protocol 

Modbus RTU protocol is to be selected for proper communication setup between 

Huawei and TrackSo IoT Gateway 

Set communication Address 

 

The address/ID is used to identify the inverter in a RS485 connection

 

 

Set a different inverter ID for each inverter in the PV plant. Otherwise, the 

inverters cannot be correctly identified.  

 

On the last inverter in the RS485 connection, switch on the RS485 termination 

resistor 

Содержание SUN2000-(25KTL, 30KTL)-US

Страница 1: ...he connections from the Terminal Block to TrackSo IoT Gateway as mentioned in Table HT1 Provide 12V external supply to TrackSo IoT Gateway via 12V 2A DC adaptor provided in the package Figure H1 Huawei SUN2000 33KTL 36KTL 40KTL 55KTL 60KTL String Inverter communicatio port Table HT1 Huawei SUN2000 33KTL 36KTL 40KTL 55KTL 60KTL RS485 connections with TrackSo IoT Gateway Note RS485 Out Used in case ...

Страница 2: ...2 Please make the connections from the Terminal Block to TrackSo IoT Gateway as mentioned in Table HT2 Provide 12V external supply to TrackSo IoT Gateway via 12V 2A DC adaptor provided in the package Table HT2 Huawei SUN2000 25KTL 30KTL RS485 connections with TrackSo IoT Gateway Note RS485 Out Used in case of Multiple Inverter Connection Daisy chain Huawei Pin no Assignment TrackSo Pin No Assignme...

Страница 3: ...gs Set Data Time For a precise calculation of the statistics in the inverter itself and in a monitoring system date and time have to be correct Set Baud Rate Default Value for configuration TrackSo 9600 If you connect multiple inverters via RS485 set the same baud rate on each inverter Set Protocol Modbus RTU protocol is to be selected for proper communication setup between Huawei and TrackSo IoT ...

Страница 4: ... Pin 2 4 of Inv 1 is connected to Pin 1 3 of next inverter in Daisy Chain When two or more inverters are in parallel communication the terminal resistor should be switched on or else it may cause communication interruption NOTE The above details are mentioned in the Installation Operation Manual for SUN2000 33KTL 36KTL 40KTL 55KTL 60KTL or Installation Operation Manual for SUN2000 25KTL 30KTL ...

Страница 5: ...he installed location LED NAME DESCRIPTION GREEN POWER Light when Power on the device RED GSM LED Status Connection State Flashing ON for 100ms and OFF for 100ms SIM Card not found Flashing ON for 500ms and OFF for 500ms Searching for GSM Network Flashing ON for 0 1s and OFF for 2 9s Once at every 3sec GSM Network Registered Flashing twice at every 3sec GPRS IP Connected Flashing 5times GPRS IP Se...

Страница 6: ...ted NC not connected PIP Connected to TrackSo Server or not CONT connected NC not connected LOG no of data points stored in devices incase of no interet 6 If the GSM light starts flashing 5 times then Login to www trackso in with your Username Password 7 Click on Units from the menu bar You will be able to view your installed unit in the table as shown below 8 Check if the Status becomes Receivein...

Страница 7: ...op right of the screen and click on Event Ingestion Logs in the dropdown 10 Check if there is some log generated at the time of installation of the TrackSo IoT Gateway device a If NO please restart the device and try the same flow again b If YES email us at we freespirits in to consult the same ...

Отзывы: