R240D
Hardware Installation and Maintenance Guide
5 Appendix
Issue 03 (2016-01-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
106
Com
pone
nt
No.
Applic
able
Scope
Check Item
cables are fixed on a sharp mechanical part, take protection
measures.
7
General
The equipotential cables between the attaching cabinets shall
be securely connected.
8
General
The lugs for the power cables and ground cables are soldered
or crimped securely.
9
General
The lugs and bare wires of power cables and ground cables
are tightly wrapped with tubes or insulation tape without any
exposed copper wire. Flat washers and spring washers are
installed correctly.
10
General
Labels are filled and attached to power cables and ground
cables correctly.
11
General
Power cables deployed outdoors must be covered by PVC
tubes.
Optica
l
modul
e
1
General
A single-mode fiber can only be used with a single-mode
optical module while a multimode optical fiber can only be
used with a multimode optical module. On most optical
modules, the fibers of different types cannot be used
together.
2
General
The labels of pluggable optical modules are smoothly
attached and intact, and cannot be covered by the optical
modules.
3
General
If a short-distance optical fiber is used for a long-distance
optical module, especially in loopback scenarios, use an
optical attenuator to prevent the optical module from being
burnt.