Purchase List (North America)
The following table lists materials not included in Huawei auxiliary material packages. Purchase these materials
before installation. All installation operations in this document are only for your reference.
DC power
supply
(3) PDU power cable
terminal (connected to the
DC power supply)
(1) PDU power
cable
(2) PDU power cable
terminal (connected to
the PDU)
(5) Ground cable terminal
(connected to the cabinet)
(4) Cabinet
ground cable
(6) Ground cable terminal
(connected to the ground
bar)
10
Item
Sub-item
Remarks
PDU power
cable
(1) PDU power cable
It is advised to use 6 AWG electronic power cables, each
of which spans over a maximum distance of 8.8 m (29 ft).
(2) PDU power cable terminal
(connected to the PDU)
Single insulated wire ferrules
(3) PDU power cable terminal
(connected to the DC power supply)
Terminal specifications depend on the DC power supply.
Cabinet
ground
cable
(4) Cabinet ground cable
It is advised to use 6 AWG electronic power cables.
(5) Ground cable terminal
(connected to the cabinet)
Two-Hole Lug, #6AWG, 3/8" stud spacing, 25.4 mm (1 in)
Hole Distance
(6) Ground cable terminal
(connected to the ground bar)
Terminal specifications depend on the ground position.