2 Installing/Routing Ground and Power Cables
Install Power Cables
– Install Copper Fittings (DPD63-8-8)
e
Copper Plates
Copper fitting
Right
Left
Do not install the copper plates in the power supply output area of the DC PDU. You should
determine whether the copper plates are installed in the power supply input area only according to
the on-site power supply situation.
Determine the input terminal pairs that must be connected internally. Then position the copper
plates to the NEG(-) input terminals on the air breakers on the PDU. Tighten the screws on the
air breakers to secure the copper plates. Note that there are copper plates targeted for the left
and right power input areas and they are not interchangeable.
Install an appropriate copper fitting on the RTN(+) input terminals in the middle of the PDU.
Connect external power cables (blue) to the NEG(-) input terminals and BGND cables (black) to
RTN(+) input terminals.