Item
Indicator
Color
Status Description
Cause of the Abnormality
Protection
indicator
Yellow
If the indicator is off,
the EPS200-4850A is
running properly. If the
indicator is on, an
exception occurs.
A temperature alarm is
generated (if the temperature
exceeds 65°C, the
EPS200-4850A will be powered
off), or the EPS200-4850A is in
the dormant state (the indicator
is on and no alarm is generated).
Fault indicator
Red
If the indicator is off,
the EPS200-4850A is
running properly. If the
indicator is on, an
exception occurs.
The EPS200-4850A is powered
off due to over-voltage or over-
temperature, or fans are faulty,
or the EPS200-4850A has no
output due to its internal faults.
DC output
voltage
-
The normal voltage
ranges from –43.2 V
DC to –57 V DC
-
diagrams the AC power supply system of the CX600-X16. The input AC power is
converted into regulated DC power by an EPS200-4850A. The resulting DC power output is
connected to the PEMs through external cables to supply power for all boards and fan modules.
Two -48V power inputs are joined on the board.
, each DC power input contains one -48 V power input and one RTN input. Two
separated RTN inputs are joined on the board.
HUAWEI CX600-8/16/X3/X8/X16 Metro Service Platform
Hardware Description
3 CX600-X16
Issue 03 (2013-11-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.