Technical Manual
Airbridge BTS3606A CDMA Base Station
System Description
Chapter 7 Technical Specifications
7-2
Cabinet dimensions
1700 mm x 1200 mm x 1000 mm (Height
×
Width
×
Depth)
220/230/240V AC:
Single-phase/three-phase input
Voltage range: 176 V to 264 V
Frequency range: 47 Hz to 63 Hz
Over-voltage protection when the voltage reaches 290V.
Power supply
110/115/127V AC:
Single-phase/three-phase input
Voltage range: 90 V to 135 V
Frequency range: 47 Hz to 63 Hz
Under-voltage protection when the voltage reaches 85V.
Cabinet weight
650 kg (excluding the batteries and the built-in transmission
equipment)
Air
conditioner
6100 W (with air conditioner set to cooling function, and without battery
cabinet)
11000 W (with air conditioner set to cooling function, and with battery
cabinet)
6000 W (with air conditioner set to heating function, and without battery
recharging considered)
Power
consumption
(in full
configuration)
Heat
exchanger
4500W (without battery cabinet)
9500W (with battery cabinet)
6000W (heating, without recharging)
Air
conditioner
-40°C to 55°C
Operating
ambient
temperature
Heat
exchanger
-40°C to 45°C
Relative humidity
5% to 100%
Noise
≤
65 dBA (The noise varies with the ambient temperature)
Availability
≥
99.999%
MTBF:
≥
100000 hours
Reliability
MTTR:
≤
1 hour (excluding the time spent on the journey)
MTTR:
≤
3 hours (including the time spent on the journey)
7.2 Capacity Specifications
The maximum capacity of one BTS3606A is six sector carriers. With the multi-carrier
modules, the capacity can reach 18 sector carriers.