E. Condensate Piping
When installing the condensate discharge device in vertically mounted
fan coils, connect the condensate collection tray discharge union
(Figure 18, C) to a pipe (Figure 18, B), and pipe discharge to a drain. The
discharge pipe must be adequately sized (minimum inside diameter
of 0.63 inches).
Figure 18 - Condensate Detail
•
When discharging directly into open drains it is advisable
to make a siphon to prevent odors from the pipe entering
the room. The curve of the siphon must be lower than the
condensate collection orifice.
•
If the condensate is to be discharged into a container, the
pipe must be open to the atmosphere and the terminal must
not be submerged in water to avoid vacuum locks that would
interfere with normal outflow.
Failure to follow these instructions could result in property damage
and WILL VOID product warranty.