HTP SSC-20TC Скачать руководство пользователя страница 10

lp-770 Rev. 000 Rel. 000 Date 6.21.21

10

Part 3 - Piping

When filling the water heater, open a hot water tap to release air in 

the tank and piping. Failure to do so could lead to improper water 

heater operation and damage to components.

E. Boiler Connections

Use a 3/4” nominal minimum pipe size when piping with zone 

valves or circulators.
On the water heater, the boiler supply connects to the outlet of the 

circulator. The circulator inlet is to be connected to the hot outlet 

side of the boiler. Be sure that the arrow on the circulator is facing 

the correct flow direction. (See pressure drop sizing for circulator, 

this manual.) On the tank, the boiler return connects to the return 

side of the boiler. The return(s) from heating loop(s) should have 

a flow check or swing check valve installed before the return pipe 

from the tank.

The water heater heat exchanger cannot be used with non-barrier 

radiant pipe systems. Use with closed loop boiler systems only.

F. Hot Water Outlet

Dielectric fittings must be used on water connections.
Exercise caution when soldering water heater connections, as 

outlet and inlet dip tubes are plastic.

Failure to follow the instructions in this section WILL VOID the 

warranty and may result in property damage, severe personal injury, 

or death.

Do not apply a torch within 12” of the water heater. If sweat 

connections are used, sweat tubing to the adapter before fitting 

adapter to the water connections on the heater. Damages due to 

improper installation practices ARE NOT covered by warranty.

A. General Plumbing Guidelines

Use two wrenches when tightening water piping at heater. Use one 

wrench to prevent the heater inlet or outlet line from turning. Failure 

to prevent piping connections from turning could cause damage to 

heater components.

The building piping system must meet or exceed the piping 

requirements in this manual.

Plumbing of this appliance should only be done by a qualified, licensed 

plumber in accordance with all local plumbing codes. 

Use both thread tape and pipe dope to connect an NPT male X 3/4” 

(minimum) pipe adapter. A shut-off valve between the hot water 

supply and tank outlet is recommended for ease of service. 
Installing a heat trap in the domestic hot water outlet will improve 

energy efficiency and reduce piping heat loss.

All plumbing must be in accordance with the requirements of the 

authority having jurisdiction.

• 

Use both thread tape and pipe dope on all mechanical con-

nections.

• 

Zone valve (if used) and circulator must be sized to provide 

minimum flow rate specified in the table to the right, Flow 

Specifications. Use 1 inch nominal copper tubing for flows 

greater than 7 GPM between the boiler and heat exchanger. 

See the tables on Friction Loss. Point of emphasis: Using a 

zone valve without a full bore may cause high pressure drop 

which will adversely affect performance. Use extreme care 

when selecting zone valve.

• 

All piping must be adequately supported.

• 

Allow for thermal expansion.

• 

Dielectric Unions (recommended) ‐ used to electrically isolate 

the tank from the connected domestic water piping. This 

helps to minimize the possibility of corrosion damage.

Model Recommended 

Flow Rate

Heat Exchanger 

Pressure Drop 

(ft. hd.)

Domestic Water 

Connection 

Sizes

20

5 GPM

1.2

3/4”

32

8 GPM

3.8

40

12 GPM

7.6

50

8.8

Table 10 - Flow Specifications

Tubing Type

Flow Rate 10 GPM

Flow Rate 15 GPM

Type K

3.1 psi

6.5 psi

Type L

2.7 psi

5.7 psi

Type M

2.3 psi

4.7 psi

Table 11 - Friction Loss per 100’ of Tubing (psi)

Fitting

Wrought

Cast

90

o

 Elbow

1

4

45

o

 Elbow

1

2

Tee - Run

1/2

1/2

Tee - Branch

3

5

Long Radius 90

Elbow

2

-

180

o

 Bend

2

-

Gate Valve

-

1

Table 12 - Friction Loss Allowance for Copper Fittings (ft. of Tubing)

C. Potable Expansion Tank

A potable hot water expansion tank may be required to offset heated 

water expansion. If there is a back flow preventer or any other type 

of no return or check valve in the system a thermal expansion tank IS 

MANDATORY. The expansion tank must be sized for the entire water 

volume of the hot water system. A weeping relief valve indicates the 

need for an expansion tank. See the Typical Expansion Tank example in 

the Piping section for details.

B. Backflow Preventer

Use a backflow preventer specifically designed for water heater 

installations. This valve should be installed on the cold water fill supply 

line per local codes.

D. Pressure Drop Sizing For Circulator

The boiler circulator flow rate must meet the requirements found 

in the pressure drop sizing chart. The chart represents the pipe run, 

water heater, and heat exchanger ONLY and does not include any flow 

checks, zone valves, or friction loss through the boiler. That resistance 

must be added to the value found in the following chart.

Содержание SSC-20TC

Страница 1: ... 02745 www htproducts com lp 770 Rev 000 Rel 000 Date 6 21 21 NOTICE HTP reserves the right to make product changes or updates without notice and will not be held liable for typographical errors in literature NOTE TO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation adjustment alteration service or maintenance could void product warranty and cause property da...

Страница 2: ...ment installations the commanding officer or departmental official may be the AHJ NOTE Themanufacturerreservestherighttomodifyproducttechnical specifications and components without prior notice For the Installer This water heater must be installed by qualified and licensed personnel The installer should be guided by the instructions furnished with the water heater and by local codes and utility co...

Страница 3: ... heater DO NOT allow children to operate this unit DO NOT use this unit if it does not appear to be operating correctly A qualified technician should service and inspect the water heater annually This water heater must be installed by a licensed plumber licensed gasfitter and orprofessionalservicetechnician Improperinstallation and or operation can cause a potentially hazardous situation which if ...

Страница 4: ... to treat the water Various solutions are available to adjust water quality Adverse water quality will affect the reliability of the system In addition operating temperatures above 135o F will accelerate the build up of lime scale and possibly shorten appliance service life Failure of an appliance due to lime scale build up low pH or other chemical imbalance IS NOT covered by the warranty The wate...

Страница 5: ...ation company by the consignee Carefully consider installation when determining heater location Please read the entire manual before attempting installation Failure to properly take factors such as heater venting piping condensate removal and wiring into account before installation could result in wasted time money and possible property damage and personal injury This water heater is certified for...

Страница 6: ... where it will not be exposed to freezing temperatures All piping should be insulated Additionally place the water heater so that the drain controls and inlets outlets are easily accessible NOTE To save on heating costs and improve energy efficiency keep the distance between the boiler and water heater to a minimum to reduce heat loss from excess piping and keep friction loss at a minimum Ensure a...

Страница 7: ...mpoo 4 X Hand Dish Washing 4 X Automatic Dish Washing 14 X Food Preparation 5 X Wringer Clothes Washer 26 X Automatic Clothes Washer 32 X Total Peak Hour Demand Table 3 Water Heater Performance and Sizing Guidelines Model Units 20 32 40 50 Tank Capacity Gallons 21 2 31 7 42 3 52 9 Minimum Recommended Power BTU Hr 75 000 95 000 115 000 140 000 Maximum Working Pressure PSI 150 Maximum Temperature oF...

Страница 8: ...nection Diagrams Figure 3 Dimensions Model SSC 20TC SSC 32TC SSC 40TC SSC 50TC A 22 B 28 7 37 45 3 54 C 27 35 3 43 6 52 25 Table 4 Dimensions 2 0 4 0 6 0 8 0 10 0 5 GPM 8 GPM 12 GPM Primary Flow Rate Head Loss FT HD PressureDrop Graph 20 32 40 50 50 32 40 20 Figure 4 Pressure Drop Graph Model Primary Flow Rate GPM Unit 5 8 12 SSC 20TC 1 2 2 9 6 2 ft hd SSC 32TC 1 6 3 8 8 0 SSC 40TC 3 6 7 6 SSC 50T...

Страница 9: ...0 000 188 134 219 155 165 000 236 167 Table 7 32 Gallon Model Performance Data Continuous Draw Ratings Based Upon Boiler s Ability to Maintain 180oF Model 40 Gallon Circulator Flow GPM 5 5 8 8 12 12 DHW Temperature 120oF 140oF 120oF 140oF 120oF 140oF Boiler Heating Capacity in BTU Hr Output 45 000 110 82 110 82 60 000 138 101 138 101 75 000 166 120 166 120 95 000 172 124 192 138 202 145 115 000 17...

Страница 10: ...ergy efficiency and reduce piping heat loss All plumbing must be in accordance with the requirements of the authority having jurisdiction Use both thread tape and pipe dope on all mechanical con nections Zone valve if used and circulator must be sized to provide minimum flow rate specified in the table to the right Flow Specifications Use 1 inch nominal copper tubing for flows greater than 7 GPM b...

Страница 11: ...e discharge to any location where freezing could occur No valve may be installed between the relief valve and heater or in the discharge line Do not plug or place any obstruction in the discharge line Test the operation of the relief valve after filling and pressurizing the system by lifting the lever Make sure the valve discharges freely If the valve fails to operate correctly immediately replace...

Страница 12: ...ir from system 5 This drawing is meant to demonstrate system piping only The installer is responsible for all equipment and detailing required by local codes In Massachusetts you must install a vacuum relief valve per 248 CMR 6 Mixing valve application is optional but recommended to help prevent scalding A B C D E F G H Legend A Ball Valve Typical B Dielectric Union Suggested C Temperature Pressur...

Страница 13: ...d Once the control is operational it is important to make sure the control is maintaining the desired operating temperature B Wiring Wiring is to be done in accordance with all applicable local and state codes Turn off all power related to the boiler before starting any wiring procedures It is recommended that a disconnect switch be installed between the boiler control and the water heater CAUTION...

Страница 14: ...l 000 Date 6 21 21 14 Figure 8 Zoning with Circulators R8182D and R845A Relay Figure 9 Zoning with Circulators Using L8124 E F and R845A Relay Figure 10 Using L8148A or L8152A Cold Start Boiler Control with Circulators ...

Страница 15: ...a thermostatic mixing valve be used to protect the user from potential hazard due to spikes in temperature A mixing valve in conjunction with a high temperature setting may be used for high demand applications spas hot tubs whirlpools It is important to check the output temperature of any water heater with a thermometer to insure that the setting is correct 6 When the system is completely flushed ...

Страница 16: ...omestic cold water supply valve 3 Open the household hot water taps 4 Attach a hose to the drain valve located at the bottom of the heater and drain the heater 5 Unscrew the anodes EXAMINE THE ANODES AND REPLACE IF THE DIAMETER IS LESS THAN 0 40 INCHES 6 Replacement of the Anodes The use of PTFE tape is recommended to ensure watertight connection of the anodes NOTE Some water conditions may necess...

Страница 17: ...ischarges Hot Tubs Spas Multiple Showers High Demand Problem Possible Solution Problem Possible Solution Tank temperature too high Lower tank temperature Pressure too low Check line pressure for restriction Water expands when heated Install expansion tank Tank recovery slow Slow startup boiler See chart Water pressure too high Install pressure reducing valve Not enough hot water Boiler sized too s...

Страница 18: ...pressly agreed between HTP and the Owner that repair replacement or refund are the exclusive remedies of the Owner OWNER RESPONSIBILITIES The Owner or Installer must 1 Have a relief valve bearing the listing marks of the American Society of Mechanical Engineers ASME installed with the water heater assembly in accordance with federal state and local codes 2 Have a vacuum relief valve certified to A...

Страница 19: ...on is required and requested by the HTP Claims Departmentyouwillhavethirty 30 daystoprovideit Whenallrequested information is provided HTP will respond within three 3 business days The claim will be automatically closed if requested information is not provided within thirty 30 days Claims will not be reopened without HTP Warranty Supervisor approval During the claims process a product that must be...

Страница 20: ...te of Installation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer IMPORTANT Customer Please only sign after the qualified installer service technician has fully reviewed the installation safety proper operation and maintenance of the system If the system has any problems please call the qualified insta...

Отзывы: