After final adjustment, tighten lock screws on the air inlet, let unit cool and restart burner to be sure burner 
operates on a cold start. Remove the pressure gauge and install pipe plug. 

D. DRAFT 

 
Adjust the draft regulator so that there is -.01" to -.04" draft over the fire, maximum. Take readings and 
adjust air so that a minimum of 9 1/2% CO

2

 is obtained with a smoke reading between 0 and 1. 

 
Draft reading in the stack should be -.02" to -.05". High Draft may be caused by over firing or too much 
excess air. 
 

DO NOT

 

OPERATE

 the burner if there is back draft caused by down draft. Back pressure (back draft or 

down draft) may also be caused by the chimney termination being lower in elevation than surrounding 
objects, such as buildings, hills, trees, rooftops, etc. Back pressure may be caused by an exhaust fan in 
the building. Correct this situation before operating the burner. 

E. NOZZLE (OIL INPUT) VARIATIONS 

 
Fuel oils vary greatly. Because of this, nozzles will not always deliver the gallons per hour or angle of 
spray indicated on the nozzle. In addition, it has been found that in certain areas, due to local conditions, 
nozzles other than those furnished as original equipment offer better performance due to the type of oil 
being delivered. Oil service personnel will carry several nozzles of different manufacture, angles and 
spray types in order to obtain the most suitable performance for the particular application. 

PART 14: IMPORTANT INSTALLATION AND MAINTENANCE 
REMINDERS 

A. INSTALLATION 

 

1. Install all electrical work in strict accordance with local codes and ordinances. 
2. All unions must be of the ground seat type. 
3. When the tank is below the burner, a check valve must be installed in the suction line to 
prevent oil from returning to the storage tank when unit is not in operation. 
4. Bleed the pump and make sure oil is clear of air bubbles. If frothy, check lines for air leaks at 
fittings. Check the oil filter gaskets and make sure filter cartridge is clean. 
5. Set the draft to a range of -.02" to -.05". 
6. See that the smoke pipe enters the chimney far enough to be tight and not so far as to reduce 
flue area. It should end flush with the inside of the chimney. 
7. There must be at least -.01" draft over the fire. 
8. Make certain there is no backpressure such as down draft or back draft. 
9. There must be sufficient air in heater room for proper combustion at all times. 
10. Explain the operation of the burner to the owner. 
11. Show owner how to operate controls and main cutout switch. 
12. Hang burner-operating instructions as supplied with burner in prominent place near 
installation. 

B. MAINTENANCE 

 

1. Make sure that the flue and venting system is checked at least once a year by a plumbing 
professional or the oil supplier's service technicians. 
2. The tank should be inspected every six months for LIME AND SEDIMENT accumulations. If 
lime or sediment is present, remove by scraping or with chemical lime remover. 

Содержание OFT-30

Страница 1: ...Freetown MA 02717 0429 www htproducts com Oil Fired Water Heater INSTALLATION MANUAL NOTICE HTP reserves the right to make product changes or updates without notice and will not be held liable for typ...

Страница 2: ...ially hazardous situation which if not avoided may result in property damage FOREWORD This manual is intended to be used in conjunction with other literature provided with the heater This includes pow...

Страница 3: ...given to codes and requirements where they differ from the heater furnished instructions Additional publications which should guide the installer include The latest version of the National Fuel Gas C...

Страница 4: ...CE 9 B CONFINED SPACE 9 PART 7 THERMAL EXPANSION CLOSED SYSTEMS 10 PART 8 VENTING 10 A VENT CONNECTOR 11 B BAROMETRIC DRAFT CONTROL ASSEMBLY 11 PART 9 ELECTRICAL CONNECTIONS 12 PART 10 WATER CONNECTIO...

Страница 5: ...ing shutdown periods B CHEMICAL VAPOR CORROSION Corrosion of the flueways and vent system may occur if combustion air contains certain chemical vapors which break down into acids at high temperature S...

Страница 6: ...nutes before using any electrical appliance connected to the hot water system THERE MUST BE NO SMOKING OR FLAME NEAR THE OPEN FAUCET If hydrogen is present there will probably be an unusual sound such...

Страница 7: ...he floor This may reduce the risk of ignition In these circumstances the heater must be located or protected so it is not subject to physical damage by a moving vehicle Flammable items pressurized con...

Страница 8: ...st the heater use metal shims under the channel type skid base B CLEARANCES Provide ample clearance on all sides for installation adjustment and replacement of burner control components and other serv...

Страница 9: ...INCHES OF THE TOP ENCLOSURE AND ONE IN OR WITHIN 12 INCHES OF THE BOTTOM ENCLOSURE Each opening shall have a free air area of at least one square inch per 1000 BTU hr of the total input of all applian...

Страница 10: ...f water Service problems or parts failure due to excessive pressure ARE NOT covered under warranty The temperature and pressure relief valve supplied with the water heater IS NOT considered to be prot...

Страница 11: ...ween the heater and chimney opening The connector length should be kept as short as possible B BAROMETRIC DRAFT CONTROL ASSEMBLY A double acting barometric draft control assembly is necessary for this...

Страница 12: ...it conductors and connected to the equipment grounding terminal or lead on the water heater If any of the original wiring must be replaced replacement shall be with 105 degree C wire or equivalent Fig...

Страница 13: ...cumstances PART 11 OIL LINE CONNECTIONS A SINGLE LINE SYSTEM NOTE NOT RECOMMENDED WHEN IT IS NECESSARY TO LIFT THE OIL This type of installation is used where the oil storage tank is above the burner...

Страница 14: ...be used Avoid as many connections as possible in the suction line Make all connections tight by using good pipe joint compound for oil on all pipe threads To minimize the possibility of air leaks tigh...

Страница 15: ...water system This valve will reduce water temperature by mixing cold and hot water in branch water lines Such valves are available from your local plumbing supplier Consumer Please consult your water...

Страница 16: ...most suitable performance for the particular application PART 14 IMPORTANT INSTALLATION AND MAINTENANCE REMINDERS A INSTALLATION 1 Install all electrical work in strict accordance with local codes an...

Страница 17: ...ded to about a third of its diameter it should be replaced 4 Open the relief valve at least once annually to make sure it is not stuck CAUTION RELEASED WATER MAY BE HOT Do not attempt to start the bur...

Страница 18: ...18 PART 15 REPLACEMENT PARTS Figure 5 LP 340 REV 7 13 10...

Отзывы: