oil to the oil storage tank during the burner off cycle period. Do not run suction or return line overhead, as 
this greatly increases the possibility of air pockets, oil leaks, siphoning and transmission of noise. 
 
When the top of the oil storage tank is above the fuel unit and a gravity feed is not permitted, the suction 
line should run to a point above the tank where an approved anti-siphon valve and a 5/8" OD gate valve 
shall be installed inside. No ball check valve is required, but a union between the gate valve and the 
strainer should be installed to facilitate removal of the strainer for occasional cleaning.  

D. RETURN LINE 

 
The return line should be the same size as a suction line and run as directly as possible from the return 
opening in the fuel unit to the oil storage tank. The return line should extend into the oil storage tank to 
the same depth as the suction line. 

E. PRESSURE TEST FOR BURIED OIL LINES 

 
It is important that buried oil lines be thoroughly tested for leaks before being covered. 

F. MISCELLANEOUS INFORMATION 

 
If suction and return lines are less than 30 feet in length, use at least 1/2" OD tubing. When the oil line is 
30 feet or over, 5/8" OD tubing is recommended. 
 
Where basement oil storage tanks or tanks installed above the burner are used, and/or when the oil flows 
by gravity to the oil pump, a single-stage fuel unit with a single oil line to the pump may be used. Avoid as 
many connections as possible in the suction line. Make all connections tight by using good pipe joint 
compound for oil on all pipe threads. To minimize the possibility of air leaks, tighten packing gland on any 
valve installed in the suction line. Also, be sure to tighten the oil filter cover, as filter gaskets often shrink. 
Check for kinks in the oil lines as well as for possible air pockets and loose connections. 
 
A water trap can be installed at the oil storage tank outlet to prevent water from entering the burner. 
There are a number of fuel oil additives on the market that hold water in suspension and allow it to pass 
through the burner. These additives can be added to the oil storage tank. Consult a local fuel oil dealer for 
information concerning the use of these additives. 
 

PART 12: PRIMING THE FUEL UNITS 

 

 

DO NOT USE GASOLINE, CRANKCASE DRAININGS, OR ANY OIL CONTAINING GASOLINE. 

A. SINGLE LINE SYSTEM

 

 
Locate the air bleed valve on the fuel unit (pump). Place a container underneath the air bleed valve. Open 
the valve one quarter of a turn in the counter-clockwise direction. Turn the thermostat on the water heater 
to a setting that is high enough to allow the burner to operate. Turn on the power supply to the burner. 
 
Let at least one pint of oil flow into the container after the air is pumped out of the fuel unit. While running 
under these conditions, the pressure valve in the pump will not open, and there will be no flame. Close 
the air bleed valve after a pint of oil has flowed into the container. The burner should begin burning once 
the air bleed valve is closed. 

Содержание OFT-30

Страница 1: ...Freetown MA 02717 0429 www htproducts com Oil Fired Water Heater INSTALLATION MANUAL NOTICE HTP reserves the right to make product changes or updates without notice and will not be held liable for typ...

Страница 2: ...ially hazardous situation which if not avoided may result in property damage FOREWORD This manual is intended to be used in conjunction with other literature provided with the heater This includes pow...

Страница 3: ...given to codes and requirements where they differ from the heater furnished instructions Additional publications which should guide the installer include The latest version of the National Fuel Gas C...

Страница 4: ...CE 9 B CONFINED SPACE 9 PART 7 THERMAL EXPANSION CLOSED SYSTEMS 10 PART 8 VENTING 10 A VENT CONNECTOR 11 B BAROMETRIC DRAFT CONTROL ASSEMBLY 11 PART 9 ELECTRICAL CONNECTIONS 12 PART 10 WATER CONNECTIO...

Страница 5: ...ing shutdown periods B CHEMICAL VAPOR CORROSION Corrosion of the flueways and vent system may occur if combustion air contains certain chemical vapors which break down into acids at high temperature S...

Страница 6: ...nutes before using any electrical appliance connected to the hot water system THERE MUST BE NO SMOKING OR FLAME NEAR THE OPEN FAUCET If hydrogen is present there will probably be an unusual sound such...

Страница 7: ...he floor This may reduce the risk of ignition In these circumstances the heater must be located or protected so it is not subject to physical damage by a moving vehicle Flammable items pressurized con...

Страница 8: ...st the heater use metal shims under the channel type skid base B CLEARANCES Provide ample clearance on all sides for installation adjustment and replacement of burner control components and other serv...

Страница 9: ...INCHES OF THE TOP ENCLOSURE AND ONE IN OR WITHIN 12 INCHES OF THE BOTTOM ENCLOSURE Each opening shall have a free air area of at least one square inch per 1000 BTU hr of the total input of all applian...

Страница 10: ...f water Service problems or parts failure due to excessive pressure ARE NOT covered under warranty The temperature and pressure relief valve supplied with the water heater IS NOT considered to be prot...

Страница 11: ...ween the heater and chimney opening The connector length should be kept as short as possible B BAROMETRIC DRAFT CONTROL ASSEMBLY A double acting barometric draft control assembly is necessary for this...

Страница 12: ...it conductors and connected to the equipment grounding terminal or lead on the water heater If any of the original wiring must be replaced replacement shall be with 105 degree C wire or equivalent Fig...

Страница 13: ...cumstances PART 11 OIL LINE CONNECTIONS A SINGLE LINE SYSTEM NOTE NOT RECOMMENDED WHEN IT IS NECESSARY TO LIFT THE OIL This type of installation is used where the oil storage tank is above the burner...

Страница 14: ...be used Avoid as many connections as possible in the suction line Make all connections tight by using good pipe joint compound for oil on all pipe threads To minimize the possibility of air leaks tigh...

Страница 15: ...water system This valve will reduce water temperature by mixing cold and hot water in branch water lines Such valves are available from your local plumbing supplier Consumer Please consult your water...

Страница 16: ...most suitable performance for the particular application PART 14 IMPORTANT INSTALLATION AND MAINTENANCE REMINDERS A INSTALLATION 1 Install all electrical work in strict accordance with local codes an...

Страница 17: ...ded to about a third of its diameter it should be replaced 4 Open the relief valve at least once annually to make sure it is not stuck CAUTION RELEASED WATER MAY BE HOT Do not attempt to start the bur...

Страница 18: ...18 PART 15 REPLACEMENT PARTS Figure 5 LP 340 REV 7 13 10...

Отзывы: