7
LP-362 Rev. 7.30.20
Do not use PVC pipe cement to connect the Polypro to PVC adapter. Use of PVC pipe cement will lead to
failure of the adapter, resulting in an exhaust gas leak which will cause property damage, severe personal
injury, or death.
Be certain to properly secure the Polypro to PVC adapter. Failure to do so will lead to an exhaust gas leak,
resulting in property damage, severe personal injury, or death.
Failure to properly pitch venting system could cause condensate to collect and pool, resulting in venting system
failure, property damage, severe personal injury, or death.
15. At the top of the shaft, shorten the flexible liner to the required
length and make sure that dimension B in Fig. 11 is between 1.6 and
2.4” (40 and 60 mm).
16. Fit the support cross (see Fig.
11, 1) over the liner and let it rest on
the wall of the shaft. Mount the
seal in the last whole groove of the
liner. Push the flex-rigid adaptor
on the liner and close the latching
tabs. Allow the assembly to rest
on the support cross.
17. Seal the edge of the chimney or chase shaft with water-resistant sealant (see Fig. 12, 1) and push the
weather collar (2) on the shaft. Fix the collar with four screws (3).
Figure 11 – Required Liner Length at Shaft
Top
Figure 12 – Installing the Weather Collar