LP-362 Rev. 7.30.20 

 

 

 

 

5. Mount the seal into the lowest whole groove (Fig. 3) and push the flexible 

liner into the adapter until it stops. 

Figure 3 – Mounting the Seal

 

 

 

 

 

6. Fix the adapter on the liner with the latching tabs (Fig. 4). 

 

 

 

 

 

 

 

7. It is possible to loosen the latching tabs with a screw driver. See Fig. 5. 

 

8. Mount the flexible spacer brackets with a maximum distance of 6 feet (2 

m) between each. 

 

 

 

 

9. The optional pull cone installation aid (Part #8400P-

013) must be connected using a 

bayonet connection with a rotating movement of ¼ turn 

to the right (+). Install the liner 

from the top. See Fig. 6. 

 

10. The flexible liner must be installed from the top of 

the shaft into the installation 

room. To prevent damage to the liner, a second person 

must guide the liner from the top 

in the middle of the shaft. 

 

11. After installing the required length of liner, remove the mounting aid by rotating ¼ turn counterclockwise (-). 

Then attach the rigid-flex adapter into the support bend. See Fig. 7. 

 

a. Position the support elbow on the support bracket (see 2 and 3, Fig. 7). 

b. Secure the support elbow with the clamp (see 1, Fig. 8) around the flex-rigid adaptor (see 1, fig 7) and 

through the slot of the support console (see 4, Fig. 7). 

Figure 4 – Fixing the Adapter

 

Figure 5 – Loosening the 

Latching Tabs 

 

 

Figure 6 – Pull Cone

 

Figure 2 – Coupling

 

Содержание 8400P-001

Страница 1: ...he safety alert symbol indicates a potentially hazardous situation which if not avoided may result in property damage INTRODUCTION This instruction manual is for use only with appliances that have been certified to use a Polypropylene ventilation system Installing any other appliance with this system will result in property damage severe personal injury or death SAFETY CONSIDERATIONS Prior to inst...

Страница 2: ...th A APPLICATION The maximum positive pressure of the flexible vent kit is 8 w c The maximum flue gas temperature of the appliance must be not more than 230oF 110oC ULC S636 Class IIC This vent kit must only be used in vertical system designs An existing chimney or chase must be used to route the flexible venting system To prevent condensate from pooling in the vent flex pipe is not to bend more t...

Страница 3: ...rned off and the leaks repaired No other appliance may be vented into the same chimney or chase flue with the flexible venting system Failure to heed this warning could result in property damage personal injury or death Plastic venting systems shall not pass through rated fire separations The distance between the point of termination of the system must be 6 2 m or more from the combustion air inle...

Страница 4: ... mounting instructions at the end of this manual E INSTALLATION Special notes The flexible liner must be treated carefully at low temperatures 5oC 41oF Check all parts for possible shipping damage Rotate the components slightly to assist assembly Installation procedure for flexible flue liners 1 Determine the required location of the opening in the shaft Ensure the flue access cut out meets the mi...

Страница 5: ...tall the liner from the top See Fig 6 10 The flexible liner must be installed from the top of the shaft into the installation room To prevent damage to the liner a second person must guide the liner from the top in the middle of the shaft 11 After installing the required length of liner remove the mounting aid by rotating turn counterclockwise Then attach the rigid flex adapter into the support be...

Страница 6: ...orrect version of the shaft connector to the wall plate see Fig 9 1 or 2 15 When installing the Polypro to PVC adapter first connect the adapter by pushing it onto the Polypro pipe Be certain that the arrow on the adapter is facing up Next slide the PVC CPVC pipe into the adapter Use a flathead screwdriver to tighten the adapter to the pipe Once the adapter is connected be certain that it pitches ...

Страница 7: ...failure property damage severe personal injury or death 15 At the top of the shaft shorten the flexible liner to the required length and make sure that dimension B in Fig 11 is between 1 6 and 2 4 40 and 60 mm 16 Fit the support cross see Fig 11 1 over the liner and let it rest on the wall of the shaft Mount the seal in the last whole groove of the liner Push the flex rigid adaptor on the liner an...

Страница 8: ... connector To assure proper drainage of condensate make sure that the arrow on the transition connector is facing up Make sure that the pipe is fully inserted into the connector before tightening the clamps on either end of the connector to fully secure the pipe on both ends 20 Once connected operate appliance Inspect for leaks and test for proper operation 21 Instruct the owner in proper maintena...