background image

 

 

 

 

LP-362 Rev. 7.30.20 

 

connection between the appliance and the flexible vent must be done with a rigid vent system. Follow the 

specific instructions supplied with these products. 

 

  Common venting of more than one appliance is not allowed. 

  No other gas-burning appliance may be vented in the same chase/chimney with the flexible vent system. 

  The maximum length, correct diameter, and number of fittings must be in conformance with the 

specifications of the appliance manufacturer’s instructions. 

  The venting systems must be installed with correct distance to combustibles. 

  Check for proper joint construction. 

 

Additional instructions for termination:

 

  The vent system must terminate at least 2’ (0.6 m) above the roof line or any wall or vertical structure 

within 10’ (3 m). 

  Do not install an extra rain cap on the terminal. The terminals are specially designed for high efficiency 

boilers which produce large quantities of moisture due to condensation of combustion gases. This design 

allows rain to enter the terminals which also serves to dilute acidic condensate. 

  Follow the specific mounting instructions at the end of this manual. 

E. INSTALLATION 

 

Special notes: 

  The flexible liner must be treated carefully at low temperatures (<5

o

C) (<41

o

F).

 

  Check all parts for possible shipping damage.

 

  Rotate the components slightly to assist assembly.

 

 

Installation procedure for flexible flue liners: 

1. Determine the required location of the opening in the shaft. Ensure the flue access cut-out meets the minimum 

specified size to allow manual assembly of connections within the flue. The slope of the connecting flue pipe must 

have a minimum of 3

o

 (equivalent 1.9”/ft.) (5cm/m).

 

 

2. Fix the elbow support bracket (Fig. 1) with 4 screws on the wall of the chimney 

or chase. 

 

3. The length of the flexible liner can be determined in two ways: 1) Use a rope 

with a small weight on the end to measure shaft length. Add 16 inches (.4 m) 

extra length for each bend. The flexible liner can be shortened with a saw or 

scissors by cutting in a groove. 2) Correct liner length can also be determined 

after installing the liner in 

the shaft and cutting it as 

the top of the chimney or 

chase (see Fig. 10, 

Dimension B). 

 

 

 

 

 

4. When required, a coupling (Fig. 2) can also be used to 

connect two lengths of 

flexible liner together. This piece can be ordered as an 

accessory (Part #8400P-

005). 

Figure 1 – Fixing the Support 

Bracket

 

Содержание 8400P-001

Страница 1: ...he safety alert symbol indicates a potentially hazardous situation which if not avoided may result in property damage INTRODUCTION This instruction manual is for use only with appliances that have been certified to use a Polypropylene ventilation system Installing any other appliance with this system will result in property damage severe personal injury or death SAFETY CONSIDERATIONS Prior to inst...

Страница 2: ...th A APPLICATION The maximum positive pressure of the flexible vent kit is 8 w c The maximum flue gas temperature of the appliance must be not more than 230oF 110oC ULC S636 Class IIC This vent kit must only be used in vertical system designs An existing chimney or chase must be used to route the flexible venting system To prevent condensate from pooling in the vent flex pipe is not to bend more t...

Страница 3: ...rned off and the leaks repaired No other appliance may be vented into the same chimney or chase flue with the flexible venting system Failure to heed this warning could result in property damage personal injury or death Plastic venting systems shall not pass through rated fire separations The distance between the point of termination of the system must be 6 2 m or more from the combustion air inle...

Страница 4: ... mounting instructions at the end of this manual E INSTALLATION Special notes The flexible liner must be treated carefully at low temperatures 5oC 41oF Check all parts for possible shipping damage Rotate the components slightly to assist assembly Installation procedure for flexible flue liners 1 Determine the required location of the opening in the shaft Ensure the flue access cut out meets the mi...

Страница 5: ...tall the liner from the top See Fig 6 10 The flexible liner must be installed from the top of the shaft into the installation room To prevent damage to the liner a second person must guide the liner from the top in the middle of the shaft 11 After installing the required length of liner remove the mounting aid by rotating turn counterclockwise Then attach the rigid flex adapter into the support be...

Страница 6: ...orrect version of the shaft connector to the wall plate see Fig 9 1 or 2 15 When installing the Polypro to PVC adapter first connect the adapter by pushing it onto the Polypro pipe Be certain that the arrow on the adapter is facing up Next slide the PVC CPVC pipe into the adapter Use a flathead screwdriver to tighten the adapter to the pipe Once the adapter is connected be certain that it pitches ...

Страница 7: ...failure property damage severe personal injury or death 15 At the top of the shaft shorten the flexible liner to the required length and make sure that dimension B in Fig 11 is between 1 6 and 2 4 40 and 60 mm 16 Fit the support cross see Fig 11 1 over the liner and let it rest on the wall of the shaft Mount the seal in the last whole groove of the liner Push the flex rigid adaptor on the liner an...

Страница 8: ... connector To assure proper drainage of condensate make sure that the arrow on the transition connector is facing up Make sure that the pipe is fully inserted into the connector before tightening the clamps on either end of the connector to fully secure the pipe on both ends 20 Once connected operate appliance Inspect for leaks and test for proper operation 21 Instruct the owner in proper maintena...

Страница 9: ...9 LP 362 Rev 7 30 20 Figure 14 Flex Vent Parts List ...

Отзывы: