LP- 446 REV. 9.3.14
PART 12 – MAINTENANCE
A. MAINTENANCE PROCEDURES
Periodic maintenance should be performed once a year by a qualified service technician to assure that all the equipment is operating
safely and efficiently. The owner should make necessary arrangements with a qualified heating contractor for periodic maintenance of
the heater. The installer must also inform the owner that a lack of proper care and maintenance of the heater may result in a hazardous
condition.
BEFORE EACH HEATING SEASON a trained and qualified service technician should perform the inspections as per the heater
inspection and maintenance schedule in the back of the manual. Failure to do so could result in death or serious injury.
The combustion chamber insulation in this product contains ceramic fiber material. Ceramic fibers can be converted to
cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded,
“Crystalline silica inhaled in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group
1).”
Avoid breathing dust and contact with skin and eyes.
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite
at the time this document was written. Other types of respirators may be needed depending on job site conditions.
Current NIOSH recommendations can be found on the NIOSH website: http://www.cdc.gov/niosh/homepage.html.
NIOSH approved respirators, manufacturers, and phone numbers are also listed on this website.
Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Apply enough water to the combustion chamber lining to prevent dust.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately.
Breathing: Fresh air.
Outdoor Sensor (7250P-319)
Supply Temperature Sensor (7250P-324)
Heater Sensor (7250P-667)
Indirect Sensor (7250P-325)
Outside Temperature (
o
F)
Resistance (ohms)
Outside Temperature (
o
F)
Resistance (ohms)
-22
171800
32
32550
-13
129800
41
25340
-4
98930
50
19870
5
76020
59
15700
14
58880
68
12490
23
45950
77
10000
32
36130
86
8059
41
28600
95
6535
50
22800
104
5330
59
18300
113
4372
68
14770
122
3605
77
12000
131
2989
86
9804
140
2490
95
8054
149
2084
104
6652
158
1753
113
5522
167
1481
176
1256
185
1070
194
915
203
786
212
667
Table 28
– Resistance Tables
Содержание 500 HL
Страница 12: ...12 LP 446 REV 9 3 14 Figure 2 Dimensions and Specifications ...
Страница 21: ...21 LP 446 REV 9 3 14 H PIPING DIAGRAMS Figure 6 ...
Страница 44: ...44 LP 446 REV 9 3 14 E GAS VALVE Figure 26 Mod Con 500 Gas Valve ...
Страница 52: ...52 LP 446 REV 9 3 14 Figure 33 Mod Con Internal Connection Diagram LP 428 K ...
Страница 71: ...71 LP 446 REV 9 3 14 Figure 36 ...
Страница 72: ...72 LP 446 REV 9 3 14 Figure 37 ...
Страница 73: ...73 LP 446 REV 9 3 14 Figure 38 ...
Страница 74: ...74 LP 446 REV 9 3 14 Figure 39 ...
Страница 77: ...77 LP 446 REV 9 3 14 ...
Страница 78: ...78 LP 446 REV 9 3 14 ...
Страница 79: ...79 LP 446 REV 9 3 14 MAINTENANCE NOTES ...